background image

NX-6V2-Control Panel

Installation Instructions

4

Location 3 - Phone 1 dial attempts/backup control

Location 3 has two segments of numerical data.

Segment 1 - Phone 1 dial attempts

Program the number of dial attempts (1 to 15) the communi-
cator makes to phone 1 before ending the notification 
process. The default is 

8

, which means that the communi-

cator makes eight attempts to the first number.

Segment 2 - Phone 1 backup control

Program the backup control for phone 1. The default is 

0

.

• Program a 

0

 in segment 2 to cause the NX-6V2 to make 

the designated number of attempts to phone 2 before 
setting the fail to communicate condition to stop 
reporting. 

• Program a 

1

 in segment 2 to cause the NX-6V2 to stop 

trying to communicate after the designated number of 
attempts have been made to phone 1.

• Program a 

2

 in segment 2 to cause the NX-6V2 to make 

the dial attempts in increments of two. The first two 
attempts are made to phone 1, the next two attempts to 
phone 2. This repeats until the total number of attempts 
designated in segment 1 is completed.

Location 4 - Phone 1 events reported

Location 4 has two segments of feature selection data. Use 
this location to select those events reported to phone 1. 

• If you do not want dual or split reporting, use Location 4 

to select all events to phone 1.

• If you want dual or split reporting and the split is based on 

the event type (alarm, open/close, etc.), use Location 4 to 
select only those events that are reported to phone 1.

• If you don’t want events reported to phone 1, program 

0

 

in Location 4 (disabling all options).

Segment 1

1. Alarms and alarm restores.
2. Opening and closings.
3. Zone bypass and bypass restores.
4. Zone trouble and trouble restores.
5. Power fail, low battery, power restore, and low battery 
restore.
6. Bell cut, telephone line cut, bell cut restore, telephone 
line restore.
7. Test reports.
8. Start and end programming, download complete.

Segment 2 

1. Zone and box tamper and tamper restore.
2. Auxiliary power overcurrent, ground fault, and restore 
for both.
3. Wireless sensor missing and restore.
4. Wireless sensor low battery and restore.

5. Expander trouble and restore.
6. Fail to communicate.
7. Zone activity monitor.
8. Reserved

Location 18 - Custom communicator format

Location 18 has four segments of feature selection data. Use 
this location to program the communicator format used to 
transmit to the receiver connected to phone 3. Refer to your 
central station receiver documentation to determine which 
format is compatible. Select a format from 

Table  

on page 3. If 

you need a format other than those listed, review the over-
ride options described in this location to build the appropriate 
format.

Segment 1

1. On for 1800 Hz transmit; off for 1900 Hz.
2. On for 2300 Hz handshake; off for 1400 Hz.
3. On for cksum parity; off for double round parity.
4. On for two-digit event code; off for one-digit event 
code.
5. Reserved.
6. Reserved.
7. On for 20 pps; off for 10 or 40 pps.
8. On for 10 pps; off for 20 or 40 pps.

Segment 2

1. On for pager format (no handshake required).
2. On for 1400/2300 handshake.
3. Reserved.
4. Reserved.
5. On for contact ID.
6. On for SIA.
7. On for contact ID or 4+3.
8. On for DTMF.

Segments 3 and 4 - Reserved

Location 25 - Zones 1 to 8 zone type

Location 25 has eight segments of numerical data. Use this 
location to program the zone type for zones 1 to 8. Use 
segment 1 for zone 1, segment 2 for zone 2, etc. The segment 
defaults are 

3

5

6

6

6

6

6

6

Zones are programmed to be one of thirty different types. Use 
zone types 17 through 20 for wireless, or for hardwired zones 
using European double EOL configuration

Table 5

 describes the zone types. 

21

3/1 or 4/1 fast with parity

Same as 10, but sends the alarm event 

code rather than the zone number

22

SIA

SIA with area modifiers

a.

Pulses per second.

Table 4.

Communicator formats (continued)

Data

Format

Description

Table 5.

Zone types

Zone type 

Description 

1. Day zone

This zone is instant when the system is armed; 

trouble zone when the system is disarmed.

2. 24-hour audible.

This zone creates an instant yelping siren 

alarm regardless of the armed state of the 

control panel.

3. Entry/exit delay 1

A trip starts entry delay 1. The lack of a trip 

during exit delay enables the automatic 

bypass or instant mode if programmed.

Summary of Contents for NetworX NX-6V2

Page 1: ...resistor may be required across the bell terminals when a 12 VDC siren is used If no resistor is used you may experience voltage leakage into the siren which will cause these devices to output a smal...

Page 2: ...revious location Press the Medical key for the same location 5 To review the data in a specific location repeat the above procedure pressing but with no numeric data entry Each time you press the prog...

Page 3: ...numerical data Use this loca tion to program the communicator format used to transmit to the receiver connected to phone 1 Refer to your central station receiver documentation to determine which form...

Page 4: ...eless sensor missing and restore 4 Wireless sensor low battery and restore 5 Expander trouble and restore 6 Fail to communicate 7 Zone activity monitor 8 Reserved Location 18 Custom communicator forma...

Page 5: ...d no entry or exit delay is being timed It is delayed during entry and exit delay times This zone automatically bypasses if enabled in segment 1 This zone type is used to enable the tamper on a wirele...

Page 6: ...operate over the voltage range of 11 5 to 12 4 V Compatible listed devices special applications Bell output sirens Wheelock models NS 1215W NS 121575W NS4 1215W NS4 121575W AS 1215W AS 121575W Horn s...

Page 7: ...e only with a Panasonic LC12V4BP or Yuasa NP4 12 battery There is a risk of explosion if the battery is replaced with an incorrect type WARNING If separate power supplies are necessary to accommodate...

Page 8: ...are always enabled Enabled disabled for remote arming Entry delays b b Combined abort window time and entry delay must not exceed one minute Entry 1 delay 24 1 30 30 to 240 seconds Entry 2 delay 24 3...

Reviews: