24
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
12D1
Asserted Digital Input State
0 to 1
1
–
F131
0
12D2
Input Name
0 to 12
1
–
F22
_
12D8
Block Input From Online
0 to 5000
1
s
F1
0
12D9
General Input G Control
0 to 1
1
–
F105
0
12DA
Pulsed Control Relay Dwell Time
0 to 250
1
s
F2
0
12DB
Assign Control Relays (1-5)
0 to 4
1
–
F50
0
12DC
General Input G Control Events
0 to 1
1
–
F105
0
12DD
General Input G Alarm
0 to 2
1
–
F115
0
12DE
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
12DF
General Input G Alarm Delay
1 to 50000
1
s
F2
50
12E0
General Input G Alarm Events
0 to 1
1
–
F105
0
12E1
General Input G Trip
0 to 2
1
–
F115
0
12E2
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
12E3
General Input G Trip Delay
1 to 50000
1
s
F2
50
DIGITAL INPUTS / REMOTE RESET
1300
Assign Digital Input
0 to 7
1
–
F210
0
DIGITAL INPUTS / TEST INPUT
1310
Assign Digital Input
0 to 7
1
–
F210
0
DIGITAL INPUTS / THERMAL RESET
1320
Assign Digital Input
0 to 7
1
–
F210
0
DIGITAL INPUTS / DUAL SETPOINTS
1340
Assign Digital Input
0 to 7
1
–
F210
0
1341
Active Setpoint Group
0 to 1
1
–
F118
0
1342
Edit Setpoint Group
0 to 1
1
–
F118
0
DIGITAL INPUTS / SEQUENTIAL TRIP
1360
Assign Digital Input
0 to 7
1
–
F210
0
1361
Sequential Trip Type
0 to 1
1
–
F206
0
1362
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
1363
Sequential Trip Level
2 to 99
1
×
Rated MW
F14
5
1365
Sequential Trip Delay
2 to 1200
1
s
F2
10
DIGITAL INPUTS / FIELD-BREAKER DISCREPANCY
1380
Assign Digital Input
0 to 7
1
–
F210
0
1381
Field Status Contact
0 to 1
1
–
F109
0
1382
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
1383
Field-Breaker Discrepancy Trip Delay
1 to 5000
1
s
F2
10
DIGITAL INPUTS / TACHOMETER
13A0
Assign Digital Input
0 to 7
1
–
F210
0
13A1
Rated Speed
100 to 3600
1
RPM
F1
3600
13A2
Tachometer Alarm
0 to 2
1
–
F115
0
13A3
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
13A4
Tachometer Alarm Speed
101 to 175
1
%Rated
F1
110
13A5
Tachometer Alarm Delay
1 to 250
1
s
F1
1
13A6
Tachometer Alarm Events
0 to 1
1
–
F105
0
13A7
Tachometer Trip
0 to 2
1
–
F115
0
13A8
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
13A9
Tachometer Trip Speed
101 to 175
1
%Rated
F1
110
13AA
Tachometer Trip Delay
1 to 250
1
s
F1
1
DIGITAL INPUTS / WAVEFORM CAPTURE
13C0
Assign Digital Input
0 to 7
1
–
F210
0
DIGITAL INPUTS / GROUND SWITCH STATUS
13D0
Assign Digital Input
0 to 7
1
–
F210
0
13D1
Ground Switch Contact
0 to 1
1
–
F109
0
OUTPUT RELAYS / RELAY RESET MODE
Table CG–1: 489 Memory Map (Sheet 12 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42