GEK-98846A
74
α
= degrees that V leads I
α
REACTZ2ØG-5IN In=5A
REACTZ2ØG-1IN In=1A
Voltage
Acceptable Range
Voltage
Acceptable Range
+49.0
58.33
55.42 - 61.25
38.89
36.95 - 40.83
+59.0
51.36
48.79 - 53.92
34.24
32.53 - 35.95
+69.0
47.16
44.80 - 49.52
31.44
29.87 - 33.01
+79.0
44.85
42.61 - 47.09
29.90
28.40 - 31.39
+89.0
44.03
41.83 - 46.23
29.36
27.89 - 30.82
+99.0
44.57
42.35 - 46.80
29.72
28.23 - 31.20
+109.0
46.56
44.23 - 48.89
31.04
29.49 - 32.59
6.2.6 TWO PHASE MEASUREMENT UNIT'S REACH FOR THE MHO
CHARACTERISTIC
* The operation quantities used in the MHO units for phase-phase faults are:
Fault
Operation Quantity
Polarization Quantity.
ØØ
(IØ - IØ’)x Zr -(VØ - VØ’)
(VØ1m - VØ1m)
Where:
Zr:
Adjusted impedance reach.
VØn:
Ground phase voltage
VØ1m: Negative sequence voltage with memory referenced to the Ø phase.
IØ:
Phase current.
Θ
1 :
Positive sequence line impedance angle
* Set the following protection settings:
201 - OSB IN SERVICE
NO
202 - LPU IN SERVICE
NO
203 - ROD IN SERVICE:
NO
204 - FF IN SERVICE:
NO
207 - MHO/REACT:
MHO
208 - PROTEC. SCHEME
0 = D.E.
209 - PROT. IN SERVICE
YES
212 - GENERAL TRIP:
YES
213 - Z3 TRIP:
YES
214 - Z2 TRIP:
YES
215 - Zl TRIP:
YES
219 - POSITIVE SEQUENCE IMPEDANCE (ZL1 IMPED):
6.0
220 - POSITIVE SEQUENCE ANGLE (ZL1 ANGLE):
85°
221 - ZERO SEQUENCE CURRENT COMPENSATION (K0):
3.0
222 - ZERO SEQUENCE ANGLE(ZL0 ANGLE):
75º
223 - Z1 REACH:
4.80
224 - Z1X REACH:
1.40
225 - Z2 REACH:
9.00
226 - Z3 REACH:
12.0
228 - Z1 TIMER:
0
Summary of Contents for MLP1000
Page 94: ...GEK 98846A 93 Figure 1 System diagram with MLP CPR and TTI ...
Page 95: ...GEK 98846A 94 Figure 2 Case dimensions and drilling form 1 rack ...
Page 96: ...GEK 98846A 95 Figure 3 1 External Connections MLP1000 ...
Page 97: ...GEK 98846A 96 Figure 3 2 External Connections MLP1000 ...
Page 99: ...GEK 98846A 98 Figure 3 4 External Connections MLP1000 ...
Page 100: ...GEK 98846A 99 Figure 3 5 External Connections MLP2000 ...
Page 101: ...GEK 98846A 100 Figure 3 6 External Connections MLP2000 ...
Page 103: ...GEK 98846A 102 Figure 3 8 External Connections MLP2000 ...
Page 104: ...GEK 98846A 103 Figure 3 9 External Connections MLP3000 ...
Page 105: ...GEK 98846A 104 Figure 3 10 External Connections MLP3000 ...
Page 107: ...GEK 98846A 106 Figure 3 12 External Connections MLP3000 ...
Page 108: ...GEK 98846A 107 Figure 4 Protection Logic ...
Page 109: ...GEK 98846A 108 Figure 5 1 Trip decision diagram ...
Page 110: ...GEK 98846A 109 Figure 5 2 Trip decision diagram ...
Page 111: ...GEK 98846A 110 Figure 5 3 Trip decision diagram ...
Page 112: ...GEK 98846A 111 Figure 5 4 Trip decision diagram ...
Page 113: ...GEK 98846A 112 Figure 6 1 Z1X protection scheme ...
Page 114: ...GEK 98846A 113 Figure6 2 ACCZ2 Protection scheme ...
Page 115: ...GEK 98846A 114 Figure7 LPU function diagram ...
Page 116: ...GEK 98846A 115 Figure 8 1 ROD function logic ...
Page 117: ...GEK 98846A 116 Figure 8 2 ROD function diagram ...
Page 118: ...GEK 98846A 117 Figure 9 1 DD function logic ...
Page 119: ...GEK 98846A 118 Figure 9 2 DD function diagram ...
Page 120: ...GEK 98846A 119 Figure 10 1 FF function logic ...
Page 121: ...GEK 98846A 120 Figure 10 2 FF function diagram ...
Page 122: ...GEK 98846A 121 Figure 11 1 Recloser diagram ...
Page 123: ...GEK 98846A 122 Figure 11 2 Recloser Diagram ...
Page 124: ...GEK 98846A 123 Figure 11 3 Recloser Diagram ...
Page 125: ...GEK 98846A 124 Figure 12 Fault selector ...
Page 126: ...GEK 98846A 125 Figure 13 Menu Tree Diagram ...
Page 127: ...GEK 98846A 126 Figure 14 MLP3000 Settings and data ...
Page 128: ...GEK 98846A 127 Figure 15 Connection scheme for relay tests ...
Page 129: ...GEK 98846A 128 Figure 16 Power swing diagram function ...
Page 130: ...GEK 98846A 129 Figure 17 Mho Reactance characteristics of the MLP ...