5.3.3
Configurable Memory for CPU Module
IC200CPUE05
Configurable memory
128K bytes maximum
Application program size (not configurable)
128 bytes minimum
Hardware configuration size (not configurable)
528 bytes minimum
Registers (%R)
256 bytes (128 words) minimum
Analog Inputs (%AI)
256 bytes (128 words) minimum
Analog Outputs (%AQ)
256 bytes (128 words) minimum
If you reconfigure memory allocation from the default sizes, storing a hardware
configuration to the PLC in the future will clear memory contents. If you want to retain
memory contents, first load memory contents from the PLC to the programmer. Then,
re-store memory when you store the hardware configuration from the programmer to the
PLC.
Configuration
GFK-1503E User Manual 75
For public disclosure