General Information
Owner’s Manual for Australian 50 Hz Air-Cooled Generators
11
Protection Systems
The generator set may need to run for long periods of
time with no operator present to monitor engine/genera-
tor set conditions. The generator set is equipped with
protection systems to automatically shut down unit to
protect against potentially damaging conditions. Some of
these systems include:
Alarms
:
Warnings:
The control panel contains a display which alerts the
operator when a fault condition occurs. The above list is
not all inclusive. See
about alarms and control panel operation.
NOTE:
A warning will indicate a condition on the genera-
tor set that should be addressed, but will not shut down
the unit. An alarm will shut down the unit to protect sys-
tem from any damage. In the event of an alarm, a user
can clear the alarm and restart the unit prior to contacting
an IASD. Contact an IASD if the intermittent issue per-
sists.
Emission Information
The engine used in this generator set is not certified to
United States EPA emission standards, or any other
emission standards. Sale or use of this generator set is
not legal in the U.S or any country which has emission
standards applicable to this product.
Fuel Requirements
The engine has been fitted with a dual fuel carburetion
system. The unit will run on NG or LP gas, but it has been
factory set to run on NG. The fuel system will be config-
ured for the available fuel source during installation.
BTU Content
Recommended fuels should have a MJ (BTU) content of
at least 37.26 MJ/m
3
(1,000 BTU/ft
3
) for NG, or at least
93.15 MJ/m
3
(2,500 BTU/ft
3
) for LP gas.
NOTE:
If converting to LP gas from NG, a minimum LP
tank size of 946 L (250 gal) is recommended. See instal-
lation manual for complete procedures and details.
NOTE:
Some regions require installation of an auxiliary
fuel field install kit. If kit is required, see installation man-
ual for information on how to purchase and install parts.
Battery Requirements
12 volts, Group 26R 540CCA minimum or Group 35 AGM
650CCA minimum (not included with unit.) See
for correct battery maintenance procedures.
Battery Charger
The battery charger is integrated into the control panel
module in all models. It operates as a smart charger,
which verifies output charging levels are safe and contin-
uously optimized to promote maximum battery life.
NOTE:
Do not use external battery chargers.
Engine Oil Requirements
See
.
Activating the Generator Set
Generator set should be activated upon initial startup.
See installation manual for more information.
Wi-Fi Module
Generator set is equipped with a Wi-Fi module. See Wi-
Fi module owner’s manual for more information.
•
High Temperature
•
Low Oil Pressure
•
Overcrank
•
Overspeed
•
Overvoltage
•
Undervoltage
•
Overload
•
Underspeed
•
Rpm Sensor Loss
•
Controller Fault
•
Wiring Error
•
Stepper Overcurrent
•
Charger Warning
•
Charger Missing AC
•
Low Battery
•
Battery Problem
•
Exercise Set Error
•
USB Warning
•
Download Failure
(000105)
Explosion and Fire. Fuel and vapors are extremely
flammable and explosive. Add fuel in a well
ventilated area. Keep fire and spark away. Failure
to do so will result in death or serious injury.
DANGER