background image

49

ge.com

Typical 800 Series, 208/20-Volt Wiring Diagram

Typical 800 Series, 208/20-Volt Schematic Diagram

Summary of Contents for Zoneline AZ28E09DAP

Page 1: ...GE Zoneline packaged terminal air conditioners 2007 contract sales architects and engineers data manual ...

Page 2: ...200 11 0 3800 Series Heat Pump with Backup Electric Heat MODEL NUMBER COOLING Btuh EER Reverse Cycle BTUH COP AZ38H07DA 7100 6900 12 7 12 7 6400 6200 3 6 3 6 AZ38H09DA 9000 8800 12 0 12 0 8400 8200 3 6 3 6 AZ38H12DA 11700 11500 11 5 11 5 10900 10700 3 4 3 4 AZ38H15DA 14600 14300 10 0 10 0 13400 13200 3 2 3 2 AZ38H07EA 7100 12 7 6400 3 6 AZ38H09EA 9000 12 0 8400 3 6 AZ38H12EA 11700 11 5 10900 3 4 A...

Page 3: ... 13900 5000 4090 22 3 20 3 30 Electric Heat Amps include electric heater and fan motor current draw Units connected through sub base do not require a LCDI or AFCI device since they are not considered to be line cord connected Each 230 208 volt sub base kit consists of sub base with appropriate receptacle for minimum circuit amperage chaseway to route power connector from sub base to chassis wiring...

Page 4: ...ine refrigerant circuit As warm humid air is pulled through the pre cool front section of the heat pipe the heat removed from the air is absorbed by the refrigerant causing the refrigerant to change to a gas and flow to the re heat rear section of the heat pipe The air leaving the pre cool section of the heat pipe is cooler and at a higher relative humidity level than the room air The pre cooled a...

Page 5: ... 44 Cooling Heat Pump Performance Data 45 Latent System Capacity 46 Normal Yearly Operating Data 47 Schematics 48 50 Product Specifications Suggested Bid Form Specifications 51 53 Zoneline Chassis Nomenclature Receptacles Sub bases 54 Specifications 55 Complete Accessory List 56 General Installation Suggestions 57 58 Warranty 58 Alphabetical Index 59 Back Cover 60 Important Notice Equipment used a...

Page 6: ...lemental Resistance Heat on Heat Pumps Quick Heat Recovery Deluxe Line Optional Features Corrosion Protection Internal Condensate Removal on 3800 Series Heat Pump without Corrosion Protection NOTE Dry Air 25 models include all the standard features of the 2800 Series plus standard corrosion protection Premium Line Standard Features All the Standard Features of the Deluxe Line Plus Two fan motor sy...

Page 7: ...of failure not covered by the warranty Components of the Zoneline System Typical Installation Deluxe Series shown See pages 23 and 33 for information on electrical sub bases and chaseway See pages 37 39 for information on ducted installations RAK601 602 For Deluxe Series Duct Extension Register and Trim Flange RAK6052 Duct Adapter For Deluxe Series Wall Case RAB71A Steel Insulated RAB77 SMC Molded...

Page 8: ...tandard HIGH LOW AUTO Fan Only Setting HIGH LOW Standard Standard Standard Fan Cycle Switch Smart Fan Smart Fan Smart Fan Constant Run Fan Selectable Selectable Selectable Rotary Compressor Standard Standard Standard Automatic Compressor Restart Delay Standard Standard Standard Freeze Sentinel Standard Standard Standard Heat Sentinel Standard Standard Standard Indoor Coil Frost Control Standard St...

Page 9: ...Heat Automatically uses electric resistance heat if the heat pump output is not sufficient to maintain selected room temperature Reverse Cycle Heat Pump Defrost System Standard on all Zoneline 3800 and 5800 Series heat pumps Enables heat pump to operate at lower temperatures when other systems switch to more expensive electric resistance heat See pages 18 and 19 for discussion of heat pump operati...

Page 10: ... off when the room temperature reaches 80 F This will help dehumidify the air and lower high temperatures so the guest will not be entering an extremely hot room Indoor Coil Frost Control Prevents indoor coil from freezing and causing complaints due to lack of cooling Frost can form on the indoor coil when the unit is operated in cooling when outdoor temperatures are low The unit automatically shu...

Page 11: ...r withstand damage from salt air and salt water in seacoast areas Corrosion protection is standard on the 5800 Series and on Dry Air 25 models Heat Pump units with ICR are not available with corrosion protection and should not be installed in seacoast or corrosive environments Units installed in corrosive areas should be examined and cleaned more frequently than normal installations Internal Conde...

Page 12: ...ing temperature limiting See table at bottom of page TL4 TL6 Heating temperature limiting See table at bottom of page 7 Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON 8 Heat Boost 3800 series only Down Heat Boost OF Up Heat Boost ON Auxiliary 2800 and 3800 series HIGH COOL 1 2 3 4 5 6 1 2 3 4 5 6 7 8 UP DOWN UP DOWN ALLI2 R All Electric Heat 3800 Series models only C FAN CN Coolin...

Page 13: ...perature limiting See table at bottom of page TL4 TL6 Heating temperature limiting See table at bottom of page 7 Diagnostics Switch 8 Heat Sentinel switch Down Heat Sentinel OFF Up Heat Sentinel ON 9 Heat Boost Down Heat Boost OFF Up Heat Boost ON Cooling and Heating temperature limits are set independently temperature limiting switches are in factory set down position except as noted Cooling Temp...

Page 14: ...tems Consult with the provider of other energy management systems to be sure they are compatible with the GE Zoneline Zonelines have standard connectors factory installed to provide a CDC interface that permits the unit to be connected to most of the energy management systems The devices connected to the Zoneline units require no power supply or transformers external to the unit Important CDC Comm...

Page 15: ...tat wiring should not be run parallel to line voltage wires since induced current may cause erratic operation All Zoneline 2800 3800 and 5800 Series units are adaptable to Class 2 remote low voltage thermostat The only additional field supplied components are the remote thermostat and wiring necessary to connect it The controls on the unit are not functional when the remote control function is use...

Page 16: ...nits will operate slightly differently when connected to a remote thermostat The following chart shows the unit operation when connected to a remote thermostat Field Wiring Terminal R 24V AC GL Low Speed Fan GH High Speed Fan B Reversing Valve Y Compressor W Heater C Common Ground Zoneline Series Thermostat Model Type Function Low Voltage Conductors 2800 RAK163A1 Mechanical Cooling and Heating 4 R...

Page 17: ...hrough the use of field supplied isolation relays For Use With Mechanical 4 Wire Systems Only Remote Control Low Voltage Wiring One stage Thermostat Controlling Three Zoneline Units Resistance Heat Zoneline 2800 Series Units Not Applicable on Heat Pump Units Number Of Units Controlled Relay Designation R1 R2 And R3 2 POTTER and BRUMFIELD TYPE KA11AY 24 OR EQUIVALENT 3 POTTER and BRUMFIELD TYPE KA1...

Page 18: ...kup to heat pump operation At some point the heat pump is unable to provide sufficient heat to adequately warm the room Many Packaged Terminal Heat Pumps cease heat pump operation and change to more expensive resistance heat at some pre determined outdoor temperature to compensate for the inability of the heat pump to maintain room temperature This point called the switchover point is usually at a...

Page 19: ... unit is designed to provideheatpumpsavingswithoutsacrificingroomcomfort The Quick Heat Recovery feature is not affected by the Heat Source Logic shown in the chart above For more information about the Quick Heat Recovery Feature see page 9 The full heat output of the resistance heater is dependent upon circuit amperage and the power connection kit used See pages 3 and 42 43 for information on pow...

Page 20: ...ized cooling capacity is greater than required for the specific application the unit will typically cool the space down to the desired temperature thermostat set point too quickly The compressor then begins to cycle on and off Dehumidification only takes place when the compressor is operating A typical result in a hot humid climate could be a cool but excessively humid space Heating Undersizing ca...

Page 21: ...hs RAB7116 16 RAB7124 24 RAB7128 28 RAB7131 31 42 13 3 4 16 1 1 2 TYP 1 2 6 21 36 A 1 2 SQ HOLE 2 REQ D 1 2 DIA HOLE 3 REQ D 2 3 4 5 5 8 4 6 19 36 16 1 4 13 7 8 1 1 2 42 1 8 1 2 SQ HOLE 2 REQ D 9 16 2 7 8 5 5 8 4 1 2 DIA 3 REQ D RAB71 42 RAB77 42 1 8 RAB71 13 3 4 RAB77 13 7 8 42 TOP VIEW GRILLE ROOM CABINET INSIDE ROOM CABINET SIDE VIEW RAB71 20 7 8 RAB77 21 OUTSIDE RAB71 16 RAB77 16 1 4 GRILLE 7 ...

Page 22: ...ust conform to any and all local electrical codes and regulations Permanent Connection generally means wiring to the unit must be contained in an enclosed chaseway where access to the wiring connections is more restrictive than a normal line cord plugged into a receptacle NEC requirements may be met by using flexible or rigid conduit to contain the wiring between the unit and a junction box that c...

Page 23: ...h in the wall and these installations usually require a remote thermostat and are discussed on pages 15 and 16 Regardless of the installation there are several things to consider when selecting a location for installing the unit For instance drapery location could interfere with air discharge and placement of furniture may have an impact on the performance of the unit The following information is ...

Page 24: ... be located both near the wall and at the front of the wall case Sub base RAK204 Series with four leveling legs provides an excellent support for the unit in this type of installation See page 28 for details of this type of installation In existing construction common practice is to remove a pane of glass metal wood or other construction material and build a frame around the wall case Similar fill...

Page 25: ...s greater than the case dimensions spacers must be used on the sides between the wall case and the wall support structure to prevent distorting the wall case 3 Caulk or gasket the entire opening on the outside between the wall case and exterior wall surface 4 sides to provide total water and air seal 4 Caulk or gasket room side opening between wall case and interior wall surface 4 sides Opening be...

Page 26: ...ed MAIN STUDS JACK STUD HEADER MOUNTING SCREW HOLE LINTEL Framing detail for this construction is as shown in Figure 1 Note use of lintel under first course of brick above the Zoneline case Do not use the case as a lintel Mounting screw holes shown are to be made by the installer NO HOLES PERMITTED IN BOTTOM OF CASE EXCEPTION RAD10 DRAIN KIT Choice of attachment devices through both ends of case o...

Page 27: ...DUIT WALL RECEPTACLE BY OTHERS FINISHED FLOOR OR TOP OF CARPET Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior CAULK 1 4 CAULK LINTEL RAB71 13 3 4 RAB77 13 7 8 20 7 8 RAB71 21 RAB77 ROOM CABINET 2 MIN MOUNTING SCREWS BY INSTALLER RAB71 16 RAB77 16 1 4 WALL CASE OUTDOOR GRILLE SIDE CHANNEL 3 MIN 5 MAX 1 5 16 FINISHED FLOOR OR TOP OF CARPET SUB BA...

Page 28: ...CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB71 16 RAB77 16 1 4 RECEPTACLE BY OTHERS MIN 2 SUPPORTS FIELD SUPPLIED FLOOR USE NO SCREWS IN BOTTOM OF CASE 16 ROOM CABINET WALL CASE OUTDOOR GRILLE CASE ANGLE FIELD SUPPLIED RAB71 22 1 4 RAB77 22 3 8 WITH RAG61 66 RAB71 21 1 8 RAB77 21 1 4 WITH RAG60 RAB71 16 RAB77A 16 1 4 16 WALL OR WINDOW G...

Page 29: ...77 42 1 8 FINISHED EXTERIOR WALL ROOM CABINET RAB71 13 3 4 RAB77 13 7 8 ADJACENT WALL ADJACENT WALL D A C D 27 1 4 TOP VIEW 2 1 2 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior ROOM CABINET LINTEL FRONT VIEW ELECTRICAL RECEPTACLE BY OTHERS FLUSH MOUNTED WALL OPENING 16 1 4 x 42 1 4 MIN FOR RAB71 16 1 2 x 42 3 8 MIN FOR RAB77 See page 42 for lin...

Page 30: ...dditionally sealed with a quality grade sealant 2 T he wall case and extension should be connected prior to installation in the wall opening A quality grade sealant should be applied to all four 4 butting flanges Use bolts and nuts or oversized self tapping screws driven from the wall case to the extension to attach the two assemblies Clean all drain holes of excess sealant The assembly must be fr...

Page 31: ...TED TO WALL SURFACE A SPLITTERS MUST BE USED SEE PAGE 30 B D C A B Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior 1 WIDE 45 DRIP LIP FLASHING OUTDOOR GRILLE CASE For an installation that will provide better protection against water infiltration GE recommends the use of one of the deeper RAB71 wall cases offered as special order items See page 2...

Page 32: ...EE NOTE LEFT SIDE INTERIOR ADJACENT WALL 12 3 4 12 7 8 13 LEVELING SCREW KNOCKOUT SIZE LARGE 1 1 8 DIA SMALL 7 8 DIA KNOCKOUTS ENCLOSURE 4 REAR 4 BOTTOM SHOWN WITH ACCESS COVERS REMOVED NOTE CAUTION REMOVE KNOCKOUTS FROM INSIDE OUT SIDE VIEW WITH WALL CASE SHOWN IN PLACE FINISHED FLOOR 3 MIN ADJUSTABLE TO 5 1 5 16 2 3 8 INTERIOR WALL RAB71 16 RAB77 16 1 4 7 8 1 1 2 FINISHED FLOOR RAB71 16 RAB77 16...

Page 33: ...G TYPE A SCREWS 6 TYPE A SCREW TYPE C SCREW ACCESS PLATES TYPE C SCREW TYPE B SCREW SIDE CHANNELS ARE ADJUSTABLE FROM 13 3 4 TO 2 3 8 IN LENGTH BY BREAKING OFF SECTIONS OF SIDE CHANNELS NOTE IF METAL CASE DOES NOT HAVE SCREW HOLES 5 32 DIA HOLES MUST BE DRILLED 6 FROM EACH SIDE IN FRONT FLANGE SEE INSERT Electrical wiring may enter the sub base through any of the knockout holes provided in the sub...

Page 34: ...ing cooling operation Since the dew point is humidity as well as temperature related there may be more condensate on days when the relative humidity is high Heat Pump Condensate Disposal Since the outdoor coil is cold during heat pump operation the condensate water cannot be deposited on the outdoor coil as the water would cause frost to form on the coil This frost would block the airflow through ...

Page 35: ... water or precipitation to flow into the wall case and drain through two drain holes in the rear of the wall case If there is more water in the wall case than can be drained through these holes it will drain through the three overflow drain holes These drain holes must not be blocked when mounting or caulking the wall case For those installations where water draining from the drain holes is object...

Page 36: ...e bottom of the wall case prior to installation of the case in the wall It may be located anywhere on the room side portion except for sub base installations For these the drain should be at least 3 from the indoor edge of the case so as to adequately clear the sub base 3 A template is furnished with the kit for locating the necessary 3 holes in the case bottom two to provide a securing means and ...

Page 37: ...ations providing the sum of the two duct lengths necessary do not exceed the 44 length Even in single applications the mounting flange must be cut off one end of the duct to accept the collar and supply register Mounting Collar and Supply Register RAK602 These components are included in the Duct Extension Kit RAK601 They may be ordered separately for installations where two duct extensions are mad...

Page 38: ...ille mounting collar and discharge grille Duct extension must be cut to required length Two ducted installations may be made from one kit if the combined ducted length is less than 44 RAK602 kit contains mounting collar discharge grille and mounting hardware necessary for second installation 5 F iller strip field supplied actual width depends upon wall case projection into room A flush installatio...

Page 39: ...LOCATIONS CAULK RAG60 1 4 RAG61 66 1 3 8 Caulk around perimeter of wall case all four sides where it joins the building Interior and Exterior 1 4 MIN 2 29 32 2 3 8 min when installed with RAK204 RAG60 1 4 RAG61 66 1 3 8 3 11 16 RAK 204 3 MIN 5 MAX FINISHED FLOOR 16 1 8 TRANSITION ROOM CABINET WALL CASE Caulk around perimeter of wall case all four sides where it joins the building Interior and Exte...

Page 40: ...opening The best appearance is achieved with this grille when the wall case extends minimally between 1 4 and 1 2 beyond the exterior face of the building Colors RAG61 and 64 Beige RAG62 and 65 Dark Maple RAG63 and 66 Bittersweet Chocolate RAG67 Extruded Aluminum Grille The RAG67 is made from extruded anodized aluminum for use where an aluminum architectural grille is preferred The RAG67 is availa...

Page 41: ...let If the louver is not attached directly to the wall case a field supplied splitter or gasket is required between the chassis and the louver to prevent recirculation It is important that the above criteria be followed since a louver that is too restrictive or allows recirculation will reduce the unit s capacity and efficiency increase the electrical current draw cause intermittent operation due ...

Page 42: ...to connect to chassis and plug into the receptacle in the sub base Permanent or direct wired installation of a 230 208 volt unit requires a junction box kit RAK4002A which attaches to the chassis to form an enclosed junction box The short sub base line cord may not be used without the sub base For 2800 and 3800 Series 230 208 volt units where a permanent installation using flexible conduit is desi...

Page 43: ...it was first introduced Some of these changes require alterations to be made when replacing an older unit with a new chassis Line Cord Connected Units The plug configuration of new line cord connected units complies with the current NEC standards Older installations may have wall receptacles that conformed to NEC standards at the time the building was constructed and may not match the configuratio...

Page 44: ... AZ58H07DA 11 5 10 5 15 5 14 1 N A N A AZ58H09DA 11 5 10 5 15 5 14 1 22 3 20 3 AZ58H12DA 11 6 10 6 15 5 14 1 22 3 20 3 AZ58H15DA 11 6 10 6 15 6 14 2 22 4 20 4 All versions Electric Heat Amps include electric heater and fan motor current draw Values shown in table above are also the total connected loads for units installed with sub bases RAK204D15P same as RAK3153 RAK204D20P same as RAK3203 RAK204...

Page 45: ...9000 12000 15000 65 7500 3 85 10000 3 85 12950 3 65 15950 3 45 60 7200 3 80 9600 3 80 12500 3 60 15300 3 40 55 6900 3 75 9100 3 75 11850 3 55 14650 3 35 50 6600 3 65 8700 3 65 11300 3 45 13850 3 25 47 6400 3 60 8400 3 60 10900 3 40 13400 3 20 45 6250 3 55 8200 3 55 10600 3 35 13050 3 15 40 5950 3 45 7700 3 45 9800 3 20 12250 3 05 35 5600 3 35 7100 3 35 9200 3 10 11300 2 95 30 5250 3 20 6500 3 20 8...

Page 46: ...ts except 63 0 46 0 62 0 77 0 92 1 00 1 00 1 00 1 00 Dry Air 25 67 0 42 0 60 0 75 0 88 1 00 1 00 1 00 71 0 42 0 54 0 66 0 78 0 90 1 00 AZ28E07DAP EAP 59 0 38 0 49 0 65 0 80 0 95 1 00 1 00 1 00 1 00 Dry Air 25 63 0 38 0 54 0 68 0 80 1 00 1 00 1 00 1 00 67 0 35 0 52 0 66 0 79 0 92 1 00 1 00 71 0 32 0 45 0 58 0 73 0 85 1 00 All 9000 BTUH 59 0 42 0 59 0 77 0 93 1 00 1 00 1 00 1 00 1 00 units except 63...

Page 47: ...049 520 Glasgow 8 996 410 Great Falls 7 750 420 Missoula 8 125 350 NEBRASKA Grand Island 6 530 770 Omaha 6 612 750 NEVADA Ely 7 733 500 Las Vegas 2 709 1 980 Reno 6 332 520 NEW JERSEY Newark 4 589 710 NEW MEXICO Albuquerque 4 348 1 040 Clayton 5 158 720 Silver City 3 705 1 260 NEW YORK Albany 6 875 480 Binghamton 7 286 310 Buffalo 7 062 450 New York 4 811 790 Rochester 6 748 470 Syracuse 6 756 500...

Page 48: ...48 Typical 2800 Series 208 230 Volt Wiring Diagram Typical 2800 Series 208 230 Volt Schematic Diagram ...

Page 49: ...49 ge com Typical 3800 Series 208 230 Volt Wiring Diagram Typical 3800 Series 208 230 Volt Schematic Diagram ...

Page 50: ... 265V 208 230V COLOR BK BLACK BL BLUE BR BROWN GR GREEN GY GRAY OR ORANGE RD RED WH WHITE YL YELLOW RD 1 RED 208 230V BLUE 265V WH O L P COMP MOTOR RUNNING CAPACITOR C S R HEATER PROTECTOR RY102 RY109 RY103 OUTDOOR FAN MOTOR INDOOR FAN MOTOR FAN MOTOR CAPACITOR FAN MOTOR CAPACITOR CN102 CN101 RY106 RY107 RY104 RY105 CN8 CN103 Varistor NR101 Capacitor C101 C102 FUSE FU101 DRIVE BOARD UNIT REGULATOR...

Page 51: ...rmined by connection to the power source with the appropriate power connection kit to provide specified heat output A fan cycle switch to permit continuous fan operation or fan cycle operation independently selectable for heating and cooling operation Fan only operation in either high or low fan speed selectable by room occupant Suggested Bid Form Specifications A positive cooling condensate dispo...

Page 52: ...3800 or 5800 series heat pump units The unit shall have a factory installed Internal Condensate Removal ICR system to permit unit to automatically dispose of heat pump generated condensate water with no overflow to outdoors during heating under outdoor ambient of 55 F Dry Bulb 90 Relative Humidity indoor ambient 70 F Dry Bulb 52 Relative Humidity for four hours of continuous run time Wall Cases an...

Page 53: ...rsonnel Start Up Adjust Demonstrate Contractor shall be responsible for the initial starting of units adjustments thereto etc to place the units in required operating condition Contractor shall demonstrate to the owner or his representative the operation of units for both summer and winter functions Warranty The warranty shall be a full one year parts and labor on the entire unit plus an additiona...

Page 54: ...ne chassis see chart below The correct kit for the installation is determined by the voltage and amperage of the electrical circuit and the means of connecting the unit to the building wiring If the unit is to be plugged into a receptacle a line cord kit would be used if the unit is to be permanently connected apermanentconnectionkitwouldbeused 265 voltcordsetunitsmust be installed in compliance w...

Page 55: ...2 7 12 0 11 5 10 0 13 0 12 0 11 5 10 2 Dehumidification Pts Hr 1 7 2 7 3 6 4 5 1 7 2 8 3 6 4 8 Sensible heat ratio 265 volts 75 68 67 67 75 67 68 65 CFM indoor fan high 250 270 300 310 240 290 330 350 CFM indoor fan low 215 235 260 260 220 270 310 330 Vent CFM full open partial open 50 40 70 45 75 45 75 45 50 40 70 45 75 45 75 45 Power Ratings Power factor 96 94 94 96 96 94 94 96 Watts 560 750 102...

Page 56: ...cluded 23 RAK204E15 Sub Base 265 Volt with NEMA 7 15R 15 Amp Receptacle Chaseway included 23 RAK204E20 Sub Base 265 Volt with NEMA 7 20R 20 Amp Receptacle Chaseway included 23 RAK204E30 Sub Base 265 Volt with NEMA 7 30R 30 Amp Receptacle Chaseway included 23 RAK204U Sub Base non electrical Chaseway not included 22 RAK205CW Chaseway for Sub Base 22 RAK3153 Universal Power Cord 2800 3800 5800 series...

Page 57: ...can be run through the sub base entering the rear and exiting through one of the front panels When the room cabinet is in place the CDC or remote thermostat wiring is usually not visible to someone standing or sitting in the room Do not run the low voltage wiring in conduits with line voltage wiring or near uninsulated line voltage wiring since induced current can interrupt the low voltage control...

Page 58: ...0 Series unit can be installed using the same components that were used for the 2200 or 3200 Series unit If the existing chassis is a slope front discharge and the duct dimensions are 7 3 32 high by 6 1 2 wide only the RAK7022 transition piece is required to install a 2800 or 3800 Series unit in the ducted installation There were a number of Zoneline units installed in ducted installations that di...

Page 59: ...stallation Suggestions 57 58 Heat Pumps and Energy Savings 18 19 Introduction to Zoneline 6 Latent System Capacity 46 Maximum Connected Load 44 Mini Specs 2800 2 Mini Specs 3800 2 Mini Specs 5800 2 Mini Specs Power Connection Kits and Nomenclature 3 Normal Yearly Operating Data 47 Remote Thermostat Control 15 17 Schematics 48 50 Specifications 55 Suggested Big Form Specifications 51 53 Table of Co...

Page 60: ...dition of quality and innovation continues GE has a policy of continuous improvement of its products and reserves the right to change materials and specifications without notice 2007 GE Company Pub No 20 S087 PC48947 Before purchasing an appliance read important information about its estimated annual energy consumption or energy efficiency rating that is available from your retailer or ge com GE C...