489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
39
2B5E
Mvar Demand Minimum
0 to 200
1
×
Rated
F3
0
2B5F
Mvar Demand Maximum
0 to 200
1
×
Rated
F3
125
2B60
MW Demand Minimum
0 to 200
1
×
Rated
F3
0
2B61
MW Demand Maximum
0 to 200
1
×
Rated
F3
125
2B62
MVA Demand Minimum
0 to 200
1
×
Rated
F3
0
2B63
MVA Demand Maximum
0 to 200
1
×
Rated
F3
125
ANALOG INPUT/OUTPUT / ANALOG INPUT 1
2C00
Analog Input 1
0 to 3
1
–
F129
0
2C05
Analog Input 1 Units
0 to 6
1
–
F22
_
2C08
Analog Input 1 Minimum
–50000 to 50000
1
Units
F12
0
2C0A
Analog Input 1 Maximum
–50000 to 50000
1
Units
F12
100
2C0C
Block Analog Input 1 From Online
0 to 5000
1
s
F1
0
2C0D
Analog Input 1 Alarm
0 to 2
1
–
F115
0
2C0E
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2C0F
Analog Input 1 Alarm Level
–50000 to 50000
1
Units
F12
10
2C11
Analog Input 1 Alarm Pickup
0 to 1
1
–
F130
0
2C12
Analog Input 1 Alarm Delay
1 to 3000
1
s
F2
1
2C13
Analog Input 1 Alarm Events
0 to 1
1
–
F105
0
2C14
Analog Input 1 Trip
0 to 2
1
–
F115
0
2C15
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2C16
Analog Input 1 Trip Level
–50000 to 50000
1
Units
F12
20
2C18
Analog Input 1 Trip Pickup
0 to 1
1
–
F130
0
2C19
Analog Input 1 Trip Delay
1 to 3000
1
s
F2
1
2C1A
Analog Input 1 Name
0 to 12
1
–
F22
_
ANALOG INPUT/OUTPUT / ANALOG INPUT 2
2C40
Analog Input 2
0 to 3
1
–
F129
0
2C45
Analog Input 2 Units
0 to 6
1
–
F22
_
2C48
Analog Input 2 Minimum
–50000 to 50000
1
Units
F12
0
2C4A
Analog Input 2 Maximum
–50000 to 50000
1
Units
F12
100
2C4C
Block Analog Input 2 From Online
0 to 5000
1
s
F1
0
2C4D
Analog Input 2 Alarm
0 to 2
1
–
F115
0
2C4E
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2C4F
Analog Input 2 Alarm Level
–50000 to 50000
1
Units
F12
10
2C51
Analog Input 2 Alarm Pickup
0 to 1
1
–
F130
0
2C52
Analog Input 2 Alarm Delay
1 to 3000
1
s
F2
1
2C53
Analog Input 2 Alarm Events
0 to 1
1
–
F105
0
2C54
Analog Input 2 Trip
0 to 2
1
–
F115
0
2C55
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2C56
Analog Input 2 Trip Level
–50000 to 50000
1
Units
F12
20
2C58
Analog Input 2 Trip Pickup
0 to 1
1
–
F130
0
2C59
Analog Input 2 Trip Delay
1 to 3000
1
s
F2
1
2C5A
Analog Input 2 Name
0 to 12
1
–
F22
_
ANALOG INPUT/OUTPUT / ANALOG INPUT 3
2C80
Analog Input 3
0 to 3
1
–
F129
0
2C85
Analog Input 3 Units
0 to 6
1
–
F22
_
2C88
Analog Input 3 Minimum
–50000 to 50000
1
Units
F12
0
2C8A
Analog Input 3 Maximum
–50000 to 50000
1
Units
F12
100
2C8C
Block Analog Input 3 From Online
0 to 5000
1
s
F1
0
2C8D
Analog Input 3 Alarm
0 to 2
1
–
F115
0
2C8E
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2C8F
Analog Input 3 Alarm Level
–50000 to 50000
1
Units
F12
10
2C91
Analog Input 3 Alarm Pickup
0 to 1
1
–
F130
0
2C92
Analog Input 3 Alarm Delay
1 to 3000
1
s
F2
1
Table CG–1: 489 Memory Map (Sheet 27 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42