General Information
22
MGG100M Operating Manual
36833 C
GenLink DCP: Dual Fuel Setup and Operation
The Dual Fuel Setup page in GenLink provides flexibility in controlling the operation of the fuel source switching.
There are four modes of operation: default, digital pressure, analog pressure, and digital and analog pressure.
The default dual-fuel setup setting is analog.
shows default analog settings.
Figure 14 - Dual Fuel Setup Page (Analog Pressure)
The unit owner has access to GenLink and can affect changes to dual-fuel setup.
Rooftop Beacon
The rooftop beacon indicates what fuel source is currently in use. See table below.
Low Fuel Pressure Warning
The NG fuel system is equipped with a low fuel pressure warning; the LPL fuel system is not.
If input pressure in the NG fuel line drops below 30 PSI (207 kPa) for a certain time frame, the unit attempts to switch
to the LPL fuel source. Almost immediately after the switch, a warning activates and the controller displays message
FUEL PRESS Lo (
). The warning stops when NG input pressure rises to or above 30 PSI (207 kPa).
Resetting the controller is unnecessary. See
for more information.
Figure 15 - Low NG Fuel Pressure
Beacon Color
Indicates Fuel Source Is
Green
Primary (NG)
Red
Secondary (LPL)
02258
02227
Wr*DI12/FUEL PRESS Lo
n/a
n/a
A
CK MORE<-->(1-3)
Summary of Contents for Magnum MGG100M
Page 4: ...This Page Intentionally Left Blank 36833 C MGG100M Operating Manual iv...
Page 8: ...This Page Intentionally Left Blank 36833 C MGG100 Operating Manual viii...
Page 14: ...Safety 6 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Page 52: ...Operation 44 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Page 76: ...Wiring Diagrams 68 MGG100M Operating Manual 36833 C This Page Intentionally Left Blank...
Page 83: ......