GE Multilin
L60 Line Phase Comparison System
5-107
5 SETTINGS
5.5 GROUPED ELEMENTS
5
5.5.3 PHASE COMPARISON ELEMENTS
a) MAIN MENU
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
PHASE COMPARISON ELEMENTS
b) 87PC SCHEME
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
Ö
PHASE COMPARISON ELEMENTS
Ö
87PC SCHEME
PHASE COMPARISON
ELEMENTS
87PC SCHEME
MESSAGE
ADVANCED
FAULT DETECTORS
MESSAGE
CHARGE CURRENT
COMPENSATION
MESSAGE
OPEN BREAKER
ECHO
87PC SCHEME
87PC FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
87PC SCHEME SELECT:
2TL-TR-SPC-2FC
Range: 2TL-TR-SPC-2FC, 2TL-BL-SPC-2FC,
2TL-TR-DPC-3FC, etc.
MESSAGE
87PC BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
87PC SIGNAL SOURCE:
One Source Current
Range: One Source Current, Two Sources Current
MESSAGE
87PC SIGNAL:
Mixed I_2-K*I_1
Range: Mixed I_2–K*I_1, 3I_0
MESSAGE
87PC MIXED SIGNAL K:
0.20
Range: 0.00 to 0.25 in steps of 0.01
MESSAGE
87PC MIXED SIGNAL
REF ANGLE: 0°
Range: 0 to 359° in steps of 1
MESSAGE
87PC FDL PICKUP:
0.50 pu
Range: 0.02 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDL AUX:
Off
Range: FlexLogic™ operand
MESSAGE
87PC FDH PICKUP:
0.75 pu
Range: 0.05 to 15.00 pu in steps of 0.01
MESSAGE
87PC FDH AUX:
Off
Range: FlexLogic™ operand
MESSAGE
87PC FDH SUPV:
Off
Range: FlexLogic™ operand
MESSAGE
87PC CH1 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH2 ASYMMETRY:
0.0 ms
Range: –5.0 to 5.0 ms in steps of 0.1
MESSAGE
87PC CH1 DELAY:
0.0 ms
Range: 0.0 to 30.0 ms in steps of 0.1
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...