Simon Security System
12
Hardwire Exterior Siren without Supervision
With Option 53 turned off, connect the Hardwire Exterior Siren (13-046) to the panel
without a resistor as shown in Figure 6
Figure 6. Hardwire Exterior Siren without Supervision
Wiring Hardwire Contacts
Important !
Connect only normally
closed (N/C) reed switches
to HWIN1 and/or HWIN2.
Other types of hardwire
detectors should not be
used.
You can connect hardwire reed switches (normally closed loop only) to HWIN1 and/or
HWIN2, if either terminal is not being utilized for a hardwire siren.
Note
Do not install the resistor at
the panel terminals. This
does not provide supervision
of the wire.
The total resistance of the wire loop must not exceed 3 ohms. This allows you to use
up to 200 feet of 2-conductor, 22-gauge stranded wire.
Connect hardwire reed switches to the panel using a 47k resistor as shown in Figure 7.
The resistor must be connected at the last switch in the circuit.
Figure 7. Connecting Normally Closed Hardwire Reed Switches
Wiring a Phone Line to the Panel
You can connect a phone line to the panel for systems monitored by a central monitor-
ing station and/or systems that notify users by a digital pager or voice event notifica-
tion.
Basically, there are two methods for connecting the panel to a phone line; full line sei-
zure and no line seizure.
H W I N 2
H W I N 1
D C O U T
A C
A C
Black
Red
H W I N 2
H W I N 1
D C O U T
A C
A C
47k
Resistor