81901 “MSW_GPC-40/600A”_03-2021_ENG_page 58
3.13.13.
Alarm memory reset
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1103
79
bit
12.01.03
BIT_
RESET_
AL1_AL8
M
MainMenu
→
M
→
Expert
→
Bit
→
BIT_RESET_AL1_AL8_1
R/W
■
2127
12.02.03
E1
MainMenu
→
E1
→
Expert
→
Bit
→
BIT_RESET_AL1_AL8_2
4175
12.03.03
E2
MainMenu
→
E2
→
Expert
→
Bit
→
BIT_RESET_AL1_AL8_3
The parameter allows the memory of all generic alarms to be cleared by changing the state of the bit.
To clear the memory of a specific generic alarm, see parameters
dIG.1
,
dIG.2
,
dIG.3
and
dIG.4
for alarms 1, 2, 3 and 4 respectively
.
Options
:
OFF
= No function
ON
= Generic alarms AL1...AL8 are reset
3.13.14.
Alarm status (ALSTATE_IRQ)
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1342
318
16 bit
AL-
STATE_
IRQ
M
MainMenu
→
M
→
Status
→
ALSTATE_IRQ_1
R
2366
E1
MainMenu
→
E1
→
Status
→
ALSTATE_IRQ_2
4414
E2
MainMenu
→
E2
→
Status
→
ALSTATE_IRQ_3
The parameter shows the status of generic alarms AL1...AL8 and HB / POWER_FAULT alarms. Bit = 0 indicates the alarm is not active, bit
= 1 indicates the alarm is active.
The following table shows the correspondence between bit and individual alarms.
Options
:
bit
Description
Alarm type
0
Alarm status AL1
Generic alarm
1
Alarm status AL2
Generic alarm
2
Alarm status AL3
Generic alarm
3
Alarm status AL4
Generic alarm
4
Alarm status AL.HB (or phases 1/2/3 if three-phase) or POW-
ER_FAULT
Heater Break Alarm
/ POWER_FAULT
5
Alarm status AL.HB phase 1 (with three-phase load)
Heater Break Alarm
6
Alarm status AL.HB phase 2 (with three-phase load)
Heater Break Alarm
7
Alarm status AL.HB phase 3 (with three-phase load)
Heater Break Alarm
8
Alarm status AL5
Generic alarm
9
Alarm status AL6
Generic alarm
10
Alarm status AL7
Generic alarm
11
Alarm status AL8
Generic alarm