B-18
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
409A
DNP Channel 1 Port
0 to 4
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 4
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409D
Reserved
0 to 1
---
1
F001
0
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
1 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
1 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
1 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
1 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP unsolicited responses maximum retries
1 to 255
---
1
F001
10
40AC
DNP unsolicited responses destination address
0 to 65519
---
1
F001
1
40AD
Ethernet operation mode
0 to 1
---
1
F192
0 (Half-Duplex)
40AE
DNP current scale factor
0 to 8
---
1
F194
2 (1)
40AF
DNP voltage scale factor
0 to 8
---
1
F194
2 (1)
40B0
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B1
DNP energy scale factor
0 to 8
---
1
F194
2 (1)
40B2
DNP power scale factor
0 to 8
---
1
F194
2 (1)
40B3
DNP other scale factor
0 to 8
---
1
F194
2 (1)
40B4
DNP current default deadband
0 to 65535
---
1
F001
30000
40B6
DNP voltage default deadband
0 to 65535
---
1
F001
30000
40B8
DNP power default deadband
0 to 65535
---
1
F001
30000
40BA
DNP energy default deadband
0 to 65535
---
1
F001
30000
40BE
DNP other default deadband
0 to 65535
---
1
F001
30000
40C0
DNP IIN time synchronization bit period
1 to 10080
min
1
F001
1440
40C1
DNP message fragment size
30 to 2048
---
1
F001
240
40C2
DNP client address 3
0 to 4294967295
---
1
F003
0
40C4
DNP client address 4
0 to 4294967295
---
1
F003
0
40C6
DNP client address 5
0 to 4294967295
---
1
F003
0
40C8
DNP number of paired binary output control points
0 to 16
---
1
F001
0
40C9
DNP TCP connection timeout
0 to 16
---
1
F001
0
40CA
Reserved (22 items)
0 to 1
---
1
F001
0
40E0
TCP port number for the IEC 60870-5-104 protocol
1 to 65535
---
1
F001
2404
40E1
IEC 60870-5-104 protocol function
0 to 1
---
1
F102
0 (Disabled)
40E2
IEC 60870-5-104 protocol common address of ASDU
0 to 65535
---
1
F001
0
40E3
IEC 60870-5-104 protocol cyclic data transmit period
1 to 65535
s
1
F001
60
40E4
IEC 60870-5-104 current default threshold
0 to 65535
---
1
F001
30000
40E6
IEC 60870-5-104 voltage default threshold
0 to 65535
---
1
F001
30000
40E8
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EA
IEC 60870-5-104 energy default threshold
0 to 65535
---
1
F001
30000
40EC
IEC 60870-5-104 power default threshold
0 to 65535
---
1
F001
30000
40EE
IEC 60870-5-104 other default threshold
0 to 65535
---
1
F001
30000
40F0
IEC 60870-5-104 client address (5 items)
0 to 4294967295
---
1
F003
0
40FD
Reserved (60 items)
0 to 1
---
1
F001
0
4140
DNP object 1 default variation
1 to 2
---
1
F001
2
4141
DNP object 2 default variation
1 to 3
---
1
F001
2
4142
DNP object 20 default variation
0 to 3
---
1
F523
0 (1)
4143
DNP object 21 default variation
0 to 3
---
1
F524
0 (1)
4144
DNP object 22 default variation
0 to 3
---
1
F523
0 (1)
4145
DNP object 23 default variation
0 to 3
---
1
F523
0 (1)
4146
DNP object 30 default variation
1 to 5
---
1
F001
1
Table B–9: MODBUS MEMORY MAP (Sheet 11 of 54)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT