background image

              

 

 

Nuova Via di Piano Comprensorio Vulcano 

Sesto San Giovanni, MI 20099 Italy 

Tel. 02-24105.001 

 

IS 2653 GB

 

Page 

13

 of 

18

 

 

 

CAUTION:

  The  refilling  action  must  be  performed  by  qualified  operators.  Periodical  inspection  and 

maintenance of the gas filling station must be accurate to prevent damages to the valves and the equipment 
installed inside or to the connecting pipe to the bushing. 
 

CAUTION:

 Always use equipment certified for SF6 gas. This will avoid mistakes, safety issues and risk for the 

environment and the equipment. 

 

Gas density monitor 

 
The bushing is equipped with one or more gas density monitors. 
 
This  device  ensures  a  great  accuracy  in  the  measurement,  as  it  is  based  on  the  continuous  and  direct 
comparison  between  the  gas  density  inside  the  bushing  and  the  gas  density  of  a  built-in  reference  chamber 
filled with the same gas. 
This system is different and it is more accurate than the normal gas density monitors, which estimate the gas 
density by correcting the gas pressure measurement with the ambient temperature. 
 
The 

Figure 9

 shows an example of the instrument and its graduated scale. 

 

    

 

 

 

Figure 9 – Example of gas density monitor  

 
The indication on the scale is expressed in MPa absolute, referred to a gas temperature of 20°C. This means 
that  the  instrument  converts  the  gas  density  into  a  value  of  pressure  referred  to  20°C,  independently  for  the 
effective temperature of the gas. 
 
The instrument reading practically does not change with the gas temperature that is a function of the bushing 
loading  condition  and  ambient  temperature.  Changing  of  reading  during  the  bushing  normal  operation  is  an 
indication of gas leakages or malfunction of the instrument. 

 

NOTE:

 Due to the instrument principle of operation, the replacement of bushing gas from SF6 to a gas mixture 

SF6 N2 is not allowed without replacing the gas density monitors with the proper type. In this case contact GE 
Grid Solutions RPV for support, instructions and approval. 

 
Each gas monitoring device is equipped with four change-over micro switches for alarm and tripping signals. 
For further information regarding alarm pressure values, see the electrical scheme document. 
 
Each  gas  density  monitor  device  is  installed  on  a  DN 20 DILO Type valve for easy disassembly, without the 
need to completely empty the bushing from the gas. 
 
In addition, the electrical cables of all devices can be wired in a junction box provided with DIN type terminal 
boards for easy assembly and maintenance; see the electrical scheme document for details.

 

 

Summary of Contents for PWS

Page 1: ...any name udated 07 07 2016 AF LP 3 Storage and transport conditions updated 22 08 2016 AF LP IS 2653 GB GE Proprietary Information Class III Confidential Export Controlled U S Government approval is r...

Page 2: ...3 Storage conditions 6 4 Technical characteristics 6 5 Bushing preparation and installation 7 5 1 Controls at the arrival 7 5 2 Bushing unpacking 8 6 Gas SF6 characteristics and gas filling instructi...

Page 3: ...oltages above 1000V 2 Safety In this document important safety requirements are highlighted by the word CAUTION and important operative instructions are evidenced by the word NOTE This manual must be...

Page 4: ...ersonnel involved in wall bushing assembly All problems detected during the bushing installation must be reported to the Foreman and to GE Grid Solutions RPV Supervisor The bushing is a pressurized de...

Page 5: ...nt of the crate during the transport it is responsibility of the transport company to carefully fix it on the vehicle by suitable retain systems like ropes synthetic pulling bands or any other method...

Page 6: ...ed and tested in accordance with the IEC 62199 and IEC 60137 standard Each section is based on A composite insulator with silicone sheds The internal shielding arrangement An internal aluminium tube c...

Page 7: ...the arrival Before proceeding with the unpacking operation it is necessary to perform the following controls Check the wooden crate status Check the external visual impact recorder s Open the crate a...

Page 8: ...upports and it is locked by locking belts Additional intermediate belts support the composite insulator to a wooden structure Figure 4 Bushing crate inside view Figure 5 Bushing inside the crate top v...

Page 9: ...ow the steps indicated into the provided erection and installation manual IS 2654 GB Figure 7 Example of bushing extraction and lifting CAUTION The two composite insulators are protected by a PE plast...

Page 10: ...ium Supplier The minimum requirement is that the characteristics will be in accordance with the data listed in the GE RPV limits column The gas filling must be performed with an equipment that prevent...

Page 11: ...e up to 0 2 MPa abs 1 bar gauge Pressure must be directly measured on the gas density monitors installed on the bushing flange Check all the gas seals for leakages with a suitable SF6 leak meter devic...

Page 12: ...the DILO machine check that the machine set up is for gas filling and that the connecting pipe is full of SF6 In the case of direct filling from the bottle check that the bottle is effectively charged...

Page 13: ...ation on the scale is expressed in MPa absolute referred to a gas temperature of 20 C This means that the instrument converts the gas density into a value of pressure referred to 20 C independently fo...

Page 14: ...pair procedure is described into the component manual see reference in the summary prepared for the specific wall bushing The composite manufacturer can provide a repairing kit and also a technical su...

Page 15: ...the camera must be properly set in order to avoid false signals and background noise In addition an infrared scan on the line terminal and the incoming cables can reveal incipient hot spots phenomenon...

Page 16: ...Gas valves electrical equipment and connecting cables When plant is off Clean the cubicle Check for gas leaks Check functionality of pressure gauge and DILO Type valves Check terminal blocks wiring ca...

Page 17: ...ect the closure cap and the fixing screws CAUTION Do not remove the closure cap and do not touch the disk when the bushing is filled with gas An explosion of the disk could be very dangerous Gas densi...

Page 18: ...lectric terminals Copper silvered Dismount and recycle Toroids Aluminium Dismount and recycle Internal electrostatic shields Aluminium Dismount and recycle Transport supports Aluminium Recycle the alu...

Reviews: