Index Sub-
Index
Access
rights
Index name
Parameter
Function
Factory
settings
Setting options
0x4F
1
R/W
Error action
Error action
Set safety position
2
0
→
Hold
1
→
Open
2
→
Close
2
R/W
Error time
Determine time
from error detection
to error message
1 (0.1s)
1 … 1000
(0.1s … 100s)
0x50
1
R/W
Basic settings
Inversion of LED col-
ours
Activate / deactiv-
ate inversion of
LEDs
0
0
→
Standard
1
→
Inversed
2
R/W
On site initialization Activate / deactiv-
ate on site initializa-
tion
0
0
→
Enabled
1
→
Disabled
3
R/W
Operating mode
Operating mode
change-over (posi-
tioner; ON/OFF)
0
0
→
Positioner
1
→
On/Off
4
R/W
IO-Link process data Activate/deactivate
use of IO-Link pro-
cess data
0
0
→
Disabled
1
→
Enabled
0x51
1
R/W
Actuator position
feedback
Open request
Request valve posi-
tion OPEN
900
(90.0%)
30 … 970
(3.0 … 97.0%)
2
R/W
Close request
Request valve posi-
tion CLOSED
100
(10.0%)
30 … 970
(3.0 … 97.0%)
3
RO
Open real
Real valve position
OPEN
0 … 4095
4
RO
Close real
Real valve position
CLOSED
0 … 4095
0x53
1
RO
Initialized positions
Open
Analog value valve
position OPEN
0 … 4095
2
RO
Close
Analogue value
valve position
CLOSED
0 … 4095
3
RO
Stroke
Read out the analog
value for stroke (dif-
ference between
OPEN and CLOSED).
0 … 4095
0x55
1
RO
Calibrated positions
Max.
OPEN end position
0 … 4095
2
RO
Min.
CLOSED end posi-
tion
0 … 4095
0x60
1
RO
Analog values
Potentiometer
Analog value poten-
tiometer
0 … 4095
2
RO
Supply voltage
Analog value supply
voltage
0 … 4095
3
RO
Temperature
Analog value tem-
perature sensor
0 … 4095
4
RO
Set value (W)
Analog value set
value signal
0 … 4095
0x62
1
RO
Operating times
Open
Operating time
OPEN
0
0 to 255
(0 to 25.5s)
2
RO
Close
Operating time
CLOSE
0
0 to 255
(0 to 25.5s)
0x90
2
R/W
Drive sets
Force
Force, dependent on
valve used
1 … 6
GEMÜ 639 eSyStep
Positioner (Code S0)
www.gemu-group.com
41 / 72
12 Specific data IO-Link (pin 6)