11.10
SVCREQ 9: Read Sweep Time from Beginning of
Sweep
Use SVCREQ 9 to read the time in milliseconds since the start of the sweep. The data
format is unsigned 16-bit integer.
11.10.1
Output Parameter Block Format for
SVCREQ 9
The parameter block is an output parameter block only; it has a length of one word
address
time since start of sweep
11.10.1.1
Example of SVCREQ 9
In the following example, the elapsed time from the start of the sweep is always read into
location %R0200. If it is greater than 100ms, internal coil %M0200 is turned on.
CONST
00009
SVC_
REQ
FNC
PARM
I1
I2
Q
GT_
INT
CONST
0100
%M0200
%R0200
%R0200
The Service Request Function
GFK-1503E User Manual 211
For public disclosure