26 / 32
1434 µPos
7
Display elements
OPEN
ERROR
CLOSED
POWER
LED
Designation
Colour
1
OPEN
Yellow
2
ERROR
Red
3
CLOSED
Orange
4
POWER
Yellow
Meaning
Error number
LED 1
OPEN
LED 2
ERROR
LED 3
CLOSED
LED 4
POWER
Position reached
-
m
m
m
l
Valve in OPEN end position
-
l
m
m
l
Valve in CLOSED end position
-
m
m
l
l
Valve moves in OPEN direction
-
I
m
m
l
Valve moves in CLOSED direction
-
m
m
I
l
Positioner in initialisation phase
-
I
m
I
l
Set value > 20.5 mA / 10.25 V
Error no. 1
I
b
m
l
Set value < 3.5 mA
Error no. 2
m
b
I
l
Positioner not initialised
Error no. 3
I
b
I
l
Positioner not calibrated
Error no. 4
l
l
l
I
Device error
Error no. 5
m
b
m
l
Positioner works with lower quality
Warning no. 1
Z
l
Key
LED conditions
Flashing frequency
m
LED off
l
LED on
Z
LED flashes briefly
f = 1.66 Hz; 0.15 s on / 0.45 s off
b
LED flashes fast
f = 3.33 Hz; 0.15 s on / 0.15 s off
I
LED flashes slowly
f = 1.66 Hz; 0.30 s on / 0.30 s off