6
LOSS OF LOAD SCHEME
The Loss of Load Scheme provides fast unit protection performance for most fault types occurring on a double-
end fed line or feeder, but it does not need communications.
It is used on circuits that are designed for three-pole tripping, and provides protection for faults involving one or
two phases. It is not suitable for single-pole tripping applications, and it cannot protect against three-phase faults.
The scheme does not require communications, but it can be used alongside carrier aided schemes if
communications are available.
The Loss-of-Load scheme can be permanently enabled, permanently disabled, or enabled if communication failure
compromises channel-aided scheme operation. If used in conjunction with a channel-aided scheme, loss of load
can be set to be enabled if only Channel 1 fails, or if only Channel 2 fails, or if both channels fail, or if either channel
fails. Aided scheme communication failure is detected by permissive scheme unblocking logic, or the presence of a
Channel Out of Service (COS) input.
V02740
Zone 2 IED1
Zone 1 IED 1
Zone 1 IED 2
Zone 2 IED 2
IED 1
IED 2
Figure 115: Loss of load accelerated trip scheme
Any fault in the reach of Zone 1 results in fast tripping of the local circuit breaker. For an end zone fault for IED 1
(near IED 2) with remote infeed (from IED 2), the remote breaker is tripped in Zone 1 by the remote device at IED 2.
The local device (IED 1) can recognise this by detecting loss of load current in the healthy phases. This condition, in
conjunction with operation of a Zone 2 comparator at IED 1P, can be used to trip the local circuit breaker.
Before an accelerated trip can occur, load current must be detected before the fault. The loss of load current
opens a window during which time a trip occurs if a Zone 2 comparator operates. A typical setting for this window
is 40ms as shown in the figure below, although this can be altered in the LoL Window setting. The accelerated trip
is delayed by 18ms to prevent initiation of a loss of load trip due to circuit breaker pole discrepancy occurring for
clearance of an external fault. The local fault clearance time can be deduced as follows:
t = Z1d + 2CB + LDr + 18ms
where:
●
Z1d = Maximum downstream zone 1 trip time
●
CB = Breaker operating time
●
LDr = Upstream level detector (LOL <1) reset time
For circuits with load tapped off the protected line, care must be taken in setting the loss of load feature to ensure
that the undercurrent level detector setting is above the tapped load current. When selected, the loss of load
feature operates with the main distance scheme that is selected. This provides high speed clearance for end zone
faults when the Basic scheme is selected or, with permissive signal aided tripping schemes, it provides high speed
back up clearance for end zone faults if the channel fails.
Note:
Loss of load tripping is only available where three pole tripping is used.
Chapter 9 - Non-Aided Schemes
P446SV
222
P446SV-TM-EN-1
Summary of Contents for MiCOM P40 Agile
Page 2: ......
Page 24: ...Contents P446SV xxii P446SV TM EN 1 ...
Page 33: ...CHAPTER 1 INTRODUCTION ...
Page 34: ...Chapter 1 Introduction P446SV 2 P446SV TM EN 1 ...
Page 46: ...Chapter 1 Introduction P446SV 14 P446SV TM EN 1 ...
Page 47: ...CHAPTER 2 SAFETY INFORMATION ...
Page 48: ...Chapter 2 Safety Information P446SV 16 P446SV TM EN 1 ...
Page 60: ...Chapter 2 Safety Information P446SV 28 P446SV TM EN 1 ...
Page 61: ...CHAPTER 3 HARDWARE DESIGN ...
Page 62: ...Chapter 3 Hardware Design P446SV 30 P446SV TM EN 1 ...
Page 88: ...Chapter 3 Hardware Design P446SV 56 P446SV TM EN 1 ...
Page 89: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 90: ...Chapter 4 Software Design P446SV 58 P446SV TM EN 1 ...
Page 101: ...CHAPTER 5 CONFIGURATION ...
Page 102: ...Chapter 5 Configuration P446SV 70 P446SV TM EN 1 ...
Page 124: ...Chapter 5 Configuration P446SV 92 P446SV TM EN 1 ...
Page 125: ...CHAPTER 6 SAMPLED VALUE OPERATION ...
Page 126: ...Chapter 6 Sampled Value Operation P446SV 94 P446SV TM EN 1 ...
Page 136: ...Chapter 6 Sampled Value Operation P446SV 104 P446SV TM EN 1 ...
Page 137: ...CHAPTER 7 DISTANCE PROTECTION ...
Page 138: ...Chapter 7 Distance Protection P446SV 106 P446SV TM EN 1 ...
Page 196: ...Chapter 7 Distance Protection P446SV 164 P446SV TM EN 1 ...
Page 197: ...CHAPTER 8 CARRIER AIDED SCHEMES ...
Page 198: ...Chapter 8 Carrier Aided Schemes P446SV 166 P446SV TM EN 1 ...
Page 240: ...Chapter 8 Carrier Aided Schemes P446SV 208 P446SV TM EN 1 ...
Page 241: ...CHAPTER 9 NON AIDED SCHEMES ...
Page 242: ...Chapter 9 Non Aided Schemes P446SV 210 P446SV TM EN 1 ...
Page 256: ...Chapter 9 Non Aided Schemes P446SV 224 P446SV TM EN 1 ...
Page 257: ...CHAPTER 10 POWER SWING FUNCTIONS ...
Page 258: ...Chapter 10 Power Swing Functions P446SV 226 P446SV TM EN 1 ...
Page 281: ...CHAPTER 11 AUTORECLOSE ...
Page 282: ...Chapter 11 Autoreclose P446SV 250 P446SV TM EN 1 ...
Page 376: ...Chapter 11 Autoreclose P446SV 344 P446SV TM EN 1 ...
Page 377: ...CHAPTER 12 CB FAIL PROTECTION ...
Page 378: ...Chapter 12 CB Fail Protection P446SV 346 P446SV TM EN 1 ...
Page 389: ...CHAPTER 13 CURRENT PROTECTION FUNCTIONS ...
Page 390: ...Chapter 13 Current Protection Functions P446SV 358 P446SV TM EN 1 ...
Page 416: ...Chapter 13 Current Protection Functions P446SV 384 P446SV TM EN 1 ...
Page 417: ...CHAPTER 14 VOLTAGE PROTECTION FUNCTIONS ...
Page 418: ...Chapter 14 Voltage Protection Functions P446SV 386 P446SV TM EN 1 ...
Page 431: ...CHAPTER 15 FREQUENCY PROTECTION FUNCTIONS ...
Page 432: ...Chapter 15 Frequency Protection Functions P446SV 400 P446SV TM EN 1 ...
Page 438: ...Chapter 15 Frequency Protection Functions P446SV 406 P446SV TM EN 1 ...
Page 439: ...CHAPTER 16 MONITORING AND CONTROL ...
Page 440: ...Chapter 16 Monitoring and Control P446SV 408 P446SV TM EN 1 ...
Page 476: ...Chapter 16 Monitoring and Control P446SV 444 P446SV TM EN 1 ...
Page 477: ...CHAPTER 17 SUPERVISION ...
Page 478: ...Chapter 17 Supervision P446SV 446 P446SV TM EN 1 ...
Page 490: ...Chapter 17 Supervision P446SV 458 P446SV TM EN 1 ...
Page 491: ...CHAPTER 18 DIGITAL I O AND PSL CONFIGURATION ...
Page 492: ...Chapter 18 Digital I O and PSL Configuration P446SV 460 P446SV TM EN 1 ...
Page 504: ...Chapter 18 Digital I O and PSL Configuration P446SV 472 P446SV TM EN 1 ...
Page 505: ...CHAPTER 19 FIBRE TELEPROTECTION ...
Page 506: ...Chapter 19 Fibre Teleprotection P446SV 474 P446SV TM EN 1 ...
Page 522: ...Chapter 19 Fibre Teleprotection P446SV 490 P446SV TM EN 1 ...
Page 523: ...CHAPTER 20 ELECTRICAL TELEPROTECTION ...
Page 524: ...Chapter 20 Electrical Teleprotection P446SV 492 P446SV TM EN 1 ...
Page 534: ...Chapter 20 Electrical Teleprotection P446SV 502 P446SV TM EN 1 ...
Page 535: ...CHAPTER 21 COMMUNICATIONS ...
Page 536: ...Chapter 21 Communications P446SV 504 P446SV TM EN 1 ...
Page 606: ...Chapter 21 Communications P446SV 574 P446SV TM EN 1 ...
Page 607: ...CHAPTER 22 CYBER SECURITY ...
Page 608: ...Chapter 22 Cyber Security P446SV 576 P446SV TM EN 1 ...
Page 625: ...CHAPTER 23 INSTALLATION ...
Page 626: ...Chapter 23 Installation P446SV 594 P446SV TM EN 1 ...
Page 637: ...CHAPTER 24 COMMISSIONING INSTRUCTIONS ...
Page 638: ...Chapter 24 Commissioning Instructions P446SV 606 P446SV TM EN 1 ...
Page 695: ...CHAPTER 25 MAINTENANCE AND TROUBLESHOOTING ...
Page 696: ...Chapter 25 Maintenance and Troubleshooting P446SV 664 P446SV TM EN 1 ...
Page 712: ...Chapter 25 Maintenance and Troubleshooting P446SV 680 P446SV TM EN 1 ...
Page 713: ...CHAPTER 26 TECHNICAL SPECIFICATIONS ...
Page 714: ...Chapter 26 Technical Specifications P446SV 682 P446SV TM EN 1 ...
Page 741: ...APPENDIX A ORDERING OPTIONS ...
Page 742: ...Appendix A Ordering Options P446SV P446SV TM EN 1 ...
Page 744: ...Appendix A Ordering Options P446SV A2 P446SV TM EN 1 ...
Page 745: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 746: ...Appendix B Settings and Signals P446SV P446SV TM EN 1 ...
Page 954: ...Appendix B Settings and Signals P446SV B208 P446SV TM EN 1 ...
Page 955: ...APPENDIX C WIRING DIAGRAMS ...
Page 956: ...Appendix C Wiring Diagrams P446SV P446SV TM EN 1 ...
Page 960: ......
Page 961: ......