GE Multilin
N60 Network Stability and Synchrophasor Measurement System
5-127
5 SETTINGS
5.5 GROUPED ELEMENTS
5
5.5.6 SUPERVISING ELEMENTS
a) OPEN POLE DETECTOR
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
ÖØ
SETTING GROUP 1(6)
ÖØ
SUPERVISING ELEMENTS
ÖØ
OPEN POLE DETECTOR
The open pole detector is designed to detect if any pole of the associated circuit breaker is opened or the conductor is bro-
ken on the protected power line and cable. The output FlexLogic™ operands can be used in three-pole and single-pole trip-
ping schemes, in reclosing schemes, in blocking some elements (like CT failure), and in signaling or indication schemes. In
single-pole tripping schemes, if
OPEN POLE
flag is set, any other subsequent fault should cause a three-phase trip regard-
less of fault type.
The open pole detector logic is built on detecting absence of current in one phase during presence of current in other
phases. Phases A, B and C breaker auxiliary contacts (if available) are used in addition to make a logic decision for single-
pole tripping applications. If voltage input is available, a low voltage function is used to detect absence of the monitoring
voltage in the associated pole of the breaker.
•
OPEN POLE FUNCTION
: This setting is used to enable/disable operation of the element.
•
OPEN POLE BLOCK
: This setting is used to select a FlexLogic™ operand that blocks operation of the element.
•
OPEN POLE CURRENT SOURCE
: This setting is used to select the source for the current for the element.
•
OPEN POLE CURRENT PICKUP
: This setting is used to select the pickup value of the phase current. The pickup set-
ting is the minimum of the range and likely to be somewhat above of the charging current of the line.
OPEN POLE DETECTOR
OPEN POLE FUNCTION:
Disabled
Range: Disabled, Enabled
MESSAGE
OPEN POLE BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
OPEN POLE CURRENT
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
OPEN POLE CURRENT
PKP: 0.20
pu
Range: 0.05 to 20.00 pu in steps of 0.01
MESSAGE
OPEN POLE BROKEN
CONDUCTOR: Disabled
Range: Disabled, Enabled
MESSAGE
OPEN POLE VOLTAGE
INPUT: Disabled
Range: Disabled, Enabled
MESSAGE
OPEN POLE VOLTAGE
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
OPEN POLE
φ
A AUX CO:
Off
Range: FlexLogic™ operand
MESSAGE
OPEN POLE
φ
B AUX CO:
Off
Range: FlexLogic™ operand
MESSAGE
OPEN POLE
φ
C AUX CO:
Off
Range: FlexLogic™ operand
MESSAGE
OPEN POLE PICKUP
DELAY: 0.060
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
OPEN POLE RESET
DELAY: 0.100
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
OPEN POLE TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
OPEN POLE EVENTS:
Disabled
Range: Disabled, Enabled