81901 “MSW_GPC-40/600A”_03-2021_ENG_page 40
3.12.4.
Digital input function
Address
Format
GPC-OP
menu
Acronym
Global /
M/E1/E2
GF_eXpress menu
Attribute
Retentive
Type
Unit of mea
-
surement
Default
Single-
node
Multi-
node
Description
1164
140
16 bit
04:17:01
dIG.1
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
dIG.1
R/W
■
Unsigned
Short
0
1642
618
16 bit
04:17:02
dIG.2
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
dIG.2
R/W
■
Unsigned
Short
0
1718
694
16 bit
04:17:03
dIG.3
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
dIG.3
R/W
■
Unsigned
Short
0
1736
712
16 bit
04:17:04
dIG.4
Global
MainMenu
→
Global
→
Inputs
→
Digital inputs
→
dIG.4
R/W
■
Unsigned
Short
128
This parameter sets the function associated with digital input 1, 2, 3 or 4, depending on the address used. The input can be activated by a
change in value (“On leading edge”) or by its state (“On state”).
Each main function is identified by an index. By adding a fixed value to the index, the functions are thus modified:
+16 = input in denied logic
+32 = logic state 0 (OFF) is forced
+64 = logic state 1 (ON) is forced
Options
:
Index
Description
Activation
0
No function (input disabled)
On leading edge
1
MAN / AUTO controller
On leading edge
4
Generic alarm memory reset AL1...AL8
On state
6
Software ON/OFF
On leading edge
7
PWM * input
On leading edge
10
Reset POWER_FAULT alarm memory
On leading edge
12
AL1...AL8 and POWER_FAULT generic alarm memory reset
On state
13
Enable software startup **
On state
14
Reference calibration of feedback selected by
hd.6
On leading edge
15
HB alarm threshold calibration
On leading edge
64
FUSE_OPEN / SHORT_CIRCUIT_CURRENT alarm reset
On state
65
Reference calibration of feedback selected by
hd.6
for GPC-M
On leading edge
66
Reference calibration of feedback selected by
hd.6
for GPC-E1
On leading edge
67
Reference calibration of feedback selected by
hd.6
for GPC-E2
On leading edge
68
Calibration of HB alarm threshold for GPC-M
On leading edge
69
Calibration of HB alarm threshold for GPC-E1
On leading edge
70
Calbiration of HB alarm setpoint for GPC-E2
On leading edge
71
MAN / AUTO for GPC-M
On leading edge
72
MAN / AUTO for GPC-E1
On leading edge
73
MAN / AUTO for GPC-E2
On leading edge
74
ON / OFF Software for GPC-M
On leading edge
75
ON / OFF Software for GPC-E1
On leading edge
76
ON / OFF Software for GPC-E2
On leading edge
77
Trigger change for GPC-M
On state
78
Trigger change for GPC-E1
On state
79
Trigger change for GPC-E2
On state
128
Interlock
On state
*) only for
dIG.1
(PWM1, max 100 Hz),
dIG.2
(PWM2, max 1 Hz),
dIG.3
(PWM3, max 1 Hz)
**) only for
dIG.1
Examples
Setting value “4” activates the cancellation function of alarms AL.1...AL.8 (e.g., by closing the digital input); by setting 20 (=4+16) the
AL.1...AL.8 alarm cancellation occurs with denied logic (e.g., by opening the digital input).