Setting Input 1
This menu lets you configure parameters for the input 1 signals
Probe type, signal, enable custom linearization,
and main input scale.
Probe type
Scale limits
0
Input disabled
1
TC J °C
0/1000
2
TC J °F
32/1832
3
TC K °C
0/1300
4
TC K °F
32/2372
5
TC R °C
0/1750
6
TC R °F
32/3182
7
TC S °C
0/1750
8
TC S °F
32/3182
9 TC
T °C
-200/400
10
TC T °F
-328/752
11
PT100 °C
-200/850
12
PT100 °F
-328/1562
Probe type
Scale limits
13
Potentiometer
≥
100
Ω
-19999/99999
with 2.5V power supply
14
Strain gauge
-19999/99999
positive polarization
sensitivity: 1.5 ... 4mV/V
15
Strain gauge
-19999/99999
symmetrical polarization
sensitivity: 1.5 ... 4mV/V
16
60mV
-19999/99999
17
±60mV
-19999/99999
18
100mV
-19999/99999
19
±100mV
-19999/99999
20
1V
-19999/99999
21
±1V
-19999/99999
22
5V
-19999/99999
23
±5V
-19999/99999
24
10V
-19999/99999
25
±10V
-19999/99999
26
0...20 mA
-19999/99999
27
4...20 mA
-19999/99999
28
Strain-gauge positive
-19999/99999
polarization calibrated 40mV
29
Strain-gauge symmetrical
-19999/99999
polarization calibrated 40mV
Note
- For input type 27 (4...20mA), a current below 2mA causes the
Err
and activates the assigned relay state specified with parame-
ter
-rEL
.
- The type 28, 29, 30, 31 input can be used without having to cali-
brate the probe. Simply enter the Offset and Sensitivity data reque-
sted in configuration (ex.: 0.193mV; 1.985mV/V).
- For types 28, 29 Maximum sensitivity is 4mV/V with 10V power
supply.
- For types 30, 31 Maximum sensitivity is 6mV/V with 10V power
supply.
PV
Input 1 Digital Filter
[0.00 ... 20.00] sec
If set to “0” the average filter is excluded on the sampled
value
InP.1
tyP.1
+32 with custom linearization
+64 only for cold junction compensation thermocouples
Decimal Point Position for Scale
Input 1
MIN Scale Limit Input 1
MAX Scale Limit Input 1
Offset Correction Input 1
[-999 ... +999] scale points
Offset Input 1
[-9.999 ... +9.999] mV
Sensitivity Input 1
[-0.000 ... +9.999] mV/V
Only for probe type 28, 29
PV
F1t.1
PV
dPS.1
PV
LoS.1
PV
x1S.1
PV
0FS.1
PV
SG0F.1
PV
SGSE.1
Size
0
xxxxx
1
xxxx.x
2
xxx.xx (*)
3
xx.xxx (*)
4
x.xxxx (*)
(*) Not available for TC, RTD
probes
Min...Max value assigned to input selected with
parameter
TYP1
+8 disables the
Lo
and
x1
messages for linear inputs only
+16 disables the
Ebr
message
+32 for differential linear inputs probe type 16...25
N.B.:
the scale limits can be reversed for linear inputs only