Programming zone configuration groups
LOCATIONS 110-169 ARE USED TO CHANGE THE ZONE CONFIGURATIONS AS LISTED IN THE
TABLE ON PAGES 44-46. THESE LOCATIONS ARE CONSIDERED AS ADVANCED
PROGRAMMING, AND THEY SHOULD ONLY BE CHANGED IF YOU HAVE A THOROUGH
UNDERSTANDING OF THE OPERATION OF EACH BIT.
LOCATION 110 - CONFIGURATION GROUP 1 ALARM EVENT CODE (1 segment, numerical data)
Location 110 contains the event code that is sent for a Contact ID or SIA report. The desired
event code should be chosen from the list on pages 121-122. The zone ID will be the zone that
is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also
contain the alarm report code for the Robofon format (value 00-99).
LOCATION 111 - CONFIGURATION GROUP 1 CHARACTERISTIC SELECT (5 segments, feature selection data)
Segment 1
1 =
Fire
(turn on if this is a fire zone)
2
=
24 hour
(turn on for non-fire 24 hour zones)
3
=
Keyswitch
zone (normally open switch)
4
=
Follower
(turn on for burglary zones that are Instant during non-entry
times)
5
=
Delay 1
zone (follows timer 1 Entry and Exit times)
6
=
Delay 2
zone (follows timer 2 Entry and Exit times)
7
=
Interior
(turn on if this zone should Automatically Bypass or Bypass
for Stay Arming)
8
=
Local only
(turn on if this zone should not be reported)
Remark: for a maintained keyswitch (ON/OFF), program both
“keyswitch” and “local”
Segment 2
1 = On: if configuration group will
beep the keypad
for alarm
2
=
On: if configuration group will sound the
yelping siren
for alarm
3
=
On: if configuration group will sound the
steady siren
for alarm
4
=
On: if configuration group will
chime
5
=
On: if configuration group can be
bypassed
6
=
On: if configuration group is included in the
group shunt
7
=
On: if configuration group is
force armable
8
=
On: if configuration group is
entry guard
Segment 3
1 = On: enables
Fast Loop
Response. (50mS) - Off= 500mS
2
=
On: enables Double
End Of Line Tamper
zone. (Mainly used for
tamper on wireless zones)
3
=
On: enables
Trouble Reporting
zone. (Day zone and Fire zones)
4
=
On: if configuration group is a
Cross Zone
5
=
On: enables
Dialler Delay
zone. (See location 40)
6
=
On: if configuration group will use
swinger shutdown
. (See location
38)
7
=
On: enables
Restore reporting
8
=
On: enables
Listen-In
. (See location 40)
NX-4-EUR Installation manual
Page 63
02/07/06
Summary of Contents for NX-4-EUR
Page 2: ...NX 4 EUR Installation manual Page 2 02 07 06 ...
Page 92: ...CE DECLARATION NX 4 EUR Installation manual Page 92 02 07 06 ...
Page 93: ...NX 4 EUR Installation manual Page 93 02 07 06 ...
Page 94: ...NX 4 EUR Installation manual Page 94 02 07 06 ...
Page 95: ...NX 4 EUR Installation manual Page 95 02 07 06 ...
Page 96: ...NX 4 EUR Installation manual Page 96 02 07 06 ...
Page 97: ...NX 4 EUR Installation manual Page 97 02 07 06 ...
Page 98: ...NX 4 EUR Installation manual Page 98 02 07 06 ...
Page 99: ...NX 4 EUR Installation manual Page 99 02 07 06 ...