12.3 Parameter overview
NOTICE
▶
All IO-Link parameters that contain sub-indexes can also be addressed in bundles via sub-index 0.
Index Sub-
Index
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
0x02
0
W
System command
Transmission of
commands for
block parameteriza-
tion and data stor-
age
0x01 to 0x06
0x82
0x03
1
R/W
Data storage index
Data storage cmd
Saving and restor-
ing parameter data
for device identical
in construction
2
RO
State property
3
RO
Data storage size
4
RO
Parameter checksum
5
RO
Index list
0x0C
1
R/W
Device access locks Parameter (write) ac-
cess
Parameter write
protection
0
→
unlocked
1
→
locked
2
R/W
Data storage
Data memory
0
→
unlocked
1
→
locked
3
R/W
Local parameteriza-
tion
Local parameteriza-
tion
0
→
unlocked
1
→
locked
4
R/W
Local user interface Local user interface
0
→
unlocked
1
→
locked
0x0D
0
RO
Profile
characteristics
Supported
Device Profile IDs,
Common
Application Profile
IDs, Function Class
IDs
0x8000 (Device
Ident. Objects)
0x8002 (Process
Data Mapping)
0x8003 (Diagnosis)
0x8100 (Ext. Identi-
fication)
0x0E
0
RO
Process data input
descriptor
Data format of input
process data
0x00 (Bit offset)
0x03 (Type Length)
0x01 (DataType ->
BoolT)
0x0F
0
RO
Process data output
descriptor
Data format of out-
put process data
0x00 (Bit offset)
0x04 (Type Length)
0x01 (DataType ->
BoolT)
0x10
0
RO
Vendor name
Read out manufac-
turer name
"GEMUE"
0x12
0
RO
Product name
Read out device
name
"eSyStep Posi-
tioner"
0x13
0
RO
Product ID
Read out product ID
"eSyStep Posi-
tioner"
0x15
0
RO
Serial number
Read out serial
number
"XXXXXXXX/YYYY"
0x16
0
RO
Hardware revision
Read out hardware
version
"Rev. XX/XX"
0x17
0
RO
Firmware revision
Read out software
version
"V X.X.X.X."
GEMÜ 639 eSyStep
Positioner (Code S0)
www.gemu-group.com
39 / 72
12 Specific data IO-Link (pin 6)