![gefran 2400 Installation And Operation Manual Download Page 15](http://html.mh-extra.com/html/gefran/2400/2400_installation-and-operation-manual_2205726015.webp)
15
80290C_MHW_2400_0908_ENG
14
15
16
17
18
19
no/nc +
c -
no/nc +
no/nc +
c -
no/nc +
OUT 1
OUT 2
OUT 3
OUT 4
Digital inputs (PNP), 24V, max. 5mA or voltage-free contact (NPN) max. 5mA
Single selection PNP/NPN for DI1, DI2 by setting configuration parameter (Hd1 = +8)
22
20
21
COM
DI2
DI1
Digital inputs DI1, DI2
Electrical Connections
(for all models)
OUT 1, OUT 2, OUT 3, OUT 4 outputs
Relay 5A, 250Vac/30Vdc
Select the no/nc contacts via jumper on power
supply board (standard contact no)
(see section 6 - maintenance)
Logic 24V/30mA max
Connection with logic output
The MD8 expansion interface (D, Gnd, CK) is an alternate to outputs OUT 3, OUT 4
MD8
CK
Gnd
D
+
+
+
Load
Load
OUT (type source)
OUT (type sink)
24Vext