RT430
RT430-TM-EN-5
19
2 open collector outputs for voltages up to 400 V, normal or reversed polarity, and singly
programmable output signal;
1 output in modulation amplitude for IRIG-B124 signal;
2 optical outputs with ST connector and multimode fiber;
1 event input with screw connector CMOS/Level TTL;
Synchronization fault contactor Relay (L
OCKED
);
Front indicators for monitoring synchronization from GPS antenna and equipment status;
19’’ Panel Installation;
AC or DC power sources with two sources for equipment redundancy external power possibility;
1.4
Available Models
RT430 is available in different versions, according to the features used in the two Ethernet network
interfaces and the level of the power supplies.
For information about the different models, go to the order code on datasheet of the equipment.
1.4.1
Network Ports
Each network interface can have the configuration shown in the table below:
TABLE 1: Possible configuration of Ethernet ports according to the enabled and blocked features.
ETHERNET PORT 1
ETHERNET PORT 2
MC¹ ONLY
MC¹ ONLY
MC
1
+ NTP/SNTP+ IEEE 1588 PTP
MC
1
+ NTP/SNTP+ IEEE 1588 PTP
MC
1
+ NTP/SNTP
MC
1
+ NTP/SNTP
------------------
MC
1
+ NTP/SNTP+PRP
1
Ethernet interface for monitoring and configuration.
The equipment comes from manufacturer with a key that enables the features requested by the client. To
check the enabled features, access
Chapter 5
. For instructions about key changes to enable new features,
access
Chapter 6
1.4.2
Power Supply