GE Multilin
L60 Line Phase Comparison System
5-37
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.8 OSCILLOGRAPHY
a) MAIN MENU
PATH: SETTINGS
Ö
PRODUCT SETUP
ÖØ
OSCILLOGRAPHY
Oscillography records contain waveforms captured at the sampling rate as well as other relay data at the point of trigger.
Oscillography records are triggered by a programmable FlexLogic™ operand. Multiple oscillography records may be cap-
tured simultaneously.
The
NUMBER OF RECORDS
is selectable, but the number of cycles captured in a single record varies considerably based on
other factors such as sample rate and the number of operational modules. There is a fixed amount of data storage for oscil-
lography; the more data captured, the less the number of cycles captured per record. See the
ACTUAL VALUES
ÖØ
RECORDS
ÖØ
OSCILLOGRAPHY
menu to view the number of cycles captured per record. The following table provides sam-
ple configurations with corresponding cycles/record.
A new record may automatically overwrite an older record if
TRIGGER MODE
is set to “Automatic Overwrite”.
Set the
TRIGGER POSITION
to a percentage of the total buffer size (for example, 10%, 50%, 75%, etc.). A trigger position of
25% consists of 25% pre- and 75% post-trigger data. The
TRIGGER SOURCE
is always captured in oscillography and may be
any FlexLogic™ parameter (element state, contact input, virtual output, etc.). The relay sampling rate is 64 samples per
cycle.
The
AC INPUT WAVEFORMS
setting determines the sampling rate at which AC input signals (that is, current and voltage) are
stored. Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling
rate of the relay which is always 64 samples per cycle; that is, it has no effect on the fundamental calculations of the device.
OSCILLOGRAPHY
NUMBER OF RECORDS:
15
Range: 1 to 64 in steps of 1
MESSAGE
TRIGGER MODE:
Automatic Overwrite
Range: Automatic Overwrite, Protected
MESSAGE
TRIGGER POSITION:
50%
Range: 0 to 100% in steps of 1
MESSAGE
TRIGGER SOURCE:
Off
Range: FlexLogic™ operand
MESSAGE
AC INPUT WAVEFORMS:
16 samples/cycle
Range: Off; 8, 16, 32, 64 samples/cycle
MESSAGE
DIGITAL CHANNELS
MESSAGE
ANALOG CHANNELS
Table 5–2: OSCILLOGRAPHY CYCLES/RECORD EXAMPLE
RECORDS
CT/VTS
SAMPLE
RATE
DIGITALS
ANALOGS
CYCLES/
RECORD
1
1
8
0
0
1872.0
1
1
16
16
0
1685.0
8
1
16
16
0
276.0
8
1
16
16
4
219.5
8
2
16
16
4
93.5
8
2
16
64
16
93.5
8
2
32
64
16
57.6
8
2
64
64
16
32.3
32
2
64
64
16
9.5
Summary of Contents for UR series
Page 2: ......
Page 4: ......
Page 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Page 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Page 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Page 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Page 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Page 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Page 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Page 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Page 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...