Maintenance

24

Owner’s Manual for Australian 50 Hz Air-Cooled Generators

8.

Press MANUAL button on control panel to start
engine. Run for one minute, and inspect for leaks.

9.

Press OFF button on control panel to stop engine.
Wait five minutes.

10.

Check oil level. Add oil as needed. DO NOT
OVERFILL.

11.

Insert oil dipstick and/or attach oil fill cap.

12.

Press AUTO button on control panel to return unit
to AUTO.

13.

Close and lock lid.

14.

Dispose of used oil and filter according to local,
state, or national codes.

Servicing the Air Cleaner

Proceed as follows to service air cleaner:

1.

Lift lid and press OFF button on control panel to
stop generator set.

2.

Remove front panel.

3.

See 

Figure 4-2

. Remove cover clips (A) and air

cleaner cover (B).

Figure 4-2. Servicing Air Cleaner

4.

Remove air filter element (C) and discard.

5.

Thoroughly clean air cleaner enclosure of any dust
or debris.

6.

Install a new air filter element.

7.

Install air cleaner cover and fasten cover clips.

8.

Verify air inlet duct (D) is correctly connected to air
cleaner cover.

9.

Press AUTO button on control panel to return unit
to AUTO.

Spark Plug(s)

Proceed as follows to inspect spark plug gap(s) and
replace spark plug(s) as necessary:

1.

With generator set OFF and engine cool, lift lid and
remove front panel.

2.

Clean area around base of spark plug(s) to keep
dirt and debris out of engine.

3.

Remove spark plug(s) and inspect condition. Install
a new plug(s) if old plug(s) is worn or if reuse is
questionable. 

4.

Clean spark plug(s) by scraping or washing with a
wire brush and commercial solvent. Do not blast
spark plug(s) to clean.

NOTE: 

Clean spark plug(s) in emergency situations only.

Otherwise, replace spark plug(s).

5.

See 

Figure 4-3

. Inspect spark plug gap using a

wire feeler gauge. Replace spark plug if spark plug
gap is out of specification. See 

General Informa-

tion

.

Figure 4-3. Spark Plug Gap Measurement

NOTE: 

Inspect spark plug gap on new spark plugs prior

to installation.

6.

Install spark plug(s) and tighten to 25 Nm (18.4 ft-
lbs).

7.

Press AUTO button on control panel to return unit
to AUTO.

(000249)

WARNING

Risk of fire. Never operate engine without the 
air cleaner installed. Operating engine without 
the air cleaner could result in death or serious 
injury.

(000580)

WARNING

Explosion and fire. Never clean air filter element 
with gasoline or low flash-point detergents. Doing 
so could result in death, serious injury, or 
equipment damage.

001814

B

A

C

D

001814

(000140a)

WARNING

Electric shock. Do not disconnect spark 
plug wires with engine running. Doing so 
could result in death or serious injury.

000211

Summary of Contents for 10 KVA

Page 1: ...HIS MANUAL FOR FUTURE REFERENCE Register your Generac product at www generac com au 61 2 8106 3100 000209b WARNING Loss of life This product is not intended to be used in a critical life support appli...

Page 2: ...r of problems and keeps operating expenses at a minimum It is the operator s responsibility to perform all safety inspections to verify all maintenance for safe operation is performed promptly and to...

Page 3: ...anel Interface 15 Using the Control Panel Interface 15 Interface Menu Displays 15 LCD Panel 15 Menu System Navigation 16 Setting the Exercise Timer 18 Battery Charger 18 Operating Modes 19 Transfer Sw...

Page 4: ...Table of Contents iv Owner s Manual for Australian 50 Hz Air Cooled Generators This page intentionally left blank...

Page 5: ...INSTRUCTIONS for future reference This manual contains important instructions that must be fol lowed during placement operation and maintenance of the unit and its components Always supply this manual...

Page 6: ...tive battery cable then the positive battery cable when working on unit Failure to do so could result in death or serious injury WARNING 000182a WARNING Equipment damage Only qualified service personn...

Page 7: ...facturer s instructions Failure to do so could result in death or serious injury 000146 WARNING Equipment and property damage Do not alter construction of installation or block ventilation for generat...

Page 8: ...ipment required when working with a live electrical system Failure to use required safety equipment could result in death or serious injury 000257 000147 WARNING Risk of Fire Unit must be positioned i...

Page 9: ...Failure to do so could result in death or serious injury 000138a WARNING Risk of burns Batteries contain sulfuric acid and can cause severe chemical burns Wear protective gear when working with batter...

Page 10: ...Safety Rules General Information 6 Owner s Manual for Australian 50 Hz Air Cooled Generators This page intentionally left blank...

Page 11: ...r F Exhaust enclosure L Composite base Q Fuel regulator vents 2 B Main line circuit breaker MLCB generator set disconnect G Status LED indicators M Oil dipstick R Wi Fi module C Airbox with air cleane...

Page 12: ...losure L Composite base P Fuel inlet B MLCB generator set disconnect G Status LED indicators M Data plate location Q Fuel regulator vents 2 C Airbox with air cleaner H Oil drain N Sediment trap R Wi F...

Page 13: ...t including model number serial number production date voltage frequency amps country of origin rated ambient temperature The model data decal also includes applicable certification symbols from indep...

Page 14: ...y Standard for Stationary Engine Generator Assemblies and CSA C22 2 No 100 04 Standard for Motors and Generators Natural gas ratings will depend on specific fuel BTU joules content Typical derates are...

Page 15: ...t Recommended fuels should have a MJ BTU content of at least 37 26 MJ m3 1 000 BTU ft3 for NG or at least 93 15 MJ m3 2 500 BTU ft3 for LP gas NOTE If converting to LP gas from NG a minimum LP tank si...

Page 16: ...panel fuse 0D7178T Transfer switch fuses See transfer switch manual for part number Accessory Description Cold Weather Accessories Battery Pad Warmer Oil Warmer each sold separately Recommended in ar...

Page 17: ...ocks secure lid one on each side A Open protective rubber cap to access keyhole and press down on lid above side lock and unlock latch to correctly open the lid Repeat for other side Lid may appear st...

Page 18: ...ment trap 1 Raise lid and remove front panel 2 Use a hex wrench to remove two mounting screws B and L bracket screw C 3 Lift intake side panel up and away from generator set NOTE Always lift intake si...

Page 19: ...plays LCD Panel 001791 A C B 001798 A B Button Description of Operation AUTO Activates fully automatic system operation It allows unit to automatically start and exercise generator set according to ex...

Page 20: ...Down Running Warning Warning Message Warning Message s Low Battery Exercise Set Error Service Schedule A Service Schedule B Inspect Battery Stopping FIRMWARE ERROR 9 Fuel Pressure Battery Problem Char...

Page 21: ...XXXXX NOTE 1 Last 50 logs displayed for each Alarm Log Run Log Maint Log NOTE 2 Date and time displayed for each occurence NOTE 3 Error code displayed for each Alarm Error Code and Alarm Message swap...

Page 22: ...nless this proce dure is performed If Wi Fi is NOT enabled current date time must be reset every time the 12 volt battery is dis connected and then reconnected and or when fuse is removed Table 3 1 de...

Page 23: ...f seven second cranks fol lowed by seven second rests NOTE An alarm will be triggered if generator set does not start after these five attempts Mode Description MANUAL Will not transfer to generator s...

Page 24: ...erator set controller display will show Under Volt age if cleaning cycle fails to clear obstruction After sev eral minutes the alarm message can be cleared and generator set restarted Make no further...

Page 25: ...of operation The controller will prompt for Schedule A or Schedule B maintenance to be performed Schedule A maintenance consists of the oil oil filter and battery check Schedule B maintenance includes...

Page 26: ...oil and oil filter Replace engine air filter Clean inspect spark plug gap replace spark plugs Inspect adjust valve clearance Inspect clean sediment trap See local codes and guidelines Contact an IASD...

Page 27: ...SJ SL or better Do not use special additives Required oil Synthetic SAE 5W 30 for all temperature ranges See Engine Changing the Oil and Oil Filter Proceed as follows to change oil and oil filter 1 L...

Page 28: ...as necessary 1 With generator set OFF and engine cool lift lid and remove front panel 2 Clean area around base of spark plug s to keep dirt and debris out of engine 3 Remove spark plug s and inspect c...

Page 29: ...fasteners to 6 8 Nm 60 in lbs in a cross pattern Adjusting Valve Clearance Proceed as follows to adjust valve clearance NOTE Allow engine to cool before adjusting valve clear ance 1 Remove spark plug...

Page 30: ...13kVA 19 68 Nm 174 in lbs 000188 DANGER Electrocution Do not wear jewelry while working on this equipment Doing so will result in death or serious injury 000162 Explosion Do not dispose of batteries...

Page 31: ...rger cable Figure 4 5 Disconnecting Battery Charger Cable 5 See Figure 4 6 Inspect battery posts and cables for tightness and corrosion Tighten and clean as necessary Figure 4 6 Battery Cables 6 Unsea...

Page 32: ...uld be tested from supply to regulator See Figure 4 8 Perform a final fuel system leak test after generator set installation The test will identify possi ble leaks at all connection points A It is bes...

Page 33: ...il if necessary 2 Inspect state of battery Fill all cells of unsealed batteries to correct level with distilled water DO NOT use tap water Charge battery to 100 state of charge Replace battery if faul...

Page 34: ...Maintenance 30 Owner s Manual for Australian 50 Hz Air Cooled Generators This page intentionally left blank...

Page 35: ...Faulty spark plug s Clean inspect spark plug gap replace spark plug s if necessary Valve clearance out of adjustment Reset valve clearance Engine starts hard and runs rough Air cleaner plugged or dam...

Page 36: ...tch coil Contact an IASD Faulty transfer relay Transfer relay circuit open Faulty control logic board Engine may be warming up See Cold Smart Start Check controller screen to verify status Unit consum...

Page 37: ...delay is greater than expected contact an IASD to adjust from 2 to 1500 seconds LOW OIL PRESSURE RED Unit will not start in AUTO with utility loss Check LEDs screen for alarms Check oil level and add...

Page 38: ...y state Check screen for additional information Contact an IASD CHARGER WARNING YELLOW Yellow LED illuminated in any state Check screen for additional information Contact an IASD CHARGER MISSING AC YE...

Page 39: ......

Page 40: ...reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290 Hwy...

Reviews: