VOLTAGE TRANSFORMER SUPERVISION
The Voltage Transformer Supervision (VTS) function is used to detect failure of the AC voltage inputs to the
protection. This may be caused by voltage transformer faults, overloading, or faults on the wiring, which usually
results in one or more of the voltage transformer fuses blowing.
If there is a failure of the AC voltage input, the IED could misinterpret this as a failure of the actual phase voltages
on the power system, which could result in unnecessary tripping of a circuit breaker.
The VTS logic is designed to prevent such a situation by detecting voltage input failures, which are NOT caused by
power system phase voltage failure, and automatically blocking associated voltage dependent protection
elements. A time-delayed alarm output is available to warn of a VTS condition.
The following scenarios are possible with respect to the failure of the VT inputs.
●
Loss of one or two-phase voltages
●
Loss of all three-phase voltages under load conditions
●
Absence of three-phase voltages upon line energisation
2.1
LOSS OF ONE OR TWO PHASE VOLTAGES
If the power system voltages are healthy, no Negative Phase Sequence (NPS) current will be present. If however,
one or two of the AC voltage inputs are missing, there will be Negative Phase Sequence voltage present, even if the
actual power system phase voltages are healthy. VTS works by detecting Negative Phase Sequence (NPS) voltage
without the presence of Negative Phase Sequence current. So if there is NPS voltage present, but no NPS current,
it is certain that there is a problem with the voltage transformers and a VTS block should be applied to voltage
dependent protection functions to prevent maloperation. The use of negative sequence quantities ensures correct
operation even where three-limb or V-connected VTs are used.
The Negative Sequence VTS Element is blocked by the Any Pole Dead DDB signal during SP AR Dead Time. The
resetting of the blocking signal is delayed by 240 ms after an Any Pole Dead condition disappears.
2.2
LOSS OF ALL THREE PHASE VOLTAGES
If all three voltage inputs are lost, there will be no Negative Phase Sequence quantities present, but the device will
see that there is no voltage input. If this is caused by a power system failure, there will be a step change in the
phase currents. However, if this is not caused by a power system failure, there will be no change in any of the
phase currents. So if there is no measured voltage on any of the three phases and there is no change in any of the
phase currents, this indicates that there is a problem with the voltage transformers and a VTS block should be
applied to voltage dependent protection functions to prevent maloperation.
To avoid blocking VTS due to changing load condition, the superimposed current signal can only prevent operation
of the VTS during the time window of 40 ms following the voltage collapse.
2.3
ABSENCE OF ALL THREE PHASE VOLTAGES ON LINE ENERGISATION
On line energisation there should be a change in the phase currents as a result of loading or line charging current.
Under this condition we need an alternative method of detecting three-phase VT failure.
If there is no measured voltage on all three phases during line energisation, two conditions might apply:
●
A three-phase VT failure
●
A close-up three-phase fault.
The first condition would require VTS to block the voltage-dependent functions.
In the second condition, voltage dependent functions should not be blocked, as tripping is required.
To differentiate between these two conditions an overcurrent level detector is used (VTS I> Inhibit). This prevents a
VTS block from being issued in case of a genuine fault. This overcurrent level detector is only enabled for 240 ms
Chapter 17 - Supervision
P446SV
448
P446SV-TM-EN-1
Summary of Contents for MiCOM P40 Agile
Page 2: ......
Page 24: ...Contents P446SV xxii P446SV TM EN 1 ...
Page 33: ...CHAPTER 1 INTRODUCTION ...
Page 34: ...Chapter 1 Introduction P446SV 2 P446SV TM EN 1 ...
Page 46: ...Chapter 1 Introduction P446SV 14 P446SV TM EN 1 ...
Page 47: ...CHAPTER 2 SAFETY INFORMATION ...
Page 48: ...Chapter 2 Safety Information P446SV 16 P446SV TM EN 1 ...
Page 60: ...Chapter 2 Safety Information P446SV 28 P446SV TM EN 1 ...
Page 61: ...CHAPTER 3 HARDWARE DESIGN ...
Page 62: ...Chapter 3 Hardware Design P446SV 30 P446SV TM EN 1 ...
Page 88: ...Chapter 3 Hardware Design P446SV 56 P446SV TM EN 1 ...
Page 89: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 90: ...Chapter 4 Software Design P446SV 58 P446SV TM EN 1 ...
Page 101: ...CHAPTER 5 CONFIGURATION ...
Page 102: ...Chapter 5 Configuration P446SV 70 P446SV TM EN 1 ...
Page 124: ...Chapter 5 Configuration P446SV 92 P446SV TM EN 1 ...
Page 125: ...CHAPTER 6 SAMPLED VALUE OPERATION ...
Page 126: ...Chapter 6 Sampled Value Operation P446SV 94 P446SV TM EN 1 ...
Page 136: ...Chapter 6 Sampled Value Operation P446SV 104 P446SV TM EN 1 ...
Page 137: ...CHAPTER 7 DISTANCE PROTECTION ...
Page 138: ...Chapter 7 Distance Protection P446SV 106 P446SV TM EN 1 ...
Page 196: ...Chapter 7 Distance Protection P446SV 164 P446SV TM EN 1 ...
Page 197: ...CHAPTER 8 CARRIER AIDED SCHEMES ...
Page 198: ...Chapter 8 Carrier Aided Schemes P446SV 166 P446SV TM EN 1 ...
Page 240: ...Chapter 8 Carrier Aided Schemes P446SV 208 P446SV TM EN 1 ...
Page 241: ...CHAPTER 9 NON AIDED SCHEMES ...
Page 242: ...Chapter 9 Non Aided Schemes P446SV 210 P446SV TM EN 1 ...
Page 256: ...Chapter 9 Non Aided Schemes P446SV 224 P446SV TM EN 1 ...
Page 257: ...CHAPTER 10 POWER SWING FUNCTIONS ...
Page 258: ...Chapter 10 Power Swing Functions P446SV 226 P446SV TM EN 1 ...
Page 281: ...CHAPTER 11 AUTORECLOSE ...
Page 282: ...Chapter 11 Autoreclose P446SV 250 P446SV TM EN 1 ...
Page 376: ...Chapter 11 Autoreclose P446SV 344 P446SV TM EN 1 ...
Page 377: ...CHAPTER 12 CB FAIL PROTECTION ...
Page 378: ...Chapter 12 CB Fail Protection P446SV 346 P446SV TM EN 1 ...
Page 389: ...CHAPTER 13 CURRENT PROTECTION FUNCTIONS ...
Page 390: ...Chapter 13 Current Protection Functions P446SV 358 P446SV TM EN 1 ...
Page 416: ...Chapter 13 Current Protection Functions P446SV 384 P446SV TM EN 1 ...
Page 417: ...CHAPTER 14 VOLTAGE PROTECTION FUNCTIONS ...
Page 418: ...Chapter 14 Voltage Protection Functions P446SV 386 P446SV TM EN 1 ...
Page 431: ...CHAPTER 15 FREQUENCY PROTECTION FUNCTIONS ...
Page 432: ...Chapter 15 Frequency Protection Functions P446SV 400 P446SV TM EN 1 ...
Page 438: ...Chapter 15 Frequency Protection Functions P446SV 406 P446SV TM EN 1 ...
Page 439: ...CHAPTER 16 MONITORING AND CONTROL ...
Page 440: ...Chapter 16 Monitoring and Control P446SV 408 P446SV TM EN 1 ...
Page 476: ...Chapter 16 Monitoring and Control P446SV 444 P446SV TM EN 1 ...
Page 477: ...CHAPTER 17 SUPERVISION ...
Page 478: ...Chapter 17 Supervision P446SV 446 P446SV TM EN 1 ...
Page 490: ...Chapter 17 Supervision P446SV 458 P446SV TM EN 1 ...
Page 491: ...CHAPTER 18 DIGITAL I O AND PSL CONFIGURATION ...
Page 492: ...Chapter 18 Digital I O and PSL Configuration P446SV 460 P446SV TM EN 1 ...
Page 504: ...Chapter 18 Digital I O and PSL Configuration P446SV 472 P446SV TM EN 1 ...
Page 505: ...CHAPTER 19 FIBRE TELEPROTECTION ...
Page 506: ...Chapter 19 Fibre Teleprotection P446SV 474 P446SV TM EN 1 ...
Page 522: ...Chapter 19 Fibre Teleprotection P446SV 490 P446SV TM EN 1 ...
Page 523: ...CHAPTER 20 ELECTRICAL TELEPROTECTION ...
Page 524: ...Chapter 20 Electrical Teleprotection P446SV 492 P446SV TM EN 1 ...
Page 534: ...Chapter 20 Electrical Teleprotection P446SV 502 P446SV TM EN 1 ...
Page 535: ...CHAPTER 21 COMMUNICATIONS ...
Page 536: ...Chapter 21 Communications P446SV 504 P446SV TM EN 1 ...
Page 606: ...Chapter 21 Communications P446SV 574 P446SV TM EN 1 ...
Page 607: ...CHAPTER 22 CYBER SECURITY ...
Page 608: ...Chapter 22 Cyber Security P446SV 576 P446SV TM EN 1 ...
Page 625: ...CHAPTER 23 INSTALLATION ...
Page 626: ...Chapter 23 Installation P446SV 594 P446SV TM EN 1 ...
Page 637: ...CHAPTER 24 COMMISSIONING INSTRUCTIONS ...
Page 638: ...Chapter 24 Commissioning Instructions P446SV 606 P446SV TM EN 1 ...
Page 695: ...CHAPTER 25 MAINTENANCE AND TROUBLESHOOTING ...
Page 696: ...Chapter 25 Maintenance and Troubleshooting P446SV 664 P446SV TM EN 1 ...
Page 712: ...Chapter 25 Maintenance and Troubleshooting P446SV 680 P446SV TM EN 1 ...
Page 713: ...CHAPTER 26 TECHNICAL SPECIFICATIONS ...
Page 714: ...Chapter 26 Technical Specifications P446SV 682 P446SV TM EN 1 ...
Page 741: ...APPENDIX A ORDERING OPTIONS ...
Page 742: ...Appendix A Ordering Options P446SV P446SV TM EN 1 ...
Page 744: ...Appendix A Ordering Options P446SV A2 P446SV TM EN 1 ...
Page 745: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 746: ...Appendix B Settings and Signals P446SV P446SV TM EN 1 ...
Page 954: ...Appendix B Settings and Signals P446SV B208 P446SV TM EN 1 ...
Page 955: ...APPENDIX C WIRING DIAGRAMS ...
Page 956: ...Appendix C Wiring Diagrams P446SV P446SV TM EN 1 ...
Page 960: ......
Page 961: ......