When installing an NX-6V2 in compliance with Underwriters 
Laboratories, the following instructions must be observed:

• Initiating and indicating devices must be rated at 11.5 to 

12.4 VDC residential, 12.0 VDC commercial.

• Force arming and auto arming must not be enabled.
• For residential fire applications, the indicating devices 

shall be a Wheelock 34T-12 or equivalent.

• The

 

listen in feature shall not be enabled.

• The siren/bell test must be enabled. The auxiliary 

outputs controlling the audible device require a 
minimum cutoff time of 15 minutes for commercial 
burglary, four minutes for residential applications, or 30 
minutes for commercial burglary for Canada.

• For residential fire installations, the dynamic battery test 

time cannot exceed four hours.

• Ringback must be enabled on UL commercial burglary 

installations.

• On commercial burglary installations, the fire initiating 

circuits must not be connected.

• The entry guard feature must be disabled.
• Group bypassing must be disabled.
• Delay before dial seizure must be set to 

0

• Total current draw from auxiliary power connections at 

terminal positions POS, AUX PWR, and SMOKE PWR must 
not exceed 400 mA.

• Remote downloading must not be used on UL listed 

systems.

• For residential burglary applications, the maximum entry 

and exit delay times are 45 and 60 seconds respectively. 
The exit delay time must not exceed 60 seconds for 
commercial burglar alarm applications.

• The keyswitch option must not be used.
• The telephone line monitor must be enabled.
• The telephone line cut delay must not exceed 90 

seconds.

• The 24-hour communicator test transmission is required.
• For 24-hours of standby power using a 7.0 Ah battery, 

limit auxiliary power load to 140 mA.

• For 24-hours of standby power using a 17.2 Ah battery, 

limit auxiliary power load to 400 mA.

• The silent keypad option must not be enabled.
• UL has only verified compatibility with the following 

listed DACRs and formats: Sure-Gard SG-MLR2-DG: 
2,9,10,12,13,14; Silent Knight 9000 - 2,12; FBI - CP220FBI, 
13; and Ademco 685: 2,11,12, and 13.

• For burglary installations, cross zoned detectors must 

overlap 100 percent in the area of coverage, and similar 
coverage areas must be used. For example, interior 
protection is cross zoned with interior protection, and so 
on.

• Expander trouble must activate the siren.
• For UL 1637, expander trouble must activate the keypad 

sounder.

• If  the

 

late to close/early to open feature is enabled, the 

opening and closing reports must be enabled. 

• For Canadian installations, the class II transformer 

secure tab must not be employed.

• The four-wire smoke detector employed must be rated 

to operate over the voltage range of 11.5 to 12.4 V.

• Compatible listed devices: (special applications):

• Bell output (sirens): Wheelock models: NS-1215W, 

NS-121575W, NS4-1215W, NS4-121575W, AS-
1215W, AS-121575W

• Horn/strobe system sensor: S1224MC strobe series; 

1224MC Horn/strobe series; H12/24 Horn series

• Smoke output (four-wire detectors): ESL: 500N 

series; 449CTE series; 521 series; 541 series

• System sensor models: 2112/24R; 2112/24TR; 2112/

24AT; 2112/ATR; 2112/24AITR; 4WTA-B; 4WTR-B; 
4WTAR-B; 4WITAR-B

• Detection systems: F220-B6C; D273 series; Hochiki: 

SBC-4/12, 4/12W

Additional UL 609 installation requirements

The alarm housing for a mercantile alarm system without a 
remote alarm transmission connection shall be mounted on 
the outside of the building, visible from a public street or 
highway. It shall be accessible for examination and repair. It 
shall also be located not more than four stories above the 
street level unless:
a) A second alarm sounding device and housing, intended for 
outside service is mounted adjacent to the premises or area 
of the building in which the alarm system is installed or
b) A second alarm sounding device, intended for inside 
service is mounted within the premises.
In either case, the outside alarm sounding device and 
housing may be mounted as high as the seventh floor.

Additional UL 365 installation requirements

In a mercantile burglar alarm system, a mercantile alarm 
sounding device located within a building, but outside the 
protected area, is acceptable, provided it is rated for outside 
service and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency 
having jurisdiction over the protected property or 
b) A central station or residential monitoring station 
complying with the Standard for Central-Station Alarm 
Services, UL 827.
In a mercantile burglar alarm system, an alarm sounding 
device located within the area of greatest protection, or 
outside the area of greatest protection but within an area 
protected by an alarm system and that shares a common 
control unit with the system installed in the area of greatest 
protection, is acceptable provided it is rated for inside service 
and alarm conditions are transmitted to:
a) The dispatch location of the law enforcement agency 
having jurisdiction over the protected property or
b)  A central station or residential monitoring station 
complying with the Standard for Central-Station Alarm 
Services, UL 827. An inside sounding device shall be mounted 
at least 10 feet (3.05 m) above the floor or at the surfce of the 
ceiling. When there is fixed construction within the area that 
could provide access for an intruder, the alarm sounding 
device shall also be mounted at least 4 feet (1.2 m), as 
measured horizontally, away from the edges of the fixed 
construction or at least 10 feet (3.05 m) above it so as to mini-
mize access by an intruder.

Summary of Contents for NetworX NX-6V2

Page 1: ...resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a smal...

Page 2: ...revious location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the prog...

Page 3: ...numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which form...

Page 4: ...eless sensor missing and restore 4 Wireless sensor low battery and restore 5 Expander trouble and restore 6 Fail to communicate 7 Zone activity monitor 8 Reserved Location 18 Custom communicator forma...

Page 5: ...d no entry or exit delay is being timed It is delayed during entry and exit delay times This zone automatically bypasses if enabled in segment 1 This zone type is used to enable the tamper on a wirele...

Page 6: ...operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 121575W NS4 1215W NS4 121575W AS 1215W AS 121575W Horn s...

Page 7: ...e only with a Panasonic LC12V4BP or Yuasa NP4 12 battery There is a risk of explosion if the battery is replaced with an incorrect type WARNING If separate power supplies are necessary to accommodate...

Page 8: ...are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3...

Reviews: