5-110
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
5.4 FLEXLOGIC™
5 SETTINGS
5
5.4.9 FLEXMATH
a) SUMMATOR
PATH: SETTINGS
ÖØ
FLEXLOGIC
ÖØ
FLEXMATH
Ö
SUMMATOR
Ö
SUMMATOR 1(6)
Six identical summators are available in each N60 device.
Each summator has six inputs and a scaling factor is provided for each input. The scaling factors can be set to +1 and –1
allowing straight addition and subtraction of the inputs. A FlexLogic™ operand provided for each input can dynamically
include/exclude the input from calculations.
SUMMATOR 1
SUMMATOR 1 FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
SUMMATOR 1 INPUT
MODE: Signed
Range: Signed, Absolute
MESSAGE
SUMMATOR 1 HOLD:
Off
Range: FlexLogic™ operand
MESSAGE
SUMMATOR 1 PICKUP:
1000.000
Range: –2000000.000 to 2000000.000 in steps of 0.001
MESSAGE
SUMMATOR 1
HYSTERESIS: 3.0%
Range: 0.1 to 50.0% in steps of 0.1
MESSAGE
SUMMATOR 1 UNITS:
Range: 4 alphanumeric characters
MESSAGE
SUMMATOR 1 PU BASE:
1
Range: 1 to 2000000 in steps of 1
MESSAGE
SUMMATOR 1 INPUT1:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
MESSAGE
SUMMATOR 1 INPUT2:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
↓
MESSAGE
SUMMATOR 1 INPUT6:
Off
Range: Off, any FlexAnalog parameter.
See Appendix A for complete list.
MESSAGE
SUMMATOR 1 SCALE1:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
MESSAGE
SUMMATOR 1 SCALE2:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
↓
MESSAGE
SUMMATOR 1 SCALE6:
1.000000
Range: –2000.000000 to 2000.000000 in steps of
0.000001
MESSAGE
SUMMATOR 1 POS1:
Off
Range: FlexLogic™ operand
MESSAGE
SUMMATOR 1 POS2:
Off
Range: FlexLogic™ operand
↓
MESSAGE
SUMMATOR 1 POS6:
Off
Range: FlexLogic™ operand
MESSAGE
SUMMATOR 1 EVENTS:
Disabled
Range: Disabled, Enabled