Chapter 9. Communication
TransPort
®
PT900 User’s Manual
149
2A80 2A80
10880
RO
Ch2 Transit Time Up
RO (IEEE 32 bit)
2A82
10882
RO
Ch2 Transit Time Dn
RO (IEEE 32 bit)
2A84
10884
RO
Ch2 DeltaT
RO (IEEE 32 bit)
2A86
10886
RO
Ch2 Up Signal Quality
RO (IEEE 32 bit)
2A88
10888
RO
Ch2 Dn Signal Quality
RO (IEEE 32 bit)
2A8A
10890
RO
Ch2 Up Amp Disc
RO (IEEE 32 bit)
2A8C
10892
RO
Ch2 Dn Amp Disc
RO (IEEE 32 bit)
2A8E
10894
RO
Ch2 SNR on UP channel
RO (IEEE 32 bit)
2A90
10896
RO
Ch2 SNR on DOWN channel
RO (IEEE 32 bit)
2A92
10898
RO
Ch2 Time in buffer on Up channel
RO (IEEE 32 bit)
2A94
10900
RO
Ch2 Time in buffer on Dn channel
RO (IEEE 32 bit)
2A96
10902
RO
Ch2 Signal Gain Up
RO (IEEE 32 bit)
2A98
10904
RO
Ch2 Signal Gain Down
RO (IEEE 32 bit)
2A9A
10906
RO
Ch2 Partial Corrolatoin Ratio Up
RO (IEEE 32 bit)
2A9C
10908
RO
Ch2 Partial Corrolatoin Ratio Dn
RO (IEEE 32 bit)
2AC0 2AC0
10944
RO
Ch2 Sound Speed
RO (IEEE 32 bit)
2AC2
10946
RO
Ch2 Current Reynolds Number
RO (IEEE 32 bit)
2AC4
10948
RO
Ch2 Current Correction Factor
RO (IEEE 32 bit)
2AC6
10950
RO
Ch2 Path Length P
RO (IEEE 32 bit)
2AC8
10952
RO
Ch2 Axial Length L
RO (IEEE 32 bit)
2B00 2B00
11008
RO
Ch2 Up +- Peak
RO INT32
2B02
11010
RO
Ch2 Dn +- Peak
RO INT32
2B04
11012
RO
Ch2 dynamic threshold on UP channel
RO INT32
2B06
11014
RO
Ch2 dynamic threshold on DOWN channel
RO INT32
3000 3000
12288
User
eSupplyTempLow
RW (IEEE 32 bit)
3002
12290
User
eEnergyRRWRESV1
RW (IEEE 32 bit)
3004
12292
User
eReturnTempLow
RW (IEEE 32 bit)
3006
12294
User
eEnergyRRWRESV2
RW (IEEE 32 bit)
3008
12296
User
Analog Input 1 Base Value
RW (IEEE 32 bit)
300A
12298
User
Analog Input 1 Full Value
RW (IEEE 32 bit)
300C
12300
User
Analog Input 2 Base Value
RW (IEEE 32 bit)
300E
12302
User
Analog Input 2 Full Value
RW (IEEE 32 bit)
3010
12304
User
Analog Input 1 Zero Cali Value
RW (IEEE 32 bit)
3012
12306
User
Analog Input 1 Span Cali Value
RW (IEEE 32 bit)
3014
12308
User
Analog Input 2 Zero Cali Value
RW (IEEE 32 bit)
3016
12310
User
Analog Input 2 Span Cali Value
RW (IEEE 32 bit)
3100 3100
12544
User
eEnergyEnable
RW INT32
3102
12546
User
eEnergySystem
RW INT32
Table 17: Modbus Register Map (cont.)
Register
(in Hex)
Register
(in Dec.)
Access
Level
Description
RO/
RW
Format
Summary of Contents for TransPort PT900
Page 2: ......
Page 4: ...ii TransPort PT900 User s Manual no content intended for this page ...
Page 18: ...Chapter 1 Introduction 2 TransPort PT900 User s Manual no content intended for this page ...
Page 60: ...Chapter 2 Installation 44 TransPort PT900 User s Manual no content intended for this page ...
Page 106: ...Chapter 4 Programming 90 TransPort PT900 User s Manual no content intended for this page ...
Page 124: ...Chapter 6 Logging Data 108 TransPort PT900 User s Manual no content intended for this page ...
Page 172: ...Appendix A Specifications 156 TransPort PT900 User s Manual no content intended for this page ...
Page 189: ......