VECTOR V1100 Wireless Adapter
20
GE Oil & Gas
3. Detailed Settings
HART Dynamic Variables
The VECTOR V1100 appears as a HART device on both the wired-HART and wireless HART
networks, and supports four HART dynamic variables. These can be read using standard HART
commands and are displayed in the VECTOR V1100 DD (Table 3).
Configure Power Mode (method)
The Configure Power Mode DD Method guides you through the selection of the proper power
mode settings for their configuration.
Adapter Power
By default, the VECTOR V1100 is configured for loop powered operation with a 1.0 V insertion
voltage drop. Through the DD, the power setting can be changed (Table 4) to set the insertion
voltage drop to 1.0 V, 1.5 V, 2.0 V or 2.5 V. The power mode setting can also be set to several
different direct power modes.
Table 3 HART Dynamic Variables
HART Variable
Wireless HART Packets per Second
Primary Variable (PV)
Loop Current (mA)
Secondary Variable (SV)
Direct Power Voltage (V)
Tertiary Variable (TV)
Internal Temperature (C)
Quaternary Variable (QV)
Storage Voltage (V) (DC Bus Voltage Direct Power)
Table 4 Adapter Pow
ER
Adapter Power Setting
Wireless HART Packets per Second
Loop Powered - 1.0 V
4.25
Loop Powered - 1.5 V
12.65
Loop Powered - 2.0 V
19.66
Loop Powered - 2.5 V
26.66
Direct Powered – Max Bandwidth
101.40
Direct Powered – Power Save
26.66
Summary of Contents for Masoneilan VECTOR V1100
Page 6: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Page 37: ...37 HART DD Menu Tree Figure 2 DD Menu Tree ...
Page 38: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Page 48: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Page 50: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Page 58: ...VECTOR V1100 Wireless Adapter This page intentionally left blank ...
Page 59: ......