User Manual
SG Series 225 & 300 UL S2
4.4 RECTIFIERS PARALLELED ON THE SAME BATTERY
NOTE !
A parallel system with a
Common Battery
for two or more
Rectifiers
, requires a
particular installation and adequate setting of some parameters, (accessible only
through password), and can therefore only be done by a QUALIFIED ENGINEER from GE.
Usually each
Rectifier-Inverter Unit
runs with its own
Battery
.
In case of parallel units are running with a
Common Battery
(max. 4 UPS - see
Fig 4.4-1
), the sharing
circuit between individual
Rectifier
is integrated in the communication bus of the system in order to
assure an equal sharing of the
Rectifiers
output currents.
Fig. 4.4-1 Diagram RPA system with Rectifiers on Common Battery
1 –
2 –
3 –
4 –
5 –
6 –
7 –
8 –
Rectifier
Inverter
Automatic Bypass
Manual Bypass
Utility Power
Load Bus Bar
External Battery Fuse
Battery
Pay attention to the following recommendations:
•
The units delivered for this functioning mode needs a special parameters setting, so they must be
prepared in advance before the installation.
•
The installation must be performed only with the UPS system must be completely shut down.
•
The AC
Rectifiers
input power (5) must be the same, with clockwise phase rotation for each unit.
•
Each
Rectifier
must be set for the same floating DC voltage and the same
Battery
current limitation.
•
It is mandatory to install the fuses / MCCB (7) on each line connecting the
Rectifiers
to the common
Battery
for maintenance / safety reasons.
•
In case one must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCCB on the
Battery
line (7).
•
It is mandatory to connect an external NO free contact
“Battery Fuses”
to the UPS and to enable the
function by setting the parameter (see
Section 4.1
of the
“Installation Guide”)
.
•
If an emergency generator set supply the UPS, and the free contact
“Generator ON”
is connected to
the Customer interface, connect a separate NO free contact on each parallel unit.
•
The parameters enabling the
Battery test
, both manual and automatic, must be set in the same
mode on all the units having the
Rectifiers
on
Common Battery
.
•
Do not connect the temperature sensor for automatic
battery floating voltage
compensation.
•
Do not enable the function
Boost charge
(parameter 87).