81901 “MSW_GPC-40/600A”_03-2021_ENG_page 104
3.25. Software shutdown
The Advanced Power Controller can also be switched off by
a software command.
When the software shutdown function is activated:
•
The digital input is only enabled if it is associated with
the software shutdown function.
•
Outputs are forced to OFF at shutdown. The exception
is the reference signals
rL.4
and
rL.6
, which are forced
to ON.
•
HB alarms are reset.
•
The generic alarms AL1...AL8 can be enabled or disa-
bled via the parameter
oFF.t
.
In addition to the parameters shown below, the following
parameters should also be considered for software shut-
down:
•
digital input function
dIG.1
/
dIG.2
/
dIG.3
/
dIG.4
(see
paragraph “3.12.4. Digital input function”);
•
status (STATUS_W) (see paragraph “3.22.3. Status
(STATUS_W)”);
•
digital input status
dIG.1
/
dIG.2
/
dIG.3
/
dIG.4
(see
paragraph “3.12.2. Digital input status”)
.
3.25.1.
Software startup/shutdown
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1035
11
bit
12.01.02
BIT_
SOFT-
WARE_
ON_OFF
M
MainMenu
→
M
→
Expert
→
Bit
→
IT_SOFTWARE_ON_OFF_1
R/W
■
OFF
2059
12.02.02
E1
MainMenu
→
E1
→
Expert
→
Bit
→
IT_SOFTWARE_ON_OFF_2
4107
12.03.02
E2
MainMenu
→
E2
→
Expert
→
Bit
→
IT_SOFTWARE_ON_OFF_3
The bit sets the software startup and shutdown.
Options:
OFF
= Software on
ON
= Software off
3.25.2.
Software shutdown modes
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1724
700
16 bit
OFF.t
Global MainMenu
→
Global
→
Controls
→
OFF.t R/W
■
Unsigned
Short
0
The parameter sets the software shutdown mode.
Options:
Index
Description
0
Outputs
rL.1
-
rL.2
-
rL.3
-
rL.5
= OFF
Outputs
rL.4
-
rL.6
= ON
Generic alarms
AL1
...
AL8
disabled
1
Outputs
rL.1
-
rL.2
-
rL.3
-
rL.5
= OFF
Outputs
rL.4
-
rL.6
= ON
Generic alarms
AL1
...
AL8
enabled