489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
23
1261
General Input C Trip
0 to 2
1
–
F115
0
1262
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
1263
General Input C Trip Delay
1 to 50000
1
s
F2
50
DIGITAL INPUTS / GENERAL INPUT D
1270
Assign Digital Input
0 to 7
1
–
F210
0
1271
Asserted Digital Input State
0 to 1
1
–
F131
0
1272
Input Name
0 to 12
1
–
F22
_
1278
Block Input From Online
0 to 5000
1
s
F1
0
1279
General Input D Control
0 to 1
1
–
F105
0
127A
Pulsed Control Relay Dwell Time
0 to 250
1
s
F2
0
127B
Assign Control Relays (1-5)
0 to 4
1
–
F50
0
127C
General Input D Control Events
0 to 1
1
–
F105
0
127D
General Input D Alarm
0 to 2
1
–
F115
0
127E
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
127F
General Input D Alarm Delay
1 to 50000
1
s
F2
50
1280
General Input D Alarm Events
0 to 1
1
–
F105
0
1281
General Input D Trip
0 to 2
1
–
F115
0
1282
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
1283
General Input D Trip Delay
1 to 50000
1
s
F2
50
DIGITAL INPUTS / GENERAL INPUT E
1290
Assign Digital Input
0 to 7
1
–
F210
0
1291
Asserted Digital Input State
0 to 1
1
–
F131
0
1292
Input Name
0 to 12
1
–
F22
_
1298
Block Input From Online
0 to 5000
1
s
F1
0
1299
General Input E Control
0 to 1
1
–
F105
0
129A
Pulsed Control Relay Dwell Time
0 to 250
1
s
F2
0
129B
Assign Control Relays (1-5)
0 to 4
1
–
F50
0
129C
General Input E Control Events
0 to 1
1
–
F105
0
129D
General Input E Alarm
0 to 2
1
–
F115
0
129E
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
129F
General Input E Alarm Delay
1 to 50000
1
s
F2
50
12A0
General Input E Alarm Events
0 to 1
1
–
F105
0
12A1
General Input E Trip
0 to 2
1
–
F115
0
12A2
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
12A3
General Input E Trip Delay
1 to 50000
1
s
F2
50
DIGITAL INPUTS / GENERAL INPUT F
12B0
Assign Digital Input
0 to 7
1
–
F210
0
12B1
Asserted Digital Input State
0 to 1
1
–
F131
0
12B2
Input Name
0 to 12
1
–
F22
_
12B8
Block Input From Online
0 to 5000
1
s
F1
0
12B9
General Input F Control
0 to 1
1
–
F105
0
12BA
Pulsed Control Relay Dwell Time
0 to 250
1
s
F2
0
12BB
Assign Control Relays (1-5)
0 to 4
1
–
F50
0
12BC
General Input F Control Events
0 to 1
1
–
F105
0
12BD
General Input F Alarm
0 to 2
1
–
F115
0
12BE
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
12BF
General Input F Alarm Delay
1 to 50000
1
s
F2
50
12C0
General Input F Alarm Events
0 to 1
1
–
F105
0
12C1
General Input F Trip
0 to 2
1
–
F115
0
12C2
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
12C3
General Input F Trip Delay
1 to 50000
1
s
F2
50
DIGITAL INPUTS / GENERAL INPUT G
12D0
Assign Digital Input
0 to 7
1
–
F210
0
Table CG–1: 489 Memory Map (Sheet 11 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42