background image

8

DEH40206 Installation Instructions

ALL ON/ALL OFF

To convert to All ON/All OFF
operation, DIP switch 1 is moved to
the OFF position (1 OFF, 2 ON). This
operation is typical in a prison
application: individual control of
each cell with a Master ON/OFF to

override a bank of switches quickly.

Master Button Alternate Scenarios

OFF/RESTORE — The Default Setting

The Master Button on the 2-, 4- and 8-button switch is pre-
configured to provide an OFF/Restore scenario. If several
individual switch buttons are ON, hitting the Master turns all
of those buttons OFF. Hitting the Master again would turn
those same switches back ON.

Example (Figure 8):

 Assume that in the previous office

example, an occupant prefers a lighting arrangement with the
fluorescents at 

1

3

 and the wallwash units on. Once the

buttons on the switch are set to this combination, all the
occupant needs to do from then on is to press the Master
Button to turn off or restore this lighting combination.

Another example:

 Assume an 8-button switch is used to

control eight zones in an open office space.  At the end of the
day, all but two zones have been turned off. Upon leaving, a
conscientious employee uses the Master Button to turn off
the remaining lighting, only to hear an exclamation from the
back corner… someone is still there. Pressing the Master
Button again would restore the lighting in the two zones
which had been on, without having to turn on the entire floor.

You can change the operating
scenario of the Master Button
using the first two DIP switches
located on the back of the
switch.The DIP switches are
normally covered by a label to
prevent accidental changes. As

shown above, the factory default setting is all DIP switches in
the ON position: each DIP switch is depressed towards the
numbers along the top, indicated here by the black dots.

To access the
Master Button DIP
switches, remove
the gray portion in
the upper right
corner of the label
on the back of the
dataline switch.

SPECIAL FUNCTIONS (CONTINUED)

OFF ONLY

To convert to Master OFF Only, DIP
switch 1 is ON, switch 2 is OFF.
This is an energy-efficient setting,
but not very occupant friendly. For
example, in our office application,
this would make the occupant reset

the desired lighting combination every morning. (Don’t use
this configuration with Pattern switches).

DISABLED

Both DIP switches OFF. This configuration may be preferred

when there is concern about
someone “accidentally” turning on
all of the lights on the floor.

DISABLED & OVERRIDE
Moving the fourth DIP switch to the

OFF position as shown, disables the switch but allows for a

five-minute override. When the DIP
switch is in the OFF position the
switch can be enabled for five
minutes by pressing the service
pin.

1

3

 Lighting plus wall wash

Master OFF

Master Restore

Figure 8

Summary of Contents for ProSys DEH40206

Page 1: ... period Dip switch 4 must be in the off position to enable this feature as shown on page 8 Order this feature by adding a K to the part number for the 1 2 4 and 8 button switch For example RS2PSxK Any button on a Softwire Switch may be softwired to Any relay or group of relays within a single relay panel A channel within a single relay panel The same channel among multiple panels requires an RCLK8...

Page 2: ...nch twist lay on pairs 6 inch twist lay on cable Plenum rated copolymer jacket 0 230 O D FEP 0 010 insulation 0 060 O D 30 pF foot maximum capacitance 20 C to 150 C operating temperature range 17 lbs per 500 foot reel UL rated If you have purchased the ProSys Lighting Control System the stand alone system the devices panels switches and clock will be in self install mode This means that as soon as...

Page 3: ...tween the red and black terminals on the last switch It should be less than 3 ohms If it is higher work backwards toward the relay panel checking the resistance at each switch to find the bad connection When finished reconnect the Local Dataline at the panel Shorted Dataline After the dataline resistance test checks out you can easily test for a shorted dataline by measuring the resistance from re...

Page 4: ... single panel see next page for softwiring a dataline switch For example assume that you want the top two buttons of a 4 button switch to control open office areas associated with relays in Panel 01 while the third button controls common areas rest rooms and hallways in Panel 02 The form below shows how to record this intent and also shows the labeling for each switch button Finally write the swit...

Page 5: ...t it provides a simple way of manually overriding all of the relays which are grouped to an automation channel A H within a panel With the wallplate removed and the switch s master button flipped open 1 Press the SOFTWIRE tab The LED next to the tab will turn on then the individual button LEDs will start flashing 2 Press the switch button you want to softwire Master Button on an RS1PS x The LED fo...

Page 6: ...t Lift the button out twisting it slightly if necessary to free the small hook holding the center edge of the button in place To replace the button position the small center hook in place and press the hinge pin into the hinge bracket until it snaps in place Remove Replace Screwless Wallplate To remove the screwless cover plate press in the black tab at the bottom edge of the plate and lift the pl...

Page 7: ...Figure 7 shows how the four buttons on a quad switch would be softwired to create this switching function All of the buttons are wired as Patterns Reviewing the LED operation shows why this is important see Figure 6 When the occupant toggles the top button ON relay 01 01 will turn ON and relay 01 02 will turn OFF to give 1 3 lighting The LED for 1 3 will turn on red Pressing the second button caus...

Page 8: ...here Pressing the Master Button again would restore the lighting in the two zones which had been on without having to turn on the entire floor You can change the operating scenario of the Master Button using the first two DIP switches located on the back of the switch The DIP switches are normally covered by a label to prevent accidental changes As shown above the factory default setting is all DI...

Page 9: ... button 1 controlling a Pattern in which the north half of the floor is ON and south half is OFF The second button does just the reverse With this combination whenever the cleaners turn on one half of the floor the other half turns off automatically saving half the lighting Furthermore since switch 01 01 has been configured as a cleaning switch the cleaning crew cannot accidentally put an occupant...

Page 10: ......

Reviews: