CLC/TS 50131-3 Compliancy
In order to be compliant with the technical specification CLC/TS 50131-3 (Alarm systems – Control and
indicating equipment), the following guidelines must be taken into account :
•
Zone configuration types reporting a Hold-up alarm (event code 0) should :
-
not be bypassable
-
not have swinger shutdown enabled
•
All zone configuration types should be set for
-
double-end-of-line configuration - 2EOL (as of loc 111 segment 3 option 2)
-
fast loop response (as of loc 111 segment 3 option 1)
-
swinger shutdown(*) enabled (as of loc 111 segment 3 option 6)
•
Entry/exit zone configuration types and Follower zone configuration types should be set for Force Arming
(as of loc 111 segment 2 option) in order to fulfil paragraph 12.6.6 of the technical specifications
•
The use of instant zones (zone configuration type 6) is not allowed in order to fulfil paragraph 8.2.4.3 of the
technical specifications
•
The entry time should not be more than 45 seconds (location 24)
•
The following options need to be enabled :
-
keypad sounder for battery trouble (location 39 option 4)
-
keypad sounder for expander trouble (location 39 option 8)
-
first alarm logic (location 37 segment 6 option 4)
-
log protection mode (location 37 segment 6 option 5)
-
6 digit user codes (location 41 option 1)
-
keypad shutdown mode (location 41 option 5)
•
A warning device(**) should be protected by a tamper loop
•
Programmable outputs that are used for warning devices must operate for a minimum of 90 seconds and
a maximum of 15 minutes unless other requirements are demanded by local or national regulations.
(*)swinger shutdown counter (loc 38) should be set with a maximum value of 3.
(**)The BELL output should not be used to connect an internal warning device
Remarks :
All reportable events that are set will be processed. In the event of multiple events being
present simultaneously, all these events will be processed and notified.
The NX-4 provides one or more outputs to fulfill the requirements described in Table 9 of
the CLC/TS 50131-3. All options of Table 13 of the CLC/TS 50131-3 can be fulfilled.
The level of tamper protection fulfils the requirements for installations inside the
supervised premises
Indicators that share common means of annunciation will not apply any priorisation.
Maximum load taken from the AUX OUT should not exceed the values as stated in the
table below (EN-50131-6:1997 and EN50131-1:1997 table 16)
battery
NX-4
NX-6
NX-8
Max current consumpt
.
77mA
96mA
105mA
Max current AUX OUT
7.2Ah
480mA
460mA
450mA
Max current AUX OUT
18Ah
570mA
560mA
550mA
NX-4-EUR Installation manual
Page 34
02/07/06
Summary of Contents for NX-4-EUR
Page 2: ...NX 4 EUR Installation manual Page 2 02 07 06 ...
Page 92: ...CE DECLARATION NX 4 EUR Installation manual Page 92 02 07 06 ...
Page 93: ...NX 4 EUR Installation manual Page 93 02 07 06 ...
Page 94: ...NX 4 EUR Installation manual Page 94 02 07 06 ...
Page 95: ...NX 4 EUR Installation manual Page 95 02 07 06 ...
Page 96: ...NX 4 EUR Installation manual Page 96 02 07 06 ...
Page 97: ...NX 4 EUR Installation manual Page 97 02 07 06 ...
Page 98: ...NX 4 EUR Installation manual Page 98 02 07 06 ...
Page 99: ...NX 4 EUR Installation manual Page 99 02 07 06 ...