48
MDS P-60/P-60 HL Reference Manual
MDS 05-2818A01, Rev. C
For continued protection, replacement fuses must be of the same size and
rating.
Be sure to disconnect primary power from the station before removing
or replacing a fuse.
5.4 Backup Battery
Backup Battery Testing
If the unit is equipped with a backup battery, the system should be tested occa-
sionally for proper backup operation. To do this, temporarily shut off the AC
power to the station and check for continued radio operation. (If possible, the
system should be tested for 30 minutes or more on backup power.) If a battery
is found to be defective, refer to
Backup Battery Replacement
below for
replacement instructions. Steps are also given later in this chapter for checking
and adjusting the battery charging rate.
Table 8. Equipment Fuses
Equipment Model
Ref Desig.
Function
Type
MDS P-60
F1, F2
Primary Power
Refer to
Table 9
F3
Transceiver Power
3AG,
Fast,
250V,
3A
F4
Battery
3AG,
Fast,
250V,
3A
F5
Accessory (Analog
boards only)
1A/3AG
MDS
P-50
F1, F2
Primary Power
2A/3AG
—
Battery Fuse
(Inline)
5A/5AG
Table 9. F1/F2 Fuses for P-60 Models
Power Supply Installed
F1/F2 Fuse Rating
12 Vdc (w/o converter)
3AG, Fast, 250V, 3A
12 Vdc (w/ converter)
3AB, Normal, 250V, 10A
24 Vdc (w/ converter)
3AG, Fast, 250V, 4A
48 Vdc (w/ converter)
3AG, Fast, 250V, 2A
125 Vdc (w/ converter)
3AG, Fast, 250V, 2A
115 Vac
3AG, Slow, 250V, 1.5A
230 Vac
3AG, Fast, 250V, 1A
Other voltages
Consult Factory