26
Possible Boiler Problems
Possible Causes
Boiler and pump switch are ON,
pump does not run and low water
level in boiler.
1. Circuit breaker is tripped or fuse is blown.
2. McDonnell Miller piping is plugged.
3. McDonnell Miller float is stuck.
4. McDonnell Miller is wired incorrectly.
5. Pump or solenoid water valve is wired incorrectly.
Pump runs but does not maintain
water level in boiler.
1.
Valve between boiler pump and boiler is closed.
2.
Bad check valve. Always replace check valves with spring-loaded check valves.
3.
Bad steam trap(s).
4.
Feedwater temperature is too high (pump is cavitating).
5.
Strainer is plugged.
6.
Pump isolation valve is closed.
7.
No water supplied to pump.
Pump or solenoid overfills boiler.
1.
Solenoid water valve is not seating properly.
2.
McDonnell Miller float operating incorrectly (snap switches “sticking”).
3.
McDonnell Miller mercury tube is malfunctioning.
4.
McDonnell Miller is wired incorrectly.
5.
Pump is wired incorrectly.
Boiler takes excessive time to reach
pressure.
1.
Burner is improperly adjusted.
2.
Improper gas pressure or insufficient supply of gas to boiler.
3.
Boiler flue passages need to be cleaned.
4.
Scale build-up inside boiler.
5.
Gas valves not operating properly.
6.
Pump not feeding enough water to the boiler.
Limit switch always shuts down
boiler.
1.
Operating pressure switch is set higher than limit switch.
2.
Scale build-up inside of boiler.
3.
Operating pressure switch (Honeywell “Controller”) is not operating correctly.
Boiler shuts down on auxiliary low
water cut-off.
1.
Pump switch is turned OFF.
2. Probe
wired
incorrectly.
3.
Probe has scale, dirt, or debris on it.
4.
Probe not seated in probe socket properly.
5.
Auxiliary level control relay wired incorrectly.
6.
Foaming problem in boiler (possible chemical over treatment).
7.
Water in boiler is too soft (possible water softener over treatment).
8.
McDonnell Miller primary low water cut-off isn’t operating properly.
9.
Pump is not functioning properly.
10. Malfunctioning check valve. Always replace check valves with spring-loaded check
valves.
11. No water supplied to the pump.
Burner fails to start.
1.
Bad fuse or switch open on incoming power source or motor overload out.
2.
Control circuit has an open control such as operating, limit, or low water cut-off.
3.
Reset button on motor or flame safeguard programming control open (push reset
button).
4.
Loose or faulty wiring. Tighten all terminal screws. Check wiring against wiring diagram
furnished with burner.
5.
Regulator vent plugged.
Burner motor runs but pilot does not
light.
1.
Be sure gas is turned on at meter and pilot cock is open.
2.
Place hand on pilot valve to feel it open. Check gauge at tee in pilot line for gas
pressure and prompt opening of pilot valve.
3.
Check visually or by sound for spark arcing.
4.
Check air switch. Be sure its circuit closes during start. Be sure timing card is inserted
into flame safeguard.
5. Bad
igniter.
6.
Bad pilot solenoid valve.
7.
Pilot regulator vent plugged.
Summary of Contents for Lattner
Page 1: ...Instruction Manual WLF Steam Boilers 2006 to 2007 ...
Page 32: ...Page 32 ...
Page 33: ...Page 33 ...
Page 34: ...Page 34 ...
Page 35: ...Page 35 ...
Page 36: ...Page 36 ...
Page 37: ...Page 37 ...
Page 38: ...Page 38 ...
Page 39: ...Page 39 ...
Page 40: ...Page 40 ...
Page 41: ...Page 41 ...
Page 42: ...Page 42 ...
Page 43: ...Page 43 ...
Page 44: ...Page 44 ...
Page 45: ...Page 45 ...