Input Linearization
This menu lets you run custom linearization.
Number segments
[1 ... 32]
. . . . .
Engineering value attributed to start
of scale
[-19999 ... 99999]
Input value expressed as 1/10000 f.s.
attributed/acquired corresponding to engi-
neering value
S.01b
[0 ... 10000]
(**)
Engineering value attributed to
point 1
[-19999 ... 99999]
Input value expressed as 1/10000 f.s.
attributed/acquired corresponding to engi-
neering value
S.nnb
[0 ... 10000]
(**)
Engineering value attributed to
point nn
[-19999 ... 99999]
Step 0 (start scale value)
Display limits:
[-19999 ... 99999] (*)
Step 64 (full scale value)
Display limits:
[-19999 ... 99999] (*)
..........
(*)
Step “n” value corresponds to input:
mV start scale + n* mV
mV = (mv full scale – mV start scale) / 64
mV start scale
[-19.99 ... 99.99]
mV full scale
[-19.99 ... 99.99]
mV at temperature of 50 °C
[-1.999 ... 9.999]
Only with parameter
TYP
menu
INP
= TC Custom
Linearization type 5
Linearization type 0 ... 4
0
Variable intervals (max 32)
1
Variable intervals (max 32)
self-learning from IN1
2
Variable intervals (max 32)
self-learning from IN2
3
Variable intervals (max 32)
self-learning from IN3
4
Variable intervals (max 32)
self-learning from IN4
5
Linearization at 64 constant intervals
Linearization type
[0 ... 5]
nn assumes the maximum
value set in
Step.n
(**)
With self-learning, the acquired input value is
displayed.
Press key “F” to confirm the value.
PV
Lin
PV
tyP.L
PV
SteP.n
PV
S.00
PV
S.01 A
PV
S.01 b
PV
S.nn A
PV
S.nn b
PV
S.tc1
PV
S.tc2
PV
S.tc3
PV
S.00
PV
S.64
N.B.: must match value set in LoS.x
N.B.: must match value set in LoS.x
N.B.: must match value set in HiS.x
N.B.: the decimal point of the input appears only with
self-learning and only in
S.nnb