![GE MLP1000 Manual Download Page 38](http://html.mh-extra.com/html/ge/mlp1000/mlp1000_manual_130370038.webp)
GEK-98846A
37
4.17 SELF CHECKS AND ERROR ROUTINES.
The MLP performs the following self checks during startup as well during the idle
time when protection and communications functions are not being performed:
−
Analog digital converter.
−
Power supply (15 V)
−
Oscillographic (RAM) memory
−
Working (RAM) memory
−
(EEPROM) no volatile memory portion that includes the event register.
−
EEPROM portion that includes the system configuration (settings and calibration)
If a critical error is detected during the startup tests the following actions are taken:
- the alarm is activated
- the outputs are disabled
- the protection and the recloser are taken off-line
- communications are enabled
- the protection is placed in an infinite program loop that cannot be exited until power
is disconnected and w hen connected again the failure that caused the critical
error disappears.
To indicate locally that the relay is in this program loop, the "READY" LED on the
front panel of the relay is switched off and an error message is displayed on the monitor.
If a critical error is detected during the time when communications and protection
operations are idle, the system is reset. If the critical error is detected during the reset
initiation, the protection will enter into the infinite program loop described above.
Description of failures:
Critical errors:
−
Analog/digital converter error.
−
Non-recoverable power supply loss (15V)
−
Working (RAM) memory error.
−
Error in the part of the (EEPROM) no volatile memory that contains the system
configuration, settings and calibration (see EEPROM errors).
Non critical errors:
−
Oscillographic (RAM) memory error.
−
Error in the part of the (EEPROM) memory that contains the event log.
Testing the A/D converters consists of measuring a reference voltage taken from
+5 VDC. The failure for this test is considered critical.
The MLP uses two WATCHDOGS as a program monitoring system.
The breaker status is checked constantly and if the breaker is open with current
passing, an alarm indication is triggered and the event is registered.
Summary of Contents for MLP1000
Page 94: ...GEK 98846A 93 Figure 1 System diagram with MLP CPR and TTI ...
Page 95: ...GEK 98846A 94 Figure 2 Case dimensions and drilling form 1 rack ...
Page 96: ...GEK 98846A 95 Figure 3 1 External Connections MLP1000 ...
Page 97: ...GEK 98846A 96 Figure 3 2 External Connections MLP1000 ...
Page 99: ...GEK 98846A 98 Figure 3 4 External Connections MLP1000 ...
Page 100: ...GEK 98846A 99 Figure 3 5 External Connections MLP2000 ...
Page 101: ...GEK 98846A 100 Figure 3 6 External Connections MLP2000 ...
Page 103: ...GEK 98846A 102 Figure 3 8 External Connections MLP2000 ...
Page 104: ...GEK 98846A 103 Figure 3 9 External Connections MLP3000 ...
Page 105: ...GEK 98846A 104 Figure 3 10 External Connections MLP3000 ...
Page 107: ...GEK 98846A 106 Figure 3 12 External Connections MLP3000 ...
Page 108: ...GEK 98846A 107 Figure 4 Protection Logic ...
Page 109: ...GEK 98846A 108 Figure 5 1 Trip decision diagram ...
Page 110: ...GEK 98846A 109 Figure 5 2 Trip decision diagram ...
Page 111: ...GEK 98846A 110 Figure 5 3 Trip decision diagram ...
Page 112: ...GEK 98846A 111 Figure 5 4 Trip decision diagram ...
Page 113: ...GEK 98846A 112 Figure 6 1 Z1X protection scheme ...
Page 114: ...GEK 98846A 113 Figure6 2 ACCZ2 Protection scheme ...
Page 115: ...GEK 98846A 114 Figure7 LPU function diagram ...
Page 116: ...GEK 98846A 115 Figure 8 1 ROD function logic ...
Page 117: ...GEK 98846A 116 Figure 8 2 ROD function diagram ...
Page 118: ...GEK 98846A 117 Figure 9 1 DD function logic ...
Page 119: ...GEK 98846A 118 Figure 9 2 DD function diagram ...
Page 120: ...GEK 98846A 119 Figure 10 1 FF function logic ...
Page 121: ...GEK 98846A 120 Figure 10 2 FF function diagram ...
Page 122: ...GEK 98846A 121 Figure 11 1 Recloser diagram ...
Page 123: ...GEK 98846A 122 Figure 11 2 Recloser Diagram ...
Page 124: ...GEK 98846A 123 Figure 11 3 Recloser Diagram ...
Page 125: ...GEK 98846A 124 Figure 12 Fault selector ...
Page 126: ...GEK 98846A 125 Figure 13 Menu Tree Diagram ...
Page 127: ...GEK 98846A 126 Figure 14 MLP3000 Settings and data ...
Page 128: ...GEK 98846A 127 Figure 15 Connection scheme for relay tests ...
Page 129: ...GEK 98846A 128 Figure 16 Power swing diagram function ...
Page 130: ...GEK 98846A 129 Figure 17 Mho Reactance characteristics of the MLP ...