Capacities and Pressure Drop
CAPACITIES—expressed in CFH (m
3
/h)—0.64 sp gr gas
Sizing Instructions
In order to select the proper size regulator, you must
know the available inlet pressure, desired outlet
pressure, and the required maximum flow rate.
Example No. 1—To select a regulator of ample
capacity to handle flow.
KNOWN:
Pipe size 2-1/2", flow rate 8,000 CFH (0.64 sp gr), inlet
pressure 9" w.c., desired outlet pressure 5" w.c.
SOLUTION:
1. Determine differential pressure available:
Inlet pressure
9" w.c.
Subtract outlet pressure
- 5" w.c.
Available differential pressure
4" w.c.
2. When determining capacity Maxitrol
recommends that the pressure drop not exceed
1/2 of available differential pressure (1/2 of 4"
w.c. = 2" w.c.).
3. Check Capacity Chart to determine which
regulator has a pressure drop of 2" w.c. or less at
a flow rate of 8,000 CFH.
4. The RV111 meets these standards with a
flow rate of 12,134 CFH for the 2-1/2" pipe size at
2" w.c. pressure drop. The 2-1/2" RV91 flows
5422 CFH at 2" w.c. pressure drop. Therefore, the
RV111—2-1/2" is the correct regulator to use.
Example No. 2—To determine maximum
recommended operating outlet pressure.
KNOWN:
Pipe size 4", flow rate 21,000 CFH, inlet pressure
10" w.c.
SOLUTION:
1. Check capacity Chart above for 4" regulator,
RV131.
2. Note that at a flow rate of 21,172 CFH the
pressure drop is 2" w.c.
3. Multiply this by two to obtain recommended
differential pressure (4" w.c.).
4. Subtract 4" differential pressure from 10" w.c.
inlet pressure to obtain maximum recommended
outlet pressure setting of 6" w.c.
Pressure Drop Chart
Model
Number and Pipe Size
A.G.A.
MAX
Pressure DropÑinches w.c. (mbar)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
2
3
4
RV52
1/2 x 1/2
3/4 x 3/4
450
(12.7)
151
(4.2)
214
(6.1)
262
(7.4)
302
(8.5)
338
(9.5)
370
(10.5)
400
(11.3)
427
(12.1)
453
(12.8)
478
(13.5)
676
(19.1)
828
(23.4)
956
(27.1)
RV53
3/4 x 3/4
1 x 1
710
(20.1)
217
(6.1)
306
(8.6)
375
(10.6)
433
(12.2)
484
(13.7)
530
(15)
573
(16.2)
612
(17.3)
650
(18.4)
684
(19.3)
968
(27.4)
1185
(33.5)
1369
(38.7)
RV61
1 x 1
1-1/4 x 1-1/4
1100
(31.1)
379
(10.7)
536
(15.1)
675
(19.1)
759
(21.5)
848
(24)
929
(26.3)
1004
(28.4)
1073
(30.4)
1138
(32.2)
1200
(34.0)
1742
(49.3)
2134
(60.4)
2464
(69.8)
RV81
1-1/4 x 1-1/4
1-1/2 x 1-1/2
2500
(70.8)
780
(22.1)
1102
(31.2)
1350
(38.2)
1559
(44.1)
1743
(49.5)
1909
(54)
2062
(58.4)
2204
(62.4)
2339
(66.2)
2465
(69.8)
3485
(98.7)
4269
(120)
4929
(139)
RV91
2 x 2
2-1/2 x 2-1/2
3275
(92.7)
1212
(34.3)
1714
(48.5)
2100
(59.4)
2424
(68.6)
2711
(76.7)
2969
(84.1)
3208
(90.8)
3429
(97.1)
3637
(103)
3834
(108)
5422
(153)
6640
(188)
7668
(217)
RV111
2-1/2 x 2-1/2
3 x 3
7500
(212)
2742
(78)
3878
(110)
4750
(134)
5485
(155)
6132
(175)
6718
(190)
7256
(205)
7757
(219)
8227
(233)
8572
(243)
12134
(343)
14862
(420)
17161
(486)
RV131
4 x 4
--
4734
(134)
6695
(190)
8200
(232)
9468
(268)
10586
(300)
11596
(328)
12525
(354)
13390
(380)
14202
(402)
14971
(424)
21172
(600)
25930
(734)
29942
(848)
CSA
Page 49
Summary of Contents for Lattner
Page 1: ...Instruction Manual WLF Steam Boilers 2006 to 2007 ...
Page 32: ...Page 32 ...
Page 33: ...Page 33 ...
Page 34: ...Page 34 ...
Page 35: ...Page 35 ...
Page 36: ...Page 36 ...
Page 37: ...Page 37 ...
Page 38: ...Page 38 ...
Page 39: ...Page 39 ...
Page 40: ...Page 40 ...
Page 41: ...Page 41 ...
Page 42: ...Page 42 ...
Page 43: ...Page 43 ...
Page 44: ...Page 44 ...
Page 45: ...Page 45 ...