Setting Input 4
This menu lets you configure parameters for the input 4 signals.
Probe type, signal, enable custom
linearization, and main input scale
Input 4 Digital Filter
[0.00 ... 20.00] sec
If set to “0” the average filter is excluded on the sampled
value
Decimal Point Position for Scale
Input 4
Size
0
xxxxx
1
xxxx.x
2
xxx.xx
3
xx.xxx
4
x.xxxx
MIN Scale Limit Input 4
Min...Max value assigned to input selected with
parameter
TYP4
MAX Scale Limit Input 4
Offset Correction Input 4
[-999 ... +999] scale points
Probe type
Scale limits
0
Input disabled
1
0...10V
-19999/99999
2
0...20mA
-19999/99999
3
4...20mA
-19999/99999
4
potentiometer
-19999/99999
+32 enable custom linearization
PV
InP.4
PV
tyP.4
PV
F1t.4
PV
dPS.4
PV
LoS.4
PV
x1S.4
PV
0FS.4
N.B.:
the scale limits can be reversed
+8 disables the
Lo
and
x1
messages