![GE Simon Security System Installation Instructions Manual Download Page 40](http://html1.mh-extra.com/html/ge/simon-security-system/simon-security-system_installation-instructions-manual_4158263040.webp)
Simon Security System
33
Delete—Option #—48—DONE.
Option 49: Arming LEDs Shutdown (Default = off)
Determines whether the panel LEDs (buttons) turn off 30 seconds after the last button
press (on), or remain on for the entire arming period (off).
¾
To turn on Arming LEDs Shutdown, press:
Add—Option #—49—DONE.
¾
To turn off Arming LEDs Shutdown, press:
Delete—Option #—49—DONE.
Option 50: RF Jam Detect (Default = off)
Determines whether the panel checks for and reports RF interference/jam to the central
station (on), or not (off).
If this option is on and the panel receives a constant 319.5 MHz signal, the panel
speaker announces “Option 50 detected” and reports the condition to the central station.
If this option is off, the panel does not detect an RF jam.
Note
For UL listed systems, RF
Jam Detect must be on.
¾
To turn on RF Jam Detect, press:
Add—Option #—50—DONE.
¾
To turn off RF Jam Detect, press:
Delete—Option #—50—DONE.
Option 51: 24 Hour Sensor Tamper (Default = off)
Determines whether the system (armed or disarmed) goes into and reports an alarm any-
time a sensor tamper switch is tripped (on), or only when the system is armed and a
tamper switch of an armed sensor is tripped (off).
¾
To turn on 24 Hour Tamper, press:
Add—Option #—51—DONE.
¾
To turn off 24 Hour Tamper, press:
Delete—Option #—51—DONE.
Option 52: Unvacated Premises (Default = off)
Note
This feature does not work
from a keychain touchpad.
Determines whether the system automatically arms down to level 2 (ARM Doors &
Windows) if the user arms the system to a higher level without leaving the premises
(on), or remains at the armed level chosen by the user (off).
Note
If Options 81 and 82 are pro-
grammed, the RF Thermo-
stat will change from Energy
Saving Mode to normal
operating mode when the
panel is armed to level 2.
If this option is turned on and the user arms to level 4 (ARM Doors & Windows, +
ARM Motion Sensors) but does not exit the premises within the Exit Delay time, the
panel automatically changes to arming level 2.
Note
Option 38: Auto Arm must
be on for this feature to
work.
¾
To turn on Unvacated Premises, press:
Add—Option #—52—DONE.
¾
To turn off Unvacated Premises, press:
Delete—Option #—52—DONE.
Option 53: Hardwire Siren Supervision (Default = off)
Determines whether the panel monitors hardwired sirens for open conditions (on), or
not (off).
Summary of Contents for Simon Security System
Page 66: ...Simon Security System 59...
Page 67: ...Simon Security System 60...