81901A “MSW_GPC-40/600A”_03-2021_ENG_page 65
3.14.6.
HB alarm threshold percentage
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1761
737
16 bit
05.04.04
Hb.P
M
MainMenu
→
M
→
Alarms
→
HB alarm
→
Hb.P_1
R/W
■
Float
(####.#)
%
80.0
2785
05.05.04
E1
MainMenu
→
E1
→
Alarms
→
HB alarm
→
Hb.P_2
4833
05.06.04
E2
MainMenu
→
E2
→
Alarms
→
HB alarm
→
Hb.P_3
The parameter sets the HB alarm threshold percentage of the current read in HB calibration.
min...max
:
0.0
...
100.0
3.14.7.
CT reading in HB calibration
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1766
742
16 bit
05.04.05
Hb.tA
M
MainMenu
→
M
→
Alarms
→
HB alarm
→
Hb.tA_1
R/W
■
Float
(####.#)
A
0.0
2790
05.05.05
E1
MainMenu
→
E1
→
Alarms
→
HB alarm
→
Hb.tA_2
4838
05.06.05
E2
MainMenu
→
E2
→
Alarms
→
HB alarm
→
Hb.tA_3
The parameter sets the CT reading in HB calibration.
min...max
:
0.0
...
3275.0
3.14.8.
VT reading in HB calibration
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1476
452
16 bit
05.04.06
Hb.tV
M
MainMenu
→
M
→
Alarms
→
HB alarm
→
Hb.tV_1
R/W
■
Float
(####.#)
V
0.0
2500
05.05.06
E1
MainMenu
→
E1
→
Alarms
→
HB alarm
→
Hb.tV_2
4548
05.06.06
E2
MainMenu
→
E2
→
Alarms
→
HB alarm
→
Hb.tV_3
The parameter sets the VT reading in HB calibration.
min...max
:
0.0
...
999.9
3.14.9.
Ou.P power in calibration
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1767
743
16 bit
05.04.07
Hb.Pw
M
MainMenu
→
M
→
Alarms
→
HB alarm
→
Hb.Pw_1
R/W
■
Float
(####.#)
%
0.0
2791
05.05.07
E1
MainMenu
→
E1
→
Alarms
→
HB alarm
→
Hb.Pw_2
4839
05.06.07
E2
MainMenu
→
E2
→
Alarms
→
HB alarm
→
Hb.Pw_3
The parameter sets the
Ou.P
power in HB calibration.
min...max
:
0.0
...
100.0