Cooling Performance Data
Zoneline 2800 & 800 Series
Zoneline 2800 Dry Air 25
Zoneline 5800 Series
Nominal Capacity
Nominal Capacity
Nominal Capacity
Temperature of Air
Entering Condenser
7000
9000
12000
15000
7000
9000
12000
7000
9000
12000
15000
75
7750
9950
12950
15850
7400
9500
12250
7750
9950
12950
15850
82
7500
9700
12600
15500
7200
9200
11900
7500
9700
12600
15500
85
7400
9500
1250
1500
6950
9050
11750
7400
9500
1250
1500
95
7100
9000
11700
14600
6800
8600
11200
7100
9000
11700
14600
105
6700
8400
11000
1600
6400
8100
10600
6700
8400
11000
1600
115
600
7800
10400
1200
6000
7650
10000
600
7800
10400
1200
Total Capacity - BTUH
BTUH at 80º F D.B. - 67º F W.B.
Heat Pump Performance Data
Capacities and COP at Various Outdoor Temperatures
BTUH at 70º F Indoor Temperature
Zoneline 800 Series
Outdoor
Temperature F
7000
9000
12000
15000
65
7500
.85
10000
.85
12950
.65
15950
.45
60
7200
.80
9600
.80
12500
.60
1500
.40
55
6900
.75
9100
.75
11850
.55
14650
.5
50
6600
.65
8700
.65
1100
.45
1850
.25
47
6400
.60
8400
.60
10900
.40
1400
.20
45
6250
.55
8200
.55
10600
.5
1050
.15
40
5950
.45
7700
.45
9800
.20
12250
.05
5
5600
.5
7100
.5
9200
.10
1100
2.95
0
5250
.20
6500
.20
800
.00
1000
2.85
25
4700
.05
5900
.05
7500
2.85
9250
2.75
All data at 20 volts and 265 volts.
Zoneline 5800 Series
Outdoor
Temperature F
7000
9000
12000
15000
65
7500
.85
10000
.85
12950
.65
15950
.45
60
7200
.80
9600
.80
12500
.60
1500
.40
55
6900
.75
9100
.75
11850
.55
14650
.5
50
6600
.65
8700
.65
1100
.45
1850
.25
47
6400
.60
8400
.60
10900
.40
1400
.20
45
6250
.55
8200
.55
10600
.5
1050
.15
40
5950
.45
7700
.45
9800
.20
12250
.05
5
5600
.5
7100
.5
9200
.10
1100
2.95
0
5250
.20
6500
.20
800
.00
1000
2.85
25
4700
.05
5900
.05
7500
2.85
9250
2.75
All data at 20 volts and 265 volts.