NX-591E 

V. 

ENROLLING THE MODULE 

The NetworX control panels have the ability to automatically find and store in memory the presence of 
all keypads, zone expanders, wireless receivers, and any other device on the keypad buss. This 
allows these devices to be supervised by the control panel.  To enroll the devices, enter the Program 
Mode of the NX control panel using the procedure outlined in the NX Installation Manual.  When the 
Program Mode is exited, the NX control will automatically enroll all the devices.  The enrolling process 
takes about 12 seconds, during which time the 

A

Service

@

 LED will illuminate. When using the LCD 

Keypad, the "Service Required" message will be displayed. User codes will not be accepted during 
the enrolling process.  Once a module is enrolled, if the control panel does not detect it, the 

A

Service

@

 

LED will illuminate. 
 
 

VI. 

WIRING THE MODULE 

 

MAXIMUM WIRE RUN 

LENGTH 

(IN FEET)

 

WIRE GAUGE 

(Connected To NX Control Panel or NX320E Power Supply)

 

10

 

20

 

50

 

18

 

100

 

16

 

 

 

VII.  TERMINAL DESCRIPTION 

 
 

TERMINAL

 

DESCRIPTION

 

POS 

Connect to the KP POS terminal of the panel.  Refer to “Specifications” in 
this manual for power consumption.  

COM 

Connect to the KP COM terminal of the panel. 

DATA 

Connect to the KP DATA terminal of the panel.  

TAMPER 

Normally closed 

 
 
 

Summary of Contents for NX-591E

Page 1: ...NetworX Series NX 591E Cellemetry Module Installation and Startup...

Page 2: ...TRUCTIONS 11 Location 0 Programming the Mode 11 Location 1 Feature Selection 11 Loc 2 7 When Phone Fault Is Detected 12 Location 2 Events To Report To Central Station 12 Location 3 Special Events To R...

Page 3: ...essages to be reported keeping airtime to a minimum The NX 591E has 14 LEDs to provide extensive diagnostic and setup information II ACTIVATION VIA WEBSITE The cellemetry unit can be activated and man...

Page 4: ...e that the insertion points have two sizes of holes a larger hole and a smaller hole Diagram 1 The black plastic PCB guides are grooved on one edge where the PC Board will be seated The end with the h...

Page 5: ...ss takes about 12 seconds during which time the AService LED will illuminate When using the LCD Keypad the Service Required message will be displayed User codes will not be accepted during the enrolli...

Page 6: ...et to tower Flashing Waiting for acknowledgement DS6 ON Sending data message to tower Flashing Waiting for acknowledgement XMIT Message packet being transmitted to tower POOR FAIR GOOD BEST The LEDs w...

Page 7: ...NX 591E 7 IX CONNECTION DIAGRAM...

Page 8: ...d 3 Factory Defaulting the Module The keypad will beep 3 times indicating that the loading is in progress Remember you will erase any values you may have entered previously 4 Programming a Location On...

Page 9: ...ish The Armed LED will illuminate waiting for a new programming location to be entered To Review The Data location The Armed LED will flash If the location number is valid the Armed LED will extinguis...

Page 10: ...nce the data is programmed press r to enter the data and advance to the next segment of that location After the last segment of a location is programmed pressing r will exit that location turn the Rea...

Page 11: ...isable Cellular Service LEDs Disabled Enabled 7 Enable Tamper Switch Enabled Disabled 8 Disable SIA DCS Area Modifier Disabled Enabled Segment 2 programs for Host Acknowledgement requirements Factory...

Page 12: ...GMENT DESCRIPTION 1 Alarms 9 Tampers 2 Open Close 10 Short Circuit Ground Fault 3 Bypass 11 Sensor Lost 4 Zone Trouble 12 Sensor Low Battery 5 Power Trouble AC Failure or Low Battery 13 Expander Troub...

Page 13: ...pecial Events To Report To Email Phone fault detected 8 segments of Feature Selection Data This location selects the partition s to include when reporting Special Events to email To exclude any partit...

Page 14: ...pecial Events To Report To Pager Phone fault detected 8 segments of Feature Selection Data This location selects the partition s to include when reporting Special Events to a pager To exclude any part...

Page 15: ...ecial Events To Report To Central Station Phone line is good 8 segments of Feature Selection Data This location selects the partition s to include when reporting Special Events to the Central Station...

Page 16: ...rtitions OFF SEGMENT DESCRIPTION 1 Alarm Restores 2 Telephone Fault 3 Start Download 4 Fail to Communicate Data Lost 5 8 Reserved Location 12 Events To Report To Pager Phone line is good 16 segments o...

Page 17: ...ne is good To exclude any partition from reporting simply turn off the LED corresponding to that particular partition Using Table XI 1 on page 12 enter the corresponding number of the partition s to i...

Page 18: ...ifier OFF 2 HOST ACKNOWLEGEMENT REQUIRED 1 Host Ack for Central Station messages OFF 2 Host Ack for email messages OFF 3 Host Ack for pager messages OFF 4 Host Ack for periodic test signals OFF 5 8 Re...

Page 19: ...5 6 7 8 1 Alarms 2 Open Close 3 Bypass 4 Zone Trouble 5 Power Trouble AC Fail or Low Battery 6 Siren Telephone Fault 7 Test Reports 8 Program Download Log Full 9 Tampers 10 Short Circuit Ground Fault...

Page 20: ...e Activity Monitor 16 Reserved 7 14 REPORTING SPECIAL EVENTS TO PAGER Phone line fault detected 1 2 3 4 5 6 7 8 1 Alarm Restores 2 Telephone Fault 3 Start Download 4 Fail to Communicate Data Lost 5 8...

Page 21: ...6 7 8 1 Alarms 2 Open Close 3 Bypass 4 Zone Trouble 5 Power Trouble AC Fail or Low Battery 6 Siren Telephone Fault 7 Test Reports 8 Program Download Log Full 9 Tampers 10 Short Circuit Ground Fault 11...

Page 22: ...6 Siren Telephone Fault 7 Test Reports 8 Program Download Log Full 9 Tampers 10 Short Circuit Ground Fault 11 Sensor Lost 12 Sensor Low Battery 13 Expander Trouble 14 Fail to Communicate 15 Zone Activ...

Page 23: ...ne LED Horizontal Keypad NX 8E KIT NX 8E Control NX 108E Keypad 40VA Transformer NX 148E Alphanumeric LCD Keypad NX 8E KIT 8 NX 8E Control NX 1448E Keypad 40VA Transformer NX 1308E 8 Zone LED Door Des...

Page 24: ...EDs enabled 90mA Max Transmission Burst 1 second 1300mA Max OPERATING TEMPERATURE 32 to 120 degrees F DIMENSIONS 2 40 Wide 4 40 High 1 20 Deep SHIPPING WEIGHT 1 lb Main Phone 800 727 2339 Technical Su...