3. Temperature Differential—Stage
2—(RAK148D1 only) (1–9°F)
(1–5°C)—
Set the number of
degrees between when stage 1
turns on and stage 2 turns on.
Press the
or
button to set differential value.
Press the
SW6
button to advance to the next screen.
4. Minimum Cool Setpoint (60, 64,
66, 68, 70, 72, 74, 76°F) (15, 17, 19,
20, 21, 22, 23, 24°C)
Adjust to control the minimum Cool set temperature allowed.
Press the
or
button to select.
Press the
SW6
button to advance to the next screen.
5. Maximum Heat Setpoint (65, 70,
72, 74, 76, 78, 80, 85°F) (18, 21, 22,
23, 24, 26, 27, 29°C)
Adjust to control the maximum Heat set temperature allowed.
Press the
or
button to select.
Press the
SW6
button to advance to the next screen.
6. Room temperature offset (+9°F to
–9°F) (+5°C to –5°C)
Adjust to calibrate displayed room
temperature to match actual room temperature.
Press the
or
button to select.
Press the
SW6
button to advance to the next screen.
>
<
>
<
>
<
>
<
SET
ROOM
SET
9
SET
SET
ROOM