12.4.33 Split range
The start and end of the set value range can be set for
Split range
parameter.
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0xB4
1
0
R/W
16 bits
Split range
Split start
uint: 16
0
0 to Split End – 100
(0.0 to Split End – 10.0%)
2
16
R/W
16 bits
Split end
uint: 16
1000
Split Start + 100 to 1000
(Split Start + 10.0% to
100.0%)
Description of parameter values
Index name
Parameter
Values
Description
Split range
Split start
0 to Split End –
100
(0.0 to Split End
– 10.0%)
Set the start of the set value range.
Split end
Split Start + 100
to 1000
(Split Start +
10.0% to
100.0%)
Set the end of the set value range.
12.4.34 Stroke limiter
The upper and lower valve position of the control range can be set as stroke limiter with the
Stroke limiter
parameter.
NOTICE
To use the stroke limiter, the close tight function (open/close tight) must be deactivated. To do this, Open tight must be set
to the value 1000 (100.0%) and Close tight to the value 0 (0.0%).
Index Sub-
In-
dex
Off-
set
Access
Rights
Length
Index name
Parameter
Type
Default
Values
0xB6
1
0
R/W
16 bits
Stroke limiter
Max pos
uint:16
1000
Min Pos to 1000
(Min Pos to 100.0%)
2
16
R/W
16 bits
Min pos
uint:16
0
0 to Max Pos
(0.0% to Max Pos)
Description of parameter values
Index name
Parameter
Values
Description
Stroke limiter
Max pos
Min Pos to 1000
(Min Pos to
100.0%)
Set the stroke limiter of the control range in valve position
OPEN.
Min pos
0 to Max Pos
(0.0% to Max
Pos)
Set the stroke limiter of the control range in valve position
CLOSED.
www.gemu-group.com
58 / 72
GEMÜ 639 eSyStep
Positioner (Code S0)