background image

 

26

 
 
 

Possible Boiler Problems 

Possible Causes 

 
Boiler and pump switch are ON, 
pump does not run and low water 
level in boiler. 

1.  Circuit breaker is tripped or fuse is blown. 
2.  McDonnell Miller piping is plugged. 
3.  McDonnell Miller float is stuck. 
4.  McDonnell Miller is wired incorrectly. 
5.  Pump or solenoid water valve is wired incorrectly. 

 
Pump runs but does not maintain 
water level in boiler. 

1. 

Valve between boiler pump and boiler is closed. 

2. 

Bad check valve.  Always replace check valves with spring-loaded check valves. 

3. 

Bad steam trap(s). 

4. 

Feedwater temperature is too high (pump is cavitating). 

5. 

Strainer is plugged. 

6. 

Pump isolation valve is closed. 

7. 

No water supplied to pump. 

 
Pump or solenoid overfills boiler. 

1. 

Solenoid water valve is not seating properly. 

2. 

McDonnell Miller float operating incorrectly (snap switches “sticking”). 

3. 

McDonnell Miller mercury tube is malfunctioning. 

4. 

McDonnell Miller is wired incorrectly. 

5. 

Pump is wired incorrectly. 

 
Boiler takes excessive time to reach 
pressure. 

1. 

Burner is improperly adjusted. 

2. 

Improper gas pressure or insufficient supply of gas to boiler. 

3. 

Boiler flue passages need to be cleaned. 

4. 

Scale build-up inside boiler. 

5. 

Gas valves not operating properly. 

6. 

Pump not feeding enough water to the boiler. 

 
Limit switch always shuts down 
boiler. 

1. 

Operating pressure switch is set higher than limit switch. 

2. 

Scale build-up inside of boiler. 

3. 

Operating pressure switch (Honeywell “Controller”) is not operating correctly. 

 
Boiler shuts down on auxiliary low 
water cut-off. 

1. 

Pump switch is turned OFF. 

2. Probe 

wired 

incorrectly. 

3. 

Probe has scale, dirt, or debris on it. 

4. 

Probe not seated in probe socket properly. 

5. 

Auxiliary level control relay wired incorrectly. 

6. 

Foaming problem in boiler (possible chemical over treatment). 

7. 

Water in boiler is too soft (possible water softener over treatment). 

8. 

McDonnell Miller primary low water cut-off isn’t operating properly. 

9. 

Pump is not functioning properly. 

10.  Malfunctioning check valve.  Always replace check valves with spring-loaded check 

valves. 

11.  No water supplied to the pump. 

 
Burner fails to start. 

 
1. 

Bad fuse or switch open on incoming power source or motor overload out. 

2. 

Control circuit has an open control such as operating, limit, or low water cut-off. 

3. 

Reset button on motor or flame safeguard programming control open (push reset 
button). 

4. 

Loose or faulty wiring.  Tighten all terminal screws.  Check wiring against wiring diagram 
furnished with burner. 

5. 

Regulator vent plugged. 

 

 
Burner motor runs but pilot does not 
light. 

 
1. 

Be sure gas is turned on at meter and pilot cock is open. 

2. 

Place hand on pilot valve to feel it open.  Check gauge at tee in pilot line for gas 
pressure and prompt opening of pilot valve. 

3. 

Check visually or by sound for spark arcing. 

4. 

Check air switch.  Be sure its circuit closes during start.  Be sure timing card is inserted 
into flame safeguard. 

5. Bad 

igniter. 

6. 

Bad pilot solenoid valve. 

7. 

Pilot regulator vent plugged. 

 

Summary of Contents for Lattner

Page 1: ...Instruction Manual WLF Steam Boilers 2006 to 2007 ...

Page 2: ...Firing The Boiler N Pressuretrols Controller Limit O Start Up of Standard Burners Section II Boiler Care A General B New Boiler Clean Out C Water Conditions D Water Treatments Chemicals E Water Softener F Foaming Bouncing Chemicals G Water Treatment Summary H Blowdown I Feedwater System J Burner Adjustment K Sight Glass L External Inspections M Internal Inspections Section III Maintenance A Daily ...

Page 3: ...ng Pipe I Warrick Relay Replacement J Auxiliary Low Water Cut Off Probe Cleaning Section IV Troubleshooting A Normal Operation B Basic Service Tools C Before You Begin Lattner Boiler Limited Warranty Standard Terms Conditions Product Support Literature 22 23 23 24 24 Page 25 25 25 25 Page 28 Page 29 Page 30 ...

Page 4: ...vessel with ASME Code required stay bolts It is symmetrical in layout and completely water backed assuring a balanced flow circulating pattern under all load conditions 5 Inner Casing A non metallic gas barrier encases the heat transfer fins to ensure proper gas travel from the combustion chamber into each heat transfer zone This barrier is covered with a steel wrapper that is in turn covered with...

Page 5: ...s a float actuated device a snap acting single pole single throw switch activates a pump contactor for ON OFF pump or solenoid valve operation 5 Auxiliary Low Water Cut Off An additional control separate from the primary low water control is provided to prevent burner operation if a low low water condition exists This device is an internal probe control located on the top of the pressure vessel an...

Page 6: ... mounted on the boiler This panel contains as a minimum the following components 1 Boiler ON OFF Switch Provided to interrupt control power to the 120 volt control circuit Does not disconnect the main power source 2 Pump ON OFF Switch Provided to isolate the pump control circuit 3 Terminals Provided for the connection of the 120 1 60 volt supply and for external connections for field wiring 4 Rela...

Page 7: ...l hydrostatic pressure test This test includes the integral steam and water trim piping and the trim valves An ASME P 6 piping hydro certificate can be provided for an additional cost 3 Burner Controls To ensure proper operation of the combustion safeguard control ignition and main fuel light off the burner manufacturer subjects the packaged burner to a preliminary factory fire test All burner and...

Page 8: ...t etc place the boiler on rollers or on 2 pipes and roll the boiler into place If the unit is dragged attach chains to the base frame only CAUTION DO NOT lay the boiler on its side as the panels will not support the weight of the boiler without sustaining damage If the entry is too narrow for the boiler and controls to pass through removal of the trim and controls can be executed One should proper...

Page 9: ... 7 Walls Ceilings When passing through combustible walls or ceilings a stack thimble is required The thimble must be double wall stack 6 larger in diameter than the vent stack The material used to close the opening between the stack and the stack thimble must be non combustible F Boiler Shipped with Controls Removed 1 Reassemble See assembly print in this section p 15 2 Wiring Re wiring the contro...

Page 10: ...gh the drain should be piped to the sewer Some codes require the water to pass through an air gap before entering the sewer 9 Aftercooler If the water must be cooled before entering the sewer required by some codes then an aftercooler must be used The aftercooler attaches to the separator drain connection and mixes cold water with the hot drain water Units may be either manual or automatic Select ...

Page 11: ...part of the gas train piping This will void any warranty on the gas train assembly 7 Codes Standards All gas piping must be done in accordance with all applicable codes National Fuel Gas Code utility company requirements local building codes etc K Boiler Feed Systems 1 Condensate Return Systems a Make Up Water Supply Connect city water line to the float valve provided with the boiler feed system L...

Page 12: ...lve If a solenoid water valve is used make sure the water supply is connected N Pressuretrols Controller Limit 1 Standard All Lattner steam boilers will have at least two pressure switches a controller and a limit 2 Controller Before the boiler is started the steam pressure is 0 psi At this point the controller is in the ON condition and is calling for heat When the boiler switch is turned on the ...

Page 13: ...he manual reset on the limit switch must then be reset before the boiler will operate again 10 More Information For any additional information on the Honeywell Pressuretrols refer to the Honeywell product sheet in the back of this manual O Start Up of Standard Burners CAUTION All work performed on gas fired equipment or gas train components must be done by qualified personnel 1 Turn boiler switch ...

Page 14: ...y Data may vary by location environment fuel gas pressure BTU content and more REFER TO BURNER NAMPLATE AND BURNER MANUAL FOR MORE SPECIFIC INSTRUCTIONS including low NOx burner instructions for California and Texas Constituent Value Required Gas Pressure Maximum 14 w c Required Gas Pressure Minimum varies by burner Manifold Pressure See burner nameplate O2 4 5 to 7 5 CO2 8 to 10 CO Less than 100 ...

Page 15: ...going back through the pump and into the boiler If this is not possible then the new boiler clean out procedure becomes imperative NOTE Never fill a hot empty boiler with cold water C Water Conditions 1 Oxygen Scavenging The oxygen will then attack exposed metal surfaces This leads to corrosion and localized pitting of the metal 3 Scale Deposits As the water boils the dissolved minerals will separ...

Page 16: ...H 8 5 to 10 Total Dissolved Solids 2 000 ppm or 116 8 grains maximum Oxygen 0 ppm Alkalinity Less than 300 ppm Chloride Less than 500 ppm Sodium Phosphate Less than 100 ppm H Blowdown 1 Purpose of Blowdown The water treatment chemicals keep these substances suspended in the water Eventually the concentration of these substances increases and must be removed This is done by blowdown Blowdown remove...

Page 17: ...shers are not in place the gasket will twist causing the glass to break 4 Proper Installation L External Inspections 1 Maintenance External inspections are routine observations of the visible portions of the boiler By noticing the normal boiler operation many problems can be detected before they become serious 2 Piping Check the piping for leaks This includes steam pipes condensate pipes feedwater...

Page 18: ... boiler is being used If the boiler uses large quantities of untreated hard water the boiler may need to be inspected every 60 days If the boiler uses minimal quantities of make up water i e closed loop systems and the water is treated the boiler may need to be inspected only once a year Many state and or city codes require annual internal boiler inspections 4 Gaskets The hand hole gaskets and the...

Page 19: ...ve wear or leaks 2 Test the McDonnell Miller and auxiliary low water cut off for proper operation By opening the blowdown valves with the boiler firing the burners must shut off during this test If the burners do not shut off the control may require immediate servicing 3 Drain the sight glass 4 Visually inspect the boiler and water feed system for any water or steam leaks in the piping 5 Check the...

Page 20: ...pilot flame Notify service organization if readings are high low or fluctuating Hand Hole Plates Monthly Operator Visually check for leakage and replace gaskets as necessary Firing Rate Control Annually Service Technician Verify BTU input and gas pressure and check with combustion test analyzer Igniter or Pilot Annually Operator Make visual inspection and check flame strength with appropriate equi...

Page 21: ...ate rocks back and forth remove the high spots on the hand hole plate with a file Note Do not leave the hand hole plate installed without the gasket 11 Install the gasket on the hand hole plate Make sure the gasket is pressed firmly down on to the hand hole plate Do not use any grease lubricants or adhesives when installing handhold gaskets 12 Reinstall the hand hole plate into the boiler 13 Repla...

Page 22: ...ower fixture Be careful not to break the sight glass when removing 7 Assemble the new sight glass as shown ALWAYS replace the gaskets and brass washers when installing a new sight glass 8 Slide the new glass into the upper fixture Glass should clear the lower fixture and tilt into position 9 Slide the sight glass down into the lower fixture Equalize the gap between the upper and lower fixtures 10 ...

Page 23: ... or float arm 10 Check the float for any holes Hold the float submerged in a bucket of water and look for any air bubbles coming from the float 11 Always reassemble the McDonnell Miller operating mechanism to the body with a new gasket 12 Reinstall the eight bolts to the operating mechanism Draw up the bolts evenly to prevent damage to the gasket body or operating mechanism Do not over tighten the...

Page 24: ...screws on top of the probe enclosure with a Phillips screwdriver 3 Remove the wire from the probe using a 5 16 wrench or a crescent wrench Only the wire on the probe is to be removed 4 Use a 13 16 spark plug socket and remove the probe 5 Clean the stainless steel probe and probe fitting 6 Reinsert the probe using a 13 16 spark plug socket Only tighten the probe enough to stop any steam leaks Over ...

Page 25: ... If the McDonnell Miller does not shut down the boiler the auxiliary low water cut off will shut down the boiler 10 If the boiler has optional controls refer to the wiring diagram B Basic Service Tools The following basic equipment will aid in troubleshooting Lattner boilers Not all equipment is needed for every repair 1 Schematic diagram of the boiler 2 Volt ohm meter 3 Ammeter 4 Gas pressure gau...

Page 26: ...up inside of boiler 3 Operating pressure switch Honeywell Controller is not operating correctly Boiler shuts down on auxiliary low water cut off 1 Pump switch is turned OFF 2 Probe wired incorrectly 3 Probe has scale dirt or debris on it 4 Probe not seated in probe socket properly 5 Auxiliary level control relay wired incorrectly 6 Foaming problem in boiler possible chemical over treatment 7 Water...

Page 27: ...ge readings If sufficient check gas pressure an air damper setting Check electrodes setting If flame rod pilot flame rod may have to be re positioned 2 Check ignition cable and electrode porcelain for damage or breaks which could cause short 3 Check for loose or broken wires Burner will not start even though burner has never failed before or has been running on normal cycle without failure 1 Opera...

Page 28: ...for which the Purchaser may be liable to other persons or damages to property The remedies set forth in this Warranty are exclusive and the liability of Lattner with respect to any contract or sale shall not exceed the cost of repair or replacement of the boiler or other equipment manufactured by Lattner The above Warranty shall not apply to any boiler or other equipment manufactured by Lattner wh...

Page 29: ...ges in transit and a minimum 15 restocking charge and only if the authorized material is in new and unused condition and returned within one year from original date of shipment The credit will be based on the original invoice price or the current price whichever is lower less the applicable restocking charge SECURITY INTEREST For the purposes of securing payment the Company may issue a lien on the...

Page 30: ...gasket is in place make one last cleaning swipe of the mating surface in the boiler Use a rag wrapped around your finger 4 Set crab then center plate in opening and tighten nut enough to give a snug fit Then snug up with 1 4 turn of wrench SPECIAL NOTES If gasket leaks while pressure is being built up tighten only enough to stop leakage Never over compress a gasket Gaskets on the bottom of a boile...

Page 31: ...ase vacuum pressure in the boiler would suck the cover plate in and allow the water to leak out of the boiler Re using gaskets after they have been in service is not recommended Topog E Bolt Gaskets when required should be used with Topog E Handhole Gaskets Topog E Gaskets are sold for use in steam water air and other selected applications only Recommendations for use of Topog E Gaskets are based ...

Page 32: ...Page 32 ...

Page 33: ...Page 33 ...

Page 34: ...Page 34 ...

Page 35: ...Page 35 ...

Page 36: ...Page 36 ...

Page 37: ...Page 37 ...

Page 38: ...Page 38 ...

Page 39: ...Page 39 ...

Page 40: ...Page 40 ...

Page 41: ...Page 41 ...

Page 42: ...Page 42 ...

Page 43: ...Page 43 ...

Page 44: ...Page 44 ...

Page 45: ...Page 45 ...

Page 46: ...ternal threads To do so may cause the sealing compound to enter the valve and cause seat leakage Do not use the valve body or bonnet for installing the valve in threaded connections Use the wrench flats provided to tighten the valve to the connecting pipe and do not overtighten To do so may cause valve leakage 4 For flanged valves use new gaskets and tighten the mounting studs evenly Operation 1 M...

Page 47: ...ressure is more than 10 times desired outlet pressure EMERGENCY EXPOSURE LIMITS Maxitrol Tested RV52 RV53 3 psi 210 mbar RV61 RV81 RV91 RV111 5 psi 350 mbar RV131 15 psi 1050 mbar GAS CONTAINMENT EXPOSURE LIMITS RV 52 RV53 15 psi 1050 mbar RV61 RV81 RV91 RV111 RV131 25 psi 1750 mbar Please note that internal damage may occur when exposed to these pressures AMBIENT TEMPERATURE LIMITS RV52 RV53 RV61...

Page 48: ...agm material is cut from the finest synthetic coated fabrics available All other parts are carefully specified corrosion resistant or plated material Pipe sizes of 1 2 3 4 1 1 1 4 1 1 2 2 2 1 2 3 and 4 are available Models through the 3 size are threaded the 4 RV131 is flanged At the emergency exposure limits there may be no regulation but all models will contain gas They will suffer no internal d...

Page 49: ...w rate of 21 172 CFH the pressure drop is 2 w c 3 Multiply this by two to obtain recommended differential pressure 4 w c 4 Subtract 4 differential pressure from 10 w c inlet pressure to obtain maximum recommended outlet pressure setting of 6 w c Pressure Drop Chart Model Number and Pipe Size A G A MAX Pressure DropÑinches w c mbar 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 2 3 4 RV52 1 2 x 1 2 3 4 x 3 ...

Page 50: ... 4 8 122 6 4 164 4 4 111 5 4 138 1 6 41 RV81 3 8 NPT 6 4 162 8 4 213 6 153 7 178 2 51 RV91 2 pipe 1 2 NPT 8 5 216 10 8 275 6 5 165 9 1 232 2 3 60 RV91 2 5 pipe 1 4 NPT 8 3 212 10 5 267 7 1 181 9 1 232 2 4 62 RV111 3 4 NPT 11 5 284 15 1 373 9 229 13 4 324 3 5 89 RV131 3 4 NPT 18 2 462 23 25 590 13 9 353 18 458 5 1 129 Model Number A G A Certified Springs Other Springs Available RV52 3 to 6 7 5 15 4...

Page 51: ...ar fugas o afectar el funcionamiento del regulador Si usted sospecha que un regulador Maxitrol ha sido expuesto a más del doble de la presión máxima de entrada como se muestra en la tabla siguiente cierre el paso del gas y haga que el sistema sea verificado por un experto SAFETY WARNING INSTRUCTIONS FOR MAXITROL GAS PRESSURE REGULATORS NOTE GAS PRESSURE REGULATORS WILL NOT TURN OFF THE FLOW OF GAS...

Page 52: ...sed within the temperature range and not in excess of the maximum inlet pressure shown in the following table and should be in the mounting position indicated Maxitrol regulators can be used with all fuel gases 10 In case of any doubt please contact the Service Manager Maxitrol Company Southfield MI USA Phone 248 356 1400 Mounting Position Posición de Montaje D C A B B Vertical Flow Flujo Vertical...

Page 53: ...operating controls installed on the boiler After installation check for proper operation of all of the limit and operating controls before leaving the site We recommend that secondary redundant Low Water Cut Off controls be installed on all steam boilers with heat input greater than 400 000 BTU hour or operating above 15 psi of steam pressure At least two controls should be connected in series wit...

Page 54: ...OFF PUMP ON 3 4 DIFFERENTIAL 19mm PUMP OFF BURNER OFF NORMAL BOILER WATER LINE 113 16 DIFFERENTIAL 46mm BURNER CUT OFF LEVEL 3 8 9 5mm BELOW CAST LINE OPERATION Maximum Pressure 150 psi 10 5 kg cm2 Electrical Ratings Settings and Differential Pressures Values are 8 3 2mm Series 150 150S 157 and 157S 150 psi 10 5 kg cm2 Levels 150 psi 10 5 kg cm2 Levels 0 psi 0 kg cm2 150 psi 10 5 kg cm2 Approximat...

Page 55: ...g will occur at slightly different levels than indicated above Model 158 158S 150 psi 10 5 kg cm2 Levels 0 psi 0 kg cm2 150 psi 10 5 kg cm2 Pressure Settings and Differential Pressures continued 150 psi 10 5 kg cm2 MOTORIZED VALVE OPEN CLOSED 3 4 DIFFERENTIAL 19mm MOTORIZED VALVE CLOSED BURNER OFF NORMAL BOILER WATER LINE 113 16 DIFFERENTIAL 46mm BURNER CUT OFF LEVEL 3 8 9 5mm BELOW CAST LINE Appr...

Page 56: ...FFERENTIAL 35mm Values are 8 3 2mm 150 psi 10 5 kg cm2 Levels Approximate Distance Above Cast Line Differential Setting In mm In mm Pump 1 Off 15 16 24 5 16 8 Pump 1 On 5 8 16 Pump 2 Off 5 8 16 3 8 16 Pump 2 On 1 4 6 4 Pump 1 Off 13 8 41 3 4 19 Pump 1 On 5 8 16 Pump 2 Off 7 8 22 7 8 22 Pump 2 On 0 0 Model 159 159S 0 psi 0 kg cm2 150 psi 10 5 kg cm2 Pressure Settings and Differential Pressures cont...

Page 57: ...f STEP 1 Determine the Elevation at Which the Low Water Cut Off Pump Controller Must be Installed INSTALLATION TOOLS NEEDED Two 2 pipe wrenches one 1 flathead screw driver and pipe sealing compound IMPORTANT Follow the boiler manufacturer s instructions along with all applicable codes and ordinances for piping blow down valve and water gauge glass requirements 13 8 STEAM EQUALIZING PIPE VERTICAL E...

Page 58: ...ve G directly below the lower cross of the water equalizing pipe F Note 1 NPT tappings are provided with the exception of some 157 and 157S mod els which are 14 NPT b For Models 150 B and 150S B and Series 157 and 157S For all other models proceed to Step 3 Screw the w NPT steel plug C provided in tapping A Series 157 and 157S Models 150 B and 150S B STEP 3 Installing a Water Gauge Glass Required ...

Page 59: ...uld cause damage to the boiler and or boiler system Failure to follow this warning could cause electrical shock an explosion and or a fire which could result in property damage personal injury or death WARNING Switch Operation For all Models except 158 158S and 159 159S For Models 158 and 158S Boiler feed pump off burner on alarm off Boiler feed pump on burner on alarm off Boiler feed pump on burn...

Page 60: ...T OFF AND ALARM SWITCH ALARM CIRCUIT TERMINALS LOW WATER CUT OFF TERMINALS L PUMP SWITCH PUMP CIRCUIT TERMINALS LOW WATER CUT OFF AND ALARM SWITCH ALARM CIRCUIT TERMINALS LOW WATER CUT OFF TERMINALS L IMPORTANT There must be a minimum space of 1 2 13mm between connector fittings and electrical live metal parts Automatic Reset All models except 158S and 159S Automatic Reset Model 158S Manual Reset ...

Page 61: ...he burner circuit exceeds the switch s electrical rating 2 Pilot Switch To holding coil of a starter when the pump circuit exceeds the switch s electrical rating LINE LOAD 1 2 4 5 6 LINE LOAD 1 2 4 5 6 1 2 4 5 6 ALARM NEUTRAL HOT ALARM NEUTRAL HOT 1 2 4 5 6 1 2 4 5 6 SEE PUMP CONTROL CIRCUIT TO NEUTRAL TO BURNER CONTROL CIRCUIT HOT ALARM 1 2 4 5 6 LOAD LINE 3 PHASE SEE PUMP CONTROL CIRCUIT ALARM 1...

Page 62: ...a boiler not being fired and or not at pressure Actual operating ranges are shown on page 2 in the Operation section If the burner comes on immediately turn the boiler off and make the necessary corrections Failure to follow this warning could cause an explosion or fire and result in property damage personal injury or death WARNING 7 8 M J 22mm b The boiler should begin to fill with water Watch th...

Page 63: ...he water level reaches approximately d 22mm above the horizontal cast line press the reset button N The burner should then come on d Continue watching the gauge glass J to see that the water continues to rise to approximately 1a 35mm 17 16 37mm for MD models above the horizontal cast line M The pump should shut off the motorized valve should close with Models 158 and 158S or with Models 159 and 15...

Page 64: ...epair Procedure provided Snap switches must be replaced as an assembly CAUTION Replacement Switch Assembly Replacement Mercury Tubes 2 Wire Pump 3 Wire Burner NOTE More frequent blow down may be necessary due to dirty boiler water and or local codes BLOW DOWN PROCEDURE Blow down the control when the water in the boiler is at its normal level and the burner is on Slowly open the upper then the lowe...

Page 65: ...g level Listings U L limit control recognition 353 240 and 208 volt units are not U L limit control recognized Installation 1 Install octal socket in appropriate enclosure using two 6 or 8 metal screws 1A Install rail mount socket on appropriate rail DIN mount in appropriate enclosure if applicable 2 Wire control per wiring diagram following N E C and local codes 3 Install control module in socket...

Page 66: ...power However loss of liquid will cause control to de ener gize and remain so until liquid again rises to electrode and pushbutton is depressed Dirty Electrode Detection The LED will flash every half second once the probe resistance reaches a value greater than the nominal control sensitivity rating The relay state will not change until it exceeds the nominal sensitivity by more than 25 typically ...

Reviews: