INTRODUCTION TO AUTORECLOSE
Approximately 80 - 90% of faults on transmission lines and distribution feeders are transient in nature. This means
that most faults do not last long, and are self-clearing if isolated. A common example of a transient fault is an
insulator flashover, which may be caused, for example, by lightning, clashing conductors, or wind-blown debris.
Protection functions detecting the flashover will cause one or more circuit breakers to trip and may also remove
the fault. If the source is removed, the fault does not recur if the line is re-energised.
The remaining 10 – 20% of faults are either semi-permanent or permanent. A small tree branch falling onto the
line for example, could cause a semi-permanent fault. Here the cause of the fault would not be removed by
immediate tripping of the circuit, but could possibly be burnt away during a time-delayed trip. Permanent faults
could be broken conductors, transformer faults, cable faults or machine faults, which must be located and
repaired before the power supply can be restored. In many fault incidents, if the faulty line is immediately tripped
out, and time is allowed for the fault arc to de-ionise, reclosing the circuit breakers will result in the line being
successfully re-energised.
Autoreclose schemes are used to automatically reclose a circuit breaker a set time after it has been opened due to
operation of a protection element. On EHV transmission networks, Autoreclose is usually characterised by high-
speed single-phase operation for the first attempt at reclosure. This is intended to help maintain system stability
during a transient fault condition. On HV/MV distribution networks, Autoreclose is applied mainly to radial feeders,
where system stability problems do not generally arise, and is generally characterised by delayed three-phase
operation with potentially multiple reclosure attempts.
Autoreclosing provides an important benefit on circuits using time-graded protection, in that it allows the use of
instantaneous protection to provide a high speed first trip. With fast tripping, the duration of the power arc
resulting from an overhead line fault is reduced to a minimum. This lessens the chance of damage to the line,
which might otherwise cause a transient fault to develop into a permanent fault. Using instantaneous protection
also prevents blowing of fuses in teed feeders, as well as reducing circuit breaker maintenance by eliminating pre-
arc heating. When instantaneous protection is used with Autoreclose, the scheme is normally arranged to block
the instantaneous protection after the first trip. Therefore, if the fault persists after re-closure, the time-graded
protection will provide discriminative tripping resulting in the isolation of the faulted section. However, for certain
applications, where the majority of the faults are likely to be transient, it is common practise to allow more than
one instantaneous trip before the instantaneous protection is blocked.
Some schemes allow a number of re-closures and time-graded trips after the first instantaneous trip, which may
result in the burning out and clearance of semi-permanent faults. Such a scheme may also be used to allow fuses
to operate in teed feeders where the fault current is low.
When considering feeders that are partly overhead line and partly underground cable, any decision to install
Autoreclose should be subject to analysis of the data (knowledge of the frequency of transient faults). This is
because this type of arrangement probably has a greater proportion of semi-permanent and permanent
faults than for purely overhead feeders. In this case, the advantages of Autoreclose are small. It can even be
disadvantageous because re-closing on to a faulty cable is likely to exacerbate the damage.
Chapter 11 - Autoreclose
P446SV
252
P446SV-TM-EN-1
Summary of Contents for MiCOM P40 Agile
Page 2: ......
Page 24: ...Contents P446SV xxii P446SV TM EN 1 ...
Page 33: ...CHAPTER 1 INTRODUCTION ...
Page 34: ...Chapter 1 Introduction P446SV 2 P446SV TM EN 1 ...
Page 46: ...Chapter 1 Introduction P446SV 14 P446SV TM EN 1 ...
Page 47: ...CHAPTER 2 SAFETY INFORMATION ...
Page 48: ...Chapter 2 Safety Information P446SV 16 P446SV TM EN 1 ...
Page 60: ...Chapter 2 Safety Information P446SV 28 P446SV TM EN 1 ...
Page 61: ...CHAPTER 3 HARDWARE DESIGN ...
Page 62: ...Chapter 3 Hardware Design P446SV 30 P446SV TM EN 1 ...
Page 88: ...Chapter 3 Hardware Design P446SV 56 P446SV TM EN 1 ...
Page 89: ...CHAPTER 4 SOFTWARE DESIGN ...
Page 90: ...Chapter 4 Software Design P446SV 58 P446SV TM EN 1 ...
Page 101: ...CHAPTER 5 CONFIGURATION ...
Page 102: ...Chapter 5 Configuration P446SV 70 P446SV TM EN 1 ...
Page 124: ...Chapter 5 Configuration P446SV 92 P446SV TM EN 1 ...
Page 125: ...CHAPTER 6 SAMPLED VALUE OPERATION ...
Page 126: ...Chapter 6 Sampled Value Operation P446SV 94 P446SV TM EN 1 ...
Page 136: ...Chapter 6 Sampled Value Operation P446SV 104 P446SV TM EN 1 ...
Page 137: ...CHAPTER 7 DISTANCE PROTECTION ...
Page 138: ...Chapter 7 Distance Protection P446SV 106 P446SV TM EN 1 ...
Page 196: ...Chapter 7 Distance Protection P446SV 164 P446SV TM EN 1 ...
Page 197: ...CHAPTER 8 CARRIER AIDED SCHEMES ...
Page 198: ...Chapter 8 Carrier Aided Schemes P446SV 166 P446SV TM EN 1 ...
Page 240: ...Chapter 8 Carrier Aided Schemes P446SV 208 P446SV TM EN 1 ...
Page 241: ...CHAPTER 9 NON AIDED SCHEMES ...
Page 242: ...Chapter 9 Non Aided Schemes P446SV 210 P446SV TM EN 1 ...
Page 256: ...Chapter 9 Non Aided Schemes P446SV 224 P446SV TM EN 1 ...
Page 257: ...CHAPTER 10 POWER SWING FUNCTIONS ...
Page 258: ...Chapter 10 Power Swing Functions P446SV 226 P446SV TM EN 1 ...
Page 281: ...CHAPTER 11 AUTORECLOSE ...
Page 282: ...Chapter 11 Autoreclose P446SV 250 P446SV TM EN 1 ...
Page 376: ...Chapter 11 Autoreclose P446SV 344 P446SV TM EN 1 ...
Page 377: ...CHAPTER 12 CB FAIL PROTECTION ...
Page 378: ...Chapter 12 CB Fail Protection P446SV 346 P446SV TM EN 1 ...
Page 389: ...CHAPTER 13 CURRENT PROTECTION FUNCTIONS ...
Page 390: ...Chapter 13 Current Protection Functions P446SV 358 P446SV TM EN 1 ...
Page 416: ...Chapter 13 Current Protection Functions P446SV 384 P446SV TM EN 1 ...
Page 417: ...CHAPTER 14 VOLTAGE PROTECTION FUNCTIONS ...
Page 418: ...Chapter 14 Voltage Protection Functions P446SV 386 P446SV TM EN 1 ...
Page 431: ...CHAPTER 15 FREQUENCY PROTECTION FUNCTIONS ...
Page 432: ...Chapter 15 Frequency Protection Functions P446SV 400 P446SV TM EN 1 ...
Page 438: ...Chapter 15 Frequency Protection Functions P446SV 406 P446SV TM EN 1 ...
Page 439: ...CHAPTER 16 MONITORING AND CONTROL ...
Page 440: ...Chapter 16 Monitoring and Control P446SV 408 P446SV TM EN 1 ...
Page 476: ...Chapter 16 Monitoring and Control P446SV 444 P446SV TM EN 1 ...
Page 477: ...CHAPTER 17 SUPERVISION ...
Page 478: ...Chapter 17 Supervision P446SV 446 P446SV TM EN 1 ...
Page 490: ...Chapter 17 Supervision P446SV 458 P446SV TM EN 1 ...
Page 491: ...CHAPTER 18 DIGITAL I O AND PSL CONFIGURATION ...
Page 492: ...Chapter 18 Digital I O and PSL Configuration P446SV 460 P446SV TM EN 1 ...
Page 504: ...Chapter 18 Digital I O and PSL Configuration P446SV 472 P446SV TM EN 1 ...
Page 505: ...CHAPTER 19 FIBRE TELEPROTECTION ...
Page 506: ...Chapter 19 Fibre Teleprotection P446SV 474 P446SV TM EN 1 ...
Page 522: ...Chapter 19 Fibre Teleprotection P446SV 490 P446SV TM EN 1 ...
Page 523: ...CHAPTER 20 ELECTRICAL TELEPROTECTION ...
Page 524: ...Chapter 20 Electrical Teleprotection P446SV 492 P446SV TM EN 1 ...
Page 534: ...Chapter 20 Electrical Teleprotection P446SV 502 P446SV TM EN 1 ...
Page 535: ...CHAPTER 21 COMMUNICATIONS ...
Page 536: ...Chapter 21 Communications P446SV 504 P446SV TM EN 1 ...
Page 606: ...Chapter 21 Communications P446SV 574 P446SV TM EN 1 ...
Page 607: ...CHAPTER 22 CYBER SECURITY ...
Page 608: ...Chapter 22 Cyber Security P446SV 576 P446SV TM EN 1 ...
Page 625: ...CHAPTER 23 INSTALLATION ...
Page 626: ...Chapter 23 Installation P446SV 594 P446SV TM EN 1 ...
Page 637: ...CHAPTER 24 COMMISSIONING INSTRUCTIONS ...
Page 638: ...Chapter 24 Commissioning Instructions P446SV 606 P446SV TM EN 1 ...
Page 695: ...CHAPTER 25 MAINTENANCE AND TROUBLESHOOTING ...
Page 696: ...Chapter 25 Maintenance and Troubleshooting P446SV 664 P446SV TM EN 1 ...
Page 712: ...Chapter 25 Maintenance and Troubleshooting P446SV 680 P446SV TM EN 1 ...
Page 713: ...CHAPTER 26 TECHNICAL SPECIFICATIONS ...
Page 714: ...Chapter 26 Technical Specifications P446SV 682 P446SV TM EN 1 ...
Page 741: ...APPENDIX A ORDERING OPTIONS ...
Page 742: ...Appendix A Ordering Options P446SV P446SV TM EN 1 ...
Page 744: ...Appendix A Ordering Options P446SV A2 P446SV TM EN 1 ...
Page 745: ...APPENDIX B SETTINGS AND SIGNALS ...
Page 746: ...Appendix B Settings and Signals P446SV P446SV TM EN 1 ...
Page 954: ...Appendix B Settings and Signals P446SV B208 P446SV TM EN 1 ...
Page 955: ...APPENDIX C WIRING DIAGRAMS ...
Page 956: ...Appendix C Wiring Diagrams P446SV P446SV TM EN 1 ...
Page 960: ......
Page 961: ......