![GE MLP1000 Manual Download Page 90](http://html.mh-extra.com/html/ge/mlp1000/mlp1000_manual_130370090.webp)
GEK-98846A
89
7.7 EQUIPMENT TESTING PROCEDURES AND CONNECTION AFTER THE
EQUIPMENT IS INSTALLED.
The same procedure can be used as for the acceptance tests once the system
input and output separation measurements have been taken. When equipment testing is
performed without extracting any module keep in mind that XTM test combs interrupt the
trip signals and close signals only. The rest of the contacts remain connected and can
operate, depending on the test performed To avoid this, the wiring for the related terminals
must be disconnected, making sure that when finished all wires are reconnected properly.
The external connections scheme of figures 3.1, 3.5, and 3.9 shows which logic and analog
inputs pass through the test block (indicated by the sign ><)
8. RECEPTION, HANDLING, AND STORAGE
CAUTION
This relay contains electronic components which could be damaged by
electrostatic discharge currents if those currents flow through certain terminals of
the components. The main source of electrostatic discharge currents is the human
body. Conditions such as low humidity, carpeted floors and isolating shoes are
conducive to the generation of electrostatic discharge currents. Where these
conditions exist, care should be exercised when removing and handling the modules
to make settings on the internal switches. The persons handling the module should
make sure that their body charge has been discharged by touching some surface at
ground potential before touching any of the components on the modules.
This relay is supplied to the customer in a special package, which adequately
protects it during transportation, as long as this is performed under normal conditions.
Immediately after receiving the relay, the customer should check whether it shows
any signs of transportation damage. If it is apparent that the relay has been damaged due
to inappropriate handling, it must be immediately reported in writing to the transportation
carrier, and the damage must be reported to the manufacturer.
For unpacking the relay, care should be taken not to lose the screws also supplied
in the box.
If you do not intend to install the relay immediately, it is recommended that the relay
be stored in its original packaging and kept in a dry, dust-free place.
It is important to check that the data on the name plate coincides with the data from
the order
Summary of Contents for MLP1000
Page 94: ...GEK 98846A 93 Figure 1 System diagram with MLP CPR and TTI ...
Page 95: ...GEK 98846A 94 Figure 2 Case dimensions and drilling form 1 rack ...
Page 96: ...GEK 98846A 95 Figure 3 1 External Connections MLP1000 ...
Page 97: ...GEK 98846A 96 Figure 3 2 External Connections MLP1000 ...
Page 99: ...GEK 98846A 98 Figure 3 4 External Connections MLP1000 ...
Page 100: ...GEK 98846A 99 Figure 3 5 External Connections MLP2000 ...
Page 101: ...GEK 98846A 100 Figure 3 6 External Connections MLP2000 ...
Page 103: ...GEK 98846A 102 Figure 3 8 External Connections MLP2000 ...
Page 104: ...GEK 98846A 103 Figure 3 9 External Connections MLP3000 ...
Page 105: ...GEK 98846A 104 Figure 3 10 External Connections MLP3000 ...
Page 107: ...GEK 98846A 106 Figure 3 12 External Connections MLP3000 ...
Page 108: ...GEK 98846A 107 Figure 4 Protection Logic ...
Page 109: ...GEK 98846A 108 Figure 5 1 Trip decision diagram ...
Page 110: ...GEK 98846A 109 Figure 5 2 Trip decision diagram ...
Page 111: ...GEK 98846A 110 Figure 5 3 Trip decision diagram ...
Page 112: ...GEK 98846A 111 Figure 5 4 Trip decision diagram ...
Page 113: ...GEK 98846A 112 Figure 6 1 Z1X protection scheme ...
Page 114: ...GEK 98846A 113 Figure6 2 ACCZ2 Protection scheme ...
Page 115: ...GEK 98846A 114 Figure7 LPU function diagram ...
Page 116: ...GEK 98846A 115 Figure 8 1 ROD function logic ...
Page 117: ...GEK 98846A 116 Figure 8 2 ROD function diagram ...
Page 118: ...GEK 98846A 117 Figure 9 1 DD function logic ...
Page 119: ...GEK 98846A 118 Figure 9 2 DD function diagram ...
Page 120: ...GEK 98846A 119 Figure 10 1 FF function logic ...
Page 121: ...GEK 98846A 120 Figure 10 2 FF function diagram ...
Page 122: ...GEK 98846A 121 Figure 11 1 Recloser diagram ...
Page 123: ...GEK 98846A 122 Figure 11 2 Recloser Diagram ...
Page 124: ...GEK 98846A 123 Figure 11 3 Recloser Diagram ...
Page 125: ...GEK 98846A 124 Figure 12 Fault selector ...
Page 126: ...GEK 98846A 125 Figure 13 Menu Tree Diagram ...
Page 127: ...GEK 98846A 126 Figure 14 MLP3000 Settings and data ...
Page 128: ...GEK 98846A 127 Figure 15 Connection scheme for relay tests ...
Page 129: ...GEK 98846A 128 Figure 16 Power swing diagram function ...
Page 130: ...GEK 98846A 129 Figure 17 Mho Reactance characteristics of the MLP ...